EL9150, EL9160 - Introduction and Technical Data

Power supply terminals, 230 V AC

EL9150, EL9160 - Introduction and Technical Data 1:

EL9150, EL9160

The EL9150 power supply terminal can be positioned at any location between the input and output terminals, for establishing a further potential group, or for supplying the terminals following on the right in applications with high current load. The E-bus will pass through.

Unlike the EL9150, the EL9160 has diagnostics displayed in the process image.

Technical data

Technical data

EL9150

EL9160

Nominal voltage

230 VAC (120 VAC)

Power contact current load

max. 10 A

Electrical isolation

500 V (E-bus/field voltage)

Current consumption via E-bus

-

typ. 90 mA

Bit width in process image

0

1 diagnostic bit

Configuration

no address or configuration settings required

Power LED

yes

Diagnostics

no

yes, in the process image

Electrical connection to mounting rail

no

Renewed infeed

yes

Connection facility to additional power contact

1

Side by side mounting on EtherCAT Terminals with power contact

yes

Side by side mounting on EtherCAT Terminals without power contact

yes

Weight

approx. 50 g

Permissible ambient temperature range during operation

-25 °C ... +60 °C

Permissible ambient temperature range during storage

-40 °C ... +85 °C

Operating altitude

max. 2000 m

Overvoltage category

II

Pollution degree

2

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Installation

on 35 mm mounting rail, conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable, see chapter
Mounting of passive terminals

variable

Approvals / markings*

CE, cULus, EAC, UKCA

*) Real applicable approvals/markings see type plate on the side (product marking).

EL9150, EL9160 connection

CAUTION

Danger for persons and equipment!

  • In the project planning of the bus terminal system, observe the different potentials on the power contacts (24 V DC and 230 V AC) and if necessary use potential separation terminals (EL9080) to isolate the potentials!
  • Bring the bus terminal system into a safe, de-energized state before starting installation, disassembly or wiring of the terminal modules!
EL9150, EL9160 - Introduction and Technical Data 2:
Fig.11: EL9150, EL9160 connection

Terminal point

Description

Name

No.

 

1

not used

230 VAC (120 VAC)

2

Supply input 230 VAC (120 VAC), internally connected to terminal point 6 and power contact)

0 V

3

0 V for supply input (internally connected to terminal points 7 and power contact)

⏚

4

Ground (internally connected to terminal point 8 and power contact ground)

 

5

not used

230 VAC (120 VAC)

6

Supply input 230 VAC (120 VAC), internally connected to terminal point 2 and power contact)

0 V

7

0 V for supply input (internally connected to terminal points 3 and power contact)

⏚

8

Ground (internally connected to terminal point 4 and power contact ground)

LEDs

LED

Color

Meaning

Power LED

green

off

No voltage at the supply input

on

230 VAC (120 VAC) at the supply input

Process data (EL9160 only)

The EL9160 has a bit width of 1 bit (diagnostic bit for voltage at the power contacts, "PowerOK") in the process image and is represented in the TwinCAT tree as follows:

EL9150, EL9160 - Introduction and Technical Data 3:
Fig.12: EL9160 in the TwinCAT tree

If there is no voltage at the power contacts, the corresponding diagnostic bit "PowerOK" is set to FALSE (0).