UL notice
| 
 | ||
|  | Application Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT System only. | |
| 
 | ||
|  | Examination For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire and electrical shock (in accordance with UL508 and CSA C22.2 No. 142). | |
| 
 | ||
|  | For devices with Ethernet connectors Not for connection to telecommunication circuits. | |
| 
 | ||
|  | Usage of suitable copper cables In order to comply with UL approval, use copper cables that are designed for operating temperatures >= 90°C. | |
| 
 | ||
|  | External overcurrent protection External overcurrent protection is required for each input exceeding levels of 30Vrms, 42.4Vpeak or 60Vdc. | |
| 
 | ||
|  | Operating of the Beckhoff Terminal EL9260 with Beckhoff Terminal EL1702-0020 Fuses have to be specified as 250Vac/6.3A/size 20x5.2mm as all of these parameters are critical for safety. | |
Basic principles
UL certification according to UL508. Devices with this kind of certification are marked by this sign:

