Vendor calibration

Each analog output is calibrated in the factory. The results of the calibration are the coefficients of a correction function. The correction function is:

 

YV = GV * XV + OV

YV: Output value after vendor calibration

XV: Output value before vendor calibration

GV : Gain of the vendor calibration

OV : Offset of the vendor calibration

The coefficients GV and OV cannot be changed by the user. If you wish to carry out a calibration yourself, use the user calibration.

You will find the coefficients for the different output signal ranges in the following CoE objects:

Connection

CoE object (read only)

X01

814Fhex

AO Vendor data Ch.1

X02

815Fhex

AO Vendor data Ch.2

X05

816Fhex

AO Vendor data Ch.3

X06

817Fhex

AO Vendor data Ch.4

Disabling the vendor calibration

Notice

Output error with disabled vendor calibration

The output error specified in the technical data is no longer provided if you disable the vendor calibration.

If you use the user calibration, it may be a good idea to disable the vendor calibration.

Set the relevant "Enable vendor calibration" CoE parameters to FALSE to disable the vendor calibration for the respective output.

Connection

"Enable vendor calibration"

X01

0x8130:08

X02

0x8140:08