Input data

Index 6000 FB Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6000:0

FB Inputs Ch.1

 

UINT8

RO

0x11 (17dec)

6000:0E

TxPDO State

TRUE: the position data is invalid.

FALSE: the position data is valid.

BOOLEAN

RO

0x00 (0dec)

6000:0F

Input cycle counter

Incremented with each process data cycle, switches to 0 after reaching the maximum value of 3.

BIT2

RO

0x00 (0dec)

6000:11

Position

Position

UINT32

RO

0x00000000 (0dec)

Index 6001 FB Touch probe inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6001:0

FB Touch probe inputs Ch.1

 

UINT8

RO

0x18 (24dec)

6001:01

TP1 Enable

Touch probe 1 switched on

BOOLEAN

RO

0x00 (0dec)

6001:02

TP1 Pos value stored

Positive value of Touch probe 1 stored

BOOLEAN

RO

0x00 (0dec)

6001:03

TP1 Neg value stored

Negative value of Touch probe 1 stored

BOOLEAN

RO

0x00 (0dec)

6001:08

TP1 Input

Digital inputs Touch probe 1.

The input must be addressed with a single conductor + 24 V signal.

BOOLEAN

RO

0x00 (0dec)

6001:09

TP2 Enable

Touch probe 2 switched on

BOOLEAN

RO

0x00 (0dec)

6001:0A

TP2 Pos value stored

Positive value of Touch probe 2 stored

BOOLEAN

RO

0x00 (0dec)

6001:0B

TP2 Neg value stored

Negative value of Touch probe 2 stored

BOOLEAN

RO

0x00 (0dec)

6001:10

TP2 Input

Digital input Touch probe 2.

The input must be addressed with a single conductor + 24 V signal.

BOOLEAN

RO

0x00 (0dec)

6001:11

TP1 Pos position

Positive value of Touch probe 1.

Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6001:12

TP1 Neg position

Negative value of Touch probe 1.
Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6001:13

TP2 Pos position

Positive value of Touch probe 2.
Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6001:14

TP2 Neg position

Negative value of Touch probe 2.

Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6001:15

TP1 Pos timestamp

DC timestamp at which the last positive edge was detected on Touch probe 1.

UINT32

RO

0x00000000 (0dec)

6001:16

TP1 Neg timestamp

DC timestamp at which the last negative edge was detected on Touch probe 1.

UINT32

RO

0x00000000 (0dec)

6001:17

TP2 Pos timestamp

DC timestamp at which the last positive edge was detected on Touch probe 2.

UINT32

RO

0x00000000 (0dec)

6001:18

TP2 Neg timestamp

DC timestamp at which the last negative edge was detected on Touch probe 2.

UINT32

RO

0x00000000 (0dec)

Index 6010 DRV Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6010:0

DRV Inputs Ch.1

 

UINT8

RO

0x15 (21dec)

6010:01

Statusword

Bit 0: Ready to switch on

Bit 1: Switched on

Bit 2: Operation enabled

Bit 3: Fault

Bit 4: reserved

Bit 5: reserved

Bit 6: Switch on disabled

Bit 7: Warning

Bit 8 + 9: reserved

Bit 10: TxPDOToggle
     (Switch on via 0x8010:01)

Bit 11: Internal limit active

Bit 12: Drive follows the command value

Bit 13: Input cycle counter

Bit 14 - 15: reserved

UINT16

RO

0x0000 (0dec)

6010:03

Modes of operation display

Modes of operation display.

Possible values:

  • 8: Cyclic synchronous position mode (CSP)
  • 9: Cyclic synchronous velocity mode (CSV)
  • 10: Cyclic synchronous torque mode (CST)
  • 11: Cyclic synchronous torque mode with commutation angle (CSTCA)
  • 131: Drive Motion Control (DMC)

UINT8

RO

0x00 (0dec)

6010:06

Following error actual value

Following error.

Unit: the given value must be multiplied by the corresponding scaling factor.

INT32

RO

0x00000000 (0dec)

6010:07

Velocity actual value

Display of the current velocity value.

Unit: see 0x9010:14.

INT32

RO

0x00000000 (0dec)

6010:08

Torque actual value

Display of the current torque value
The value is given in 1000ths of the "Rated current" (0x8011:12).

Calculation formula:
M = ((Torque actual value / 1000) x rated current)) x torque constant (0x8011:16)

INT16

RO

0x0000 (0dec)

6010:12

Info data 1

Synchronous information.

Selection via 0x8010:39.

UINT16

RO

0x0000 (0dec)

6010:13

Info data 2

Synchronous information.

Selection via 0x8010:3A.

UINT16

RO

0x0000 (0dec)

6010:14

Info data 3

Synchronous information.

Selection via 0x8010:58.

UINT16

RO

0x0000 (0dec)

6010:15

Torque limitation status

Bit 0: Torque demand value is equal to ramp input

Bit 1: High velocity limit active

Bit 2: Low velocity limit active

Bit 3 - 7: reserved

UINT8

RO

0x00 (0dec)

Index 6020 DMC Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6020:0

DMC Inputs Ch.1

 

UINT8

RO

0x3C (60dec)

6020:02

DMC__FeedbackStatus__Latch extern valid

An edge was detected on the external input and latched.

BOOLEAN

RO

0x00 (0dec)

6020:03

DMC__FeedbackStatus__Set counter done

The setting of the feedback position was successful.

This bit remains present until "Set counter" is released again

BOOLEAN

RO

0x00 (0dec)

6020:0D

DMC__FeedbackStatus__Status of extern latch

Status of the external latch input.

BOOLEAN

RO

0x00 (0dec)

6020:11

DMC__DriveStatus__Ready to enable

The drive hardware is ready for activation.

BOOLEAN

RO

0x00 (0dec)

6020:12

DMC__DriveStatus__Ready

The drive hardware is activated.

BOOLEAN

RO

0x00 (0dec)

6020:13

DMC__DriveStatus__Warning

A warning is pending in the drive.

BOOLEAN

RO

0x00 (0dec)

6020:14

DMC__DriveStatus__Error

An error is pending in the drive.

The "Ready to enable" bit and the "Ready" bit are set to FALSE.

BOOLEAN

RO

0x00 (0dec)

6020:15

DMC__DriveStatus__Moving positive

The axis moves in positive direction.

BOOLEAN

RO

0x00 (0dec)

6020:16

DMC__DriveStatus__Moving negative

The axis moves in negative direction.

BOOLEAN

RO

0x00 (0dec)

6020:1C

DMC__DriveStatus__Digital input 1

Status of the first digital input.

BOOLEAN

RO

0x00 (0dec)

6020:1D

DMC__DriveStatus__Digital input 2

Status of the second digital input.

BOOLEAN

RO

0x00 (0dec)

6020:21

DMC__PositioningStatus__Busy

The positioning task is running.

BOOLEAN

RO

0x00 (0dec)

6020:22

DMC__PositioningStatus__In-Target

The axis is at the target position.

BOOLEAN

RO

0x00 (0dec)

6020:23

DMC__PositioningStatus__Warning

Warning.

BOOLEAN

RO

0x00 (0dec)

6020:24

DMC__PositioningStatus__Error

Error.

BOOLEAN

RO

0x00 (0dec)

6020:25

DMC__PositioningStatus__Calibrated

The axis is calibrated.

BOOLEAN

RO

0x00 (0dec)

6020:26

DMC__PositioningStatus__Accelerate

The axis accelerates.

BOOLEAN

RO

0x00 (0dec)

6020:27

DMC__PositioningStatus__Decelerate

The axis is decelerating.

BOOLEAN

RO

0x00 (0dec)

6020:28

DMC__PositioningStatus__Ready to execute

The path control is ready to accept a command.

This bit is FALSE …

  • ... if the drive has a fault
  • ... if the drive is not activated
  • ... as long as the "PositioningControl__Execute" is pending.

BOOLEAN

RO

0x00 (0dec)

6020:31

DMC__Set position

Current target position specified by the ramp generator in feedback increments.

INT64

RO

 

6020:32

DMC__Set velocity

Current velocity specified by the ramp generator in 10000ths of the nominal motor speed

INT16

RO

0x0000 (0dec)

6020:33

DMC__Actual drive time

The time since the start of the travel command in ms.

Stops when the target position is reached.

UINT32

RO

0x00000000 (0dec)

6020:34

DMC__Actual position lag

Following error.

INT64

RO

 

6020:35

DMC__Actual velocity

Current velocity in 10000ths of the nominal motor speed.

INT16

RO

0x0000 (0dec)

6020:36

DMC__Actual position

Current position from the feedback (incl. possible offsets due to homing, ...).

INT64

RO

 

6020:37

DMC__Error id

Error Id (identical to Diag History).

UINT32

RO

0x00000000 (0dec)

6020:38

DMC__Input cycle counter

Incremented with each process data cycle.

UINT8

RO

0x00 (0dec)

6020:39

DMC__Channel id

 

UINT8

RO

0x00 (0dec)

6020:3A

DMC__Latch value

Feedback position at latch time.

INT64

RO

 

6020:3B

DMC__Cyclic info data 1

Synchronous info data

INT16

RO

0x0000 (0dec)

6020:3C

DMC__Cyclic info data 2

Synchronous info data

INT16

RO

0x0000 (0dec)

Index 6100 FB Inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6100:0

FB Inputs Ch.2

 

UINT8

RO

0x11 (17dec)

6100:0E

TxPDO State

TRUE: the position data is invalid.

FALSE: the position data is valid.

BOOLEAN

RO

0x00 (0dec)

6100:0F

Input cycle counter

Incremented with each process data cycle, switches to 0 after reaching the maximum value of 3.

BIT2

RO

0x00 (0dec)

6100:11

Position

Position

UINT32

RO

0x00000000 (0dec)

Index 6101 FB Touch probe inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6101:0

FB Touch probe inputs Ch.2

 

UINT8

RO

0x18 (24dec)

6101:01

TP1 Enable

Touch probe 1 switched on

BOOLEAN

RO

0x00 (0dec)

6101:02

TP1 Pos value stored

Positive value of Touch probe 1 stored

BOOLEAN

RO

0x00 (0dec)

6101:03

TP1 Neg value stored

Negative value of Touch probe 1 stored

BOOLEAN

RO

0x00 (0dec)

6101:08

TP1 Input

Digital inputs Touch probe 1.

The input must be addressed with a single conductor + 24 V signal.

BOOLEAN

RO

0x00 (0dec)

6101:09

TP2 Enable

Touch probe 2 switched on

BOOLEAN

RO

0x00 (0dec)

6101:0A

TP2 Pos value stored

Positive value of Touch probe 2 stored

BOOLEAN

RO

0x00 (0dec)

6101:0B

TP2 Neg value stored

Negative value of Touch probe 2 stored

BOOLEAN

RO

0x00 (0dec)

6101:10

TP2 Input

Digital input Touch probe 2.

The input must be addressed with a single conductor + 24 V signal.

BOOLEAN

RO

0x00 (0dec)

6101:11

TP1 Pos position

Positive value of Touch probe 1.

Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6101:12

TP1 Neg position

Negative value of Touch probe 1.
Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6101:13

TP2 Pos position

Positive value of Touch probe 2.
Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6101:14

TP2 Neg position

Negative value of Touch probe 2.

Unit: the given value must be multiplied by the corresponding scaling factor.

UINT32

RO

0x00000000 (0dec)

6101:15

TP1 Pos timestamp

DC timestamp at which the last positive edge was detected on Touch probe 1.

UINT32

RO

0x00000000 (0dec)

6101:16

TP1 Neg timestamp

DC timestamp at which the last negative edge was detected on Touch probe 1.

UINT32

RO

0x00000000 (0dec)

6101:17

TP2 Pos timestamp

DC timestamp at which the last positive edge was detected on Touch probe 2.

UINT32

RO

0x00000000 (0dec)

6101:18

TP2 Neg timestamp

DC timestamp at which the last negative edge was detected on Touch probe 2.

UINT32

RO

0x00000000 (0dec)

Index 6110 DRV Inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6110:0

DRV Inputs Ch.2

 

UINT8

RO

0x15 (21dec)

6110:01

Statusword

Bit 0: Ready to switch on

Bit 1: Switched on

Bit 2: Operation enabled

Bit 3: Fault

Bit 4: reserved

Bit 5: reserved

Bit 6: Switch on disabled

Bit 7: Warning

Bit 8 + 9: reserved

Bit 10: TxPDOToggle
     (Switch on via 0x8110:01)

Bit 11: Internal limit active

Bit 12: Drive follows the command value

Bit 13: Input cycle counter

Bit 14 - 15: reserved

UINT16

RO

0x0000 (0dec)

6110:03

Modes of operation display

Modes of operation display.

Possible values:

  • 8: Cyclic synchronous position mode (CSP)
  • 9: Cyclic synchronous velocity mode (CSV)
  • 10: Cyclic synchronous torque mode (CST)
  • 11: Cyclic synchronous torque mode with commutation angle (CSTCA)
  • 131: Drive Motion Control (DMC)

UINT8

RO

0x00 (0dec)

6110:06

Following error actual value

Following error.

Unit: the given value must be multiplied by the corresponding scaling factor.

INT32

RO

0x00000000 (0dec)

6110:07

Velocity actual value

Display of the current velocity value.

Unit: see 0x9110:14.

INT32

RO

0x00000000 (0dec)

6110:08

Torque actual value

Display of the current torque value
The value is given in 1000ths of the "Rated current" (0x8111:12).

Calculation formula:
M = ((Torque actual value / 1000) x rated current)) x torque constant (0x8111:16)

INT16

RO

0x0000 (0dec)

6110:12

Info data 1

Synchronous information.

Selection via 0x8110:39.

UINT16

RO

0x0000 (0dec)

6110:13

Info data 2

Synchronous information.

Selection via 0x8110:3A.

UINT16

RO

0x0000 (0dec)

6110:14

Info data 3

Synchronous information.

Selection via 0x8110:58.

UINT16

RO

0x0000 (0dec)

6110:15

Torque limitation status

Bit 0: Torque demand value is equal to ramp input

Bit 1: High velocity limit active

Bit 2: Low velocity limit active

Bit 3 - 7: reserved

UINT8

RO

0x00 (0dec)

Index 6120 DMC Inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6120:0

DMC Inputs Ch.2

 

UINT8

RO

0x3C (60dec)

6120:02

DMC__FeedbackStatus__Latch extern valid

An edge was detected on the external input and latched.

BOOLEAN

RO

0x00 (0dec)

6120:03

DMC__FeedbackStatus__Set counter done

The setting of the feedback position was successful.

This bit remains present until "Set counter" is released again

BOOLEAN

RO

0x00 (0dec)

6120:0D

DMC__FeedbackStatus__Status of extern latch

Status of the external latch input.

BOOLEAN

RO

0x00 (0dec)

6120:11

DMC__DriveStatus__Ready to enable

The drive hardware is ready for activation.

BOOLEAN

RO

0x00 (0dec)

6120:12

DMC__DriveStatus__Ready

The drive hardware is activated.

BOOLEAN

RO

0x00 (0dec)

6120:13

DMC__DriveStatus__Warning

A warning is pending in the drive.

BOOLEAN

RO

0x00 (0dec)

6120:14

DMC__DriveStatus__Error

An error is pending in the drive.

The "Ready to enable" bit and the "Ready" bit are set to FALSE.

BOOLEAN

RO

0x00 (0dec)

6120:15

DMC__DriveStatus__Moving positive

The axis moves in positive direction.

BOOLEAN

RO

0x00 (0dec)

6120:16

DMC__DriveStatus__Moving negative

The axis moves in negative direction.

BOOLEAN

RO

0x00 (0dec)

6120:1C

DMC__DriveStatus__Digital input 1

Status of the first digital input.

BOOLEAN

RO

0x00 (0dec)

6120:1D

DMC__DriveStatus__Digital input 2

Status of the second digital input.

BOOLEAN

RO

0x00 (0dec)

6120:21

DMC__PositioningStatus__Busy

The positioning task is running.

BOOLEAN

RO

0x00 (0dec)

6120:22

DMC__PositioningStatus__In-Target

The axis is at the target position.

BOOLEAN

RO

0x00 (0dec)

6120:23

DMC__PositioningStatus__Warning

Warning.

BOOLEAN

RO

0x00 (0dec)

6120:24

DMC__PositioningStatus__Error

Error.

BOOLEAN

RO

0x00 (0dec)

6120:25

DMC__PositioningStatus__Calibrated

The axis is calibrated.

BOOLEAN

RO

0x00 (0dec)

6120:26

DMC__PositioningStatus__Accelerate

The axis accelerates.

BOOLEAN

RO

0x00 (0dec)

6120:27

DMC__PositioningStatus__Decelerate

The axis is decelerating.

BOOLEAN

RO

0x00 (0dec)

6120:28

DMC__PositioningStatus__Ready to execute

The path control is ready to accept a command.

This bit is FALSE …

  • ... if the drive has a fault
  • ... if the drive is not activated
  • ... as long as the "PositioningControl__Execute" is pending.

BOOLEAN

RO

0x00 (0dec)

6120:31

DMC__Set position

Current target position specified by the ramp generator in feedback increments.

INT64

RO

 

6120:32

DMC__Set velocity

Current velocity specified by the ramp generator in 10000ths of the nominal motor speed

INT16

RO

0x0000 (0dec)

6120:33

DMC__Actual drive time

The time since the start of the travel command in ms.

Stops when the target position is reached.

UINT32

RO

0x00000000 (0dec)

6120:34

DMC__Actual position lag

Following error.

INT64

RO

 

6120:35

DMC__Actual velocity

Current velocity in 10000ths of the nominal motor speed.

INT16

RO

0x0000 (0dec)

6120:36

DMC__Actual position

Current position from the feedback (incl. possible offsets due to homing, ...).

INT64

RO

 

6120:37

DMC__Error id

Error Id (identical to Diag History).

UINT32

RO

0x00000000 (0dec)

6120:38

DMC__Input cycle counter

Incremented with each process data cycle.

UINT8

RO

0x00 (0dec)

6120:39

DMC__Channel id

 

UINT8

RO

0x00 (0dec)

6120:3A

DMC__Latch value

Feedback position at latch time.

INT64

RO

 

6120:3B

DMC__Cyclic info data 1

Synchronous info data

INT16

RO

0x0000 (0dec)

6120:3C

DMC__Cyclic info data 2

Synchronous info data

INT16

RO

0x0000 (0dec)

Index F600 DRV Brake Chopper Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

F600:0

DRV Brake Chopper Inputs

 

UINT8

RO

0x12 (18dec)

F600:03

Brake chopper I2T warning

I2T model at least "Brake resistor power warning threshold" utilized

BOOLEAN

RO

0x00 (0dec)

F600:06

Brake chopper on

Braking resistor was switched on at least once in the last process data cycle

BOOLEAN

RO

0x00 (0dec)

F600:11

Brake chopper dutycycle

Proportion of the time of the last process data cycle in which the braking resistor was active (without further filters).

Unit: percent

UINT8

RO

0x00 (0dec)

F600:12

Brake chopper I2T utilisation

Utilization of the I2T model of the brake chopper.

Unit: percent

UINT8

RO

0x00 (0dec)