Measured value resolution

You can set the resolution of the measured values for each acceleration axis individually.

Notice

Interactions with other parameters

Certain combinations of parameter values can cause individual settings to become ineffective without being noticed.

  • Consider the following interactions of the measured value resolution with other parameters:

Setting the measured value resolution

The resolution of the measured values is determined by the following parameters:

The following table shows the possible combinations of the two parameters and the resulting measured value resolution.

"Enable Vendor Calibration"

"Range"

Measured value resolution

TRUE (factory setting)

variable

1 mg/LSB

FALSE

0

+-2G

1/256 mg/LSB

FALSE

1

+-4G

1/128 mg/LSB

FALSE

2

+-8G

1/64 mg/LSB

Measured value resolution 1:

Measured value noise

If “Enable vendor calibration” is FALSE, the noise power density increases with a larger measuring range. See chapter Measured value noise.