EL9100, EL9110, EL9190 - Introduction and Technical Data

Power supply terminal 24 V DC

EL9100, EL9110, EL9190 - Introduction and Technical Data 1:
Fig.8: EL9100, EL9110, EL9190

The EL9100, EL9110, and EL9190 power supply terminals can be placed at any position between the input/output terminals to create an additional potential group or to supply the terminals to the right with higher currents in case of high current loads.

The E-bus will pass through.

Unlike the EL9100 and EL9190, the EL9110 has diagnostics displayed in the process image.

Technical data

Technical data

EL9100

EL9110

EL9190

Nominal voltage

24 V DC

variable, up to 230 V AC/DC

Power contact current load

max. 10 A

Electrical isolation

500 V (E-bus/field voltage)

Current consumption via E-bus

-

typ. 90 mA

-

Bit width in process image

-

1 diagnostic bit

-

Configuration

no address or configuration settings required

Power LED

yes

yes

no

Diagnostics

no

yes, in the process image

no

Electrical connection to mounting rail

no

Renewed infeed

yes

Connection facility to additional power contact

1

Side by side mounting on EtherCAT Terminals with power contact

yes

Side by side mounting on EtherCAT Terminals without power contact

yes

Weight

approx. 50 g

Permissible ambient temperature range during operation

-25 °C ... +60 °C

Permissible ambient temperature range during storage

-40 °C ... +85 °C

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Installation

on 35 mm mounting rail, conforms to EN 60715

Enhanced mechanical load capacity

yes, see also Installation instructions for enhanced mechanical load capacity

-

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable, see chapter
Mounting of passive terminals

variable

variable, see chapter
Mounting of passive terminals

Approvals / markings*

CE, cULus, UKCA, EAC,
CCC, ATEX, IECEx

CE, cULus, UKCA, EAC

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc

EL9100, EL9110, EL9190 connection

CAUTION

Danger for persons and equipment!

  • In the project planning of the bus terminal system, observe the different potentials on the power contacts (24 V DC and 230 V AC/DC) and if necessary use potential separation terminals (EL9080) to isolate the potentials!
  • Bring the bus terminal system into a safe, de-energized state before starting installation, disassembly or wiring of the terminal modules!
EL9100, EL9110, EL9190 - Introduction and Technical Data 2:
Fig.8: Connection - EL9100, EL9110, EL9190

EL91100, EL9110

EL9190

Terminal point

Description

Terminal point

Description

Name

No.

Name

No.

 

 

1

not used

 

1

not used

+24 V

2

Supply input +24 V
internally connected to terminal point 6 and positive power contact

230 V AC/DC

2

Supply input 230 V AC/DC [any voltage up to 230 V AC/DC]
internally connected to terminal point 6 and 230 V AC/DC power contact

0 V

3

0 V
internally connected to terminal point 7 and negative power contact

N

3

N
internally connected to terminal point 7 and neutral conductor power contact

⏚*

4

Ground (internally connected to terminal point 8 and power contact ground)

⏚*

4

Ground (internally connected to terminal point 8 and power contact ground)

 

5

not used

 

5

not used

+24 V

6

Supply input +24 V internally connected to terminal point 2 and positive power contact

230 V AC/DC

6

Supply input 230 V AC/DC [any voltage up to 230 V AC/DC]
internally connected to terminal point 2 and 230 V AC/DC power contact

0 V

7

0 V
internally connected to terminal point 3 and negative power contact

N

7

N
internally connected to terminal point 3 and neutral conductor power contact

⏚*

8

Protective conductor (internally connected with terminal point 4 and power contact ground)

⏚*

8

Ground (internally connected to terminal point 4 and power contact ground)

* from hardware version 02

LEDs (EL9100 and EL9110 only)

LED

Color

Meaning

Power LED

green

off

No supply voltage

on

24 V DC at the supply input

Process data (EL9110 only)

The EL9110 has a bit width of 1 bit (diagnostic bit for voltage at the power contacts, "PowerOK") in the process image and is represented in the TwinCAT tree as follows:

EL9100, EL9110, EL9190 - Introduction and Technical Data 3:
Fig.10: EL9110 in the TwinCAT tree

If there is no voltage at the power contacts, the corresponding diagnostic bit "PowerOK" is set to FALSE (0).