EL9250, EL9260 - Introduction and Technical Data

Power supply terminals, 230 V AC

EL9250, EL9260 - Introduction and Technical Data 1:
Fig.33: EL9250, EL9260

The EL9250 and EL9260 power supply terminals can be placed at any position between the input/output terminals to create an additional potential group or to supply the terminals to the right with higher currents in case of high current loads.

The E-bus will pass through.

Unlike the EL9250, the EL9260 has diagnostics displayed in the process image.

The power supply is protected with a 6.3 A fine-wire fuse at all terminals.

Technical data

Technical data

EL9250

EL9260

Nominal voltage

230 V AC

Power contact current load

max. 10 A

Electrical isolation

500 V (E-bus/field voltage)

Built-in fine-wire fuse

yes; 6.3 A (see also UL note!)

Current consumption via E-bus

-

typ. 90 mA

Bit width in process image

-

2 diagnostic bits (PowerOK; FuseError)

Configuration

no address or configuration settings required

Power LED

yes

yes

Diagnostics (fuse)

yes, error-LED

yes, in the process image and error-LED

Electrical connection to mounting rail

no

Renewed infeed

yes

Connection facility to additional power contact

1

Side by side mounting on EtherCAT Terminals with power contact

yes

Side by side mounting on EtherCAT Terminals without power contact

yes

Weight

approx. 55 g

Permissible ambient temperature range during operation

0 °C ... +55 °C

Permissible ambient temperature range during storage

-25 °C ... +85 °C

Operating altitude

max. 2000 m

Overvoltage category

II

Pollution degree

2

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Installation

on 35 mm mounting rail, conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable, see chapter Mounting of passive terminals

variable

Approvals / markings*

CE, UKCA, EAC

*) Real applicable approvals/markings see type plate on the side (product marking).

EL9250, EL9260 connection

CAUTION

Danger for persons and equipment!

  • In the project planning of the bus terminal system, observe the different potentials on the power contacts (24 V DC and 230 V AC) and if necessary use potential separation terminals (EL9080) to isolate the potentials!
  • Bring the bus terminal system into a safe, de-energized state before starting installation, disassembly or wiring of the terminal modules!
EL9250, EL9260 - Introduction and Technical Data 2:
Fig.33: Connection - EL9250, EL9260

Terminal point

Description

Name

No.

230 V AC

1

Supply input 230 V AC;
internally connected to terminal point 4 and power contact 230 V AC

N

2

N;
internally connected to terminal point 5 and neutral conductor power contact

⏚

3

Ground (internally connected to terminal point 6 and power contact ground)

230 V AC

4

Supply input 230 V AC;
internally connected to terminal point 1 and power contact 230 V AC

N

5

N;
internally connected to terminal point 2 and neutral conductor power contact

⏚

6

Ground (internally connected to terminal point 3 and power contact ground)

LEDs

LED

Color

Meaning

Power LED

green

off

No supply voltage

on

230 V AC at the supply input

Error LED

red

off

Fuse OK

on

Fuse defective

Process data (EL9260 only)

The EL9260 has a bit width of 2 bits (diagnostic bit for voltage at the power contacts, "PowerOK" and diagnostic bit for defective fuse; "FuseError") in the process image and is represented in the TwinCAT tree as follows:

EL9250, EL9260 - Introduction and Technical Data 3:
Fig.35: EL9260 in the TwinCAT tree

If there is no voltage at the power contacts, the corresponding diagnostic bit "PowerOK" is set to FALSE (0).
If the fuse is defective, the corresponding diagnostic bit "FuseError" is set to TRUE (1).