Digital inputs / outputs

Each channel can be operated either as a digital input or as a digital output.

M8 sockets X01, X02, X05, X06

Digital inputs / outputs 1:

Pin

Core color 1)

Function

Designation in ZPA operation

X01

X02

X05

X06

1

brown

US1: 24 V DC output

-

-

-

-

2

white

Input B / output B 2)

Input 2 /

Output 2

Control Input 2 /

Control Output 2

Input 4 /

Output 4

Control Input 4 /

Control Output 4

3

blue

GNDS

-

-

-

-

4

black

Input A / output A 2)

Input 1 /

Output 1

Control Input 1 /

Control Output 1

Input 3 /

Output 3

Control Input 3 /

Control Output 3

1) The core colors apply to cables of the type ZK2000-3xxx. See chapter Accessories.

2) See Assignment to process data.