Configuration data
Index 8000 ENC Settings
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
8000:0 | ENC Settings | Maximum subindex | UINT8 | RO | 0x17 (23dec) |
8000:01 | The counter is reset via the C input. | BOOLEAN | RW | 0x00 (0dec) | |
8000:03 | Enablement of the up/down counter in place of the encoder with the bit set. | BOOLEAN | RW | 0x00 (0dec) | |
8000:08 | Disable filter | 0: Activates the input filter (inputs A, /A, B, /B, C, /C only) | BOOLEAN | RW | 0x01 (1dec) |
8000:0A | If DC mode is activated, the Box interpolates micro-increments between the integer encoder increments. The lower 8 bits of the Counter Value are used in each case for the display. A 32-bit counter thus becomes a 24+8-bit counter, a 16-bit counter becomes an 8+8-bit counter. | BOOLEAN | RW | 0x00 (0dec) | |
8000:0B | An open circuit on track A is indicated in object Open circuit (index 0x6000:07) and as a process data. Diagnosis is only possible if the corresponding input is wired differentially. A differential voltage < 3.5 V (typical, subject to change) is detected as a broken wire. | BOOLEAN | RW | 0x01 (1dec) | |
8000:0C | An open circuit on track B is indicated in object Open circuit (index 0x6000:07) and as a process data. Diagnosis is only possible if the corresponding input is wired differentially. A differential voltage < 3.5 V (typical, subject to change) is detected as a broken wire. | BOOLEAN | RW | 0x01 (1dec) | |
8000:0D | An open circuit on track C is indicated in object Open circuit (index 0x6000:07) and as a process data. Diagnosis is only possible if the corresponding input is wired differentially. A differential voltage < 3.5 V (typical, subject to change) is detected as a broken wire. | BOOLEAN | RW | 0x00 (0dec) | |
8000:0E | Activates reversion of rotation | BOOLEAN | RW | 0x00 (0dec) | |
8000:11 | This is the minimum time over which the frequency is determined; default value 10 ms [resolution: 1 µs]. | UINT16 | RW | 0x2710 (10000dec) | |
8000:13 | Scaling of the frequency measurement (must be divided by this value to obtain the unit in Hz): 100: “0.01 Hz” | UINT16 | RW | 0x0064 (100dec) | |
8000:14 | Resolution of the period value in the process data: 100: “100 ns” period value is a multiple of 100 ns | UINT16 | RW | 0x0064 (100dec) | |
8000:15 | Resolution of the frequency measurement: 100: “0.01 Hz” | UINT16 | RW | 0x0064 (100dec) | |
8000:16 | Internal resolution of the period value measurement: 100: “100 ns” period value is a multiple of 100 ns 500: “500 ns” period value is a multiple of 500 ns | UINT16 | RW | 0x0064 (100dec) |