Objects for parameterization
Index 1011 Restore default parameters
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
1011:0 | Restore default parameters | Restore default parameters | UINT8 | RO | 0x01 (1dec) |
1011:01 | SubIndex 001 | If this object is set to "0x64616F6C" in the set value dialog, all backup objects are reset to their delivery state. | UINT32 | RW | 0x00000000 (0dec) |
Index 8000 DPO Settings Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
8000:0 | DPO Settings Ch.1 |
| UINT8 | RO | 0x16 (22dec) |
8000:02 | Default State Us | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8000:03 | Default State Up | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8000:04 | Enable Sum Current Limitation | Activates the overcurrent protection for the sum current Us+Up on this output. See chapter Overcurrent protection for sum currents. | BOOLEAN | RW | 0x00 (0dec) |
8000:11 | Characteristic | Tripping characteristics of the overload switch-off:
See chapter Overload protection. | UINT16 | RW | 0x0001 (1dec) |
8000:12 | Nominal Current Us | Nominal current for US. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8000:13 | Nominal Current Up | Nominal current for UP. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8000:14 | Nominal Sum Current | Nominal maximum sum current (Us+Up) at the output. See chapter Overcurrent protection for sum currents. | UINT16 | RW | 0x1770 (6000dec) |
8000:15 | Timestamp 1 Trigger | Defines which events are detected by the peak value detector at this port. Possible values:
See chapter Peak value detector. | UINT16 | RW | 0x0000 (0dec) |
8000:16 | Timestamp 2 Trigger | See 8000:15. | UINT16 | RW | 0x0000 (0dec) |
Index 8010 DPO Settings Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
8010:0 | DPO Settings Ch.2 |
| UINT8 | RO | 0x16 (22dec) |
8010:02 | Default State Us | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8010:03 | Default State Up | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8010:04 | Enable Sum Current Limitation | Activates the overcurrent protection for the sum current Us+Up on this output. See chapter Overcurrent protection for sum currents. | BOOLEAN | RW | 0x00 (0dec) |
8010:11 | Characteristic | Tripping characteristics of the overload switch-off:
See chapter Overload protection. | UINT16 | RW | 0x0001 (1dec) |
8010:12 | Nominal Current Us | Nominal current for US. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8010:13 | Nominal Current Up | Nominal current for UP. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8010:14 | Nominal Sum Current | Nominal maximum sum current (Us+Up) at the output. See chapter Overcurrent protection for sum currents. | UINT16 | RW | 0x1770 (6000dec) |
8010:15 | Timestamp 1 Trigger | Defines which events are detected by the peak value detector at this port. Possible values:
See chapter Peak value detector. | UINT16 | RW | 0x0000 (0dec) |
8010:16 | Timestamp 2 Trigger | See 8010:15. | UINT16 | RW | 0x0000 (0dec) |
Index 8020 DPO Settings Ch.3
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
8020:0 | DPO Settings Ch.3 |
| UINT8 | RO | 0x16 (22dec) |
8020:02 | Default State Us | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8020:03 | Default State Up | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8020:04 | Enable Sum Current Limitation | Activates the overcurrent protection for the sum current Us+Up on this output. See chapter Overcurrent protection for sum currents. | BOOLEAN | RW | 0x00 (0dec) |
8020:11 | Characteristic | Tripping characteristics of the overload switch-off:
See chapter Overload protection. | UINT16 | RW | 0x0001 (1dec) |
8020:12 | Nominal Current Us | Nominal current for US. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8020:13 | Nominal Current Up | Nominal current for UP. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8020:14 | Nominal Sum Current | Nominal maximum sum current (Us+Up) at the output. See chapter Overcurrent protection for sum currents. | UINT16 | RW | 0x1770 (6000dec) |
8020:15 | Timestamp 1 Trigger | Defines which events are detected by the peak value detector at this port. Possible values:
See chapter Peak value detector. | UINT16 | RW | 0x0000 (0dec) |
8020:16 | Timestamp 2 Trigger | See 8020:15 | UINT16 | RW | 0x0000 (0dec) |
Index 8030 DPO Settings Ch.4
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
8030:0 | DPO Settings Ch.4 |
| UINT8 | RO | 0x16 (22dec) |
8030:02 | Default State Us | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8030:03 | Default State Up | The output assumes this value if F707:01 "Enable Control Via Fieldbus" is not set. See chapter Switch output voltages. | BOOLEAN | RW | 0x01 (1dec) |
8030:04 | Enable Sum Current Limitation | Activates the overcurrent protection for the sum current Us+Up on this output. See chapter Overcurrent protection for sum currents. | BOOLEAN | RW | 0x00 (0dec) |
8030:11 | Characteristic | Tripping characteristics of the overload switch-off:
See chapter Overload protection. | UINT16 | RW | 0x0001 (1dec) |
8030:12 | Nominal Current Us | Nominal current for US. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8030:13 | Nominal Current Up | Nominal current for UP. Unit: mA Value range: 1000 ... 3000dec See chapter Overload protection. | UINT16 | RW | 0x0BB8 (3000dec) |
8030:14 | Nominal Sum Current | Nominal maximum sum current (Us+Up) at the output. See chapter Overcurrent protection for sum currents. | UINT16 | RW | 0x1770 (6000dec) |
8030:15 | Timestamp 1 Trigger | Defines which events are detected by the peak value detector at this port. Possible values:
See chapter Peak value detector. | UINT16 | RW | 0x0000 (0dec) |
8030:16 | Timestamp 2 Trigger | See 8030:15 | UINT16 | RW | 0x0000 (0dec) |
Index 8040 LOG Settings
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
8040:0 | LOG Settings |
| UINT8 | RO | 0x11 (17dec) |
8040:11 | Sampling Rate | Sampling rate of the data logger
See chapter Data logger. | UINT16 | RW | 0x000A (10dec) |
Index F707 DPO Outputs Device
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
707F:0 | DPO Outputs Device |
| UINT8 | RO | 0x11 (17dec) |
F707:01 | Enable Control Via Fieldbus | 0bin: All outputs are set according to their default values (80n0:02, 80n0:03) 1bin: All outputs are set according to their PDOs (70n0:01, 70n0:02) See chapter Switch output voltages. | BOOLEAN | RO | 0x00 (0dec) |
707F:04 | Global Reset | Reset all errors. | BOOLEAN | RO | 0x00 (0dec) |
707F:11 | Reset Extended Diag Data | Reset all values of the peak value detector. See chapter Peak value detector. | BOOLEAN | RO | 0x00 (0dec) |
Index F80E DPO Settings Device
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
F80E:0 | DPO Settings Device |
| UINT8 | RO | 0x16 (22dec) |
F80E:02 | Enable Sum Current Limitation | Enables the overcurrent protection for the sum current ∑ US + ∑ UP. | BOOLEAN | RW | 0x00 (0dec) |
F80E:05 | Disable Up Undervoltage Error | Disables the undervoltage protection for the peripheral voltage UP. | BOOLEAN | RW | 0x00 (0dec) |
F80E:11 | Startup Delay | Sets the time that is kept between two switch-on procedures:
| UINT16 | RW | 0x0001 (1dec) |
F80E:12 | Nominal Sum Current | Nominal maximum current for the sum current. | INT16 | RW | 0x5DC0 (24000dec) |
F80E:13 | Sum Current Characteristic | Specifies the characteristic with which the current monitoring reacts:
| UINT16 | RW | 0x0001 (1dec) |
F80E:15 | Timestamp 1 Trigger | Defines which events are detected by the peak value detector. Possible values:
See chapter Peak value detector. | UINT16 | RW | 0x0000 (0dec) |
F80E:16 | Timestamp 2 Trigger | See F80E:15. | UINT16 | RW | 0x0000 (0dec) |