Input/output data
Index 2001 Outputs
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
2001:0 | Outputs | Maximum subindex | UINT8 | RO | 0x11 (17dec) |
2001:11 | Torque offset | Torque value offset Equation for index 0x2002:54 = 0 : Equation for index 0x2002:54 = 1 : | INT16 | RO | 0x0000 (0dec) |
Index 2008 Inputs
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
2008:0 | Inputs | Maximum subindex | UINT8 | RO | 0x02 (2dec) |
2008:01 | Info data1 | Synchronous information (selection via subindex 0x2002:55) | UINT16 | RO | 0x0000 (0dec) |
2008:01 | Info data2 | Synchronous information (selection via subindex 0x2002:56) | UINT16 | RO | 0x0000 (0dec) |
Index 603E TxPDO Data invalid
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
603E:0 | TxPDO Data invalid | Max. subindex | UINT8 | RO | 0x02 (2dec) |
603E:02 | Position actual value | 0: The current position is valid | BOOLEAN | RO P | 0 |
Index 6040 Controlword
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6040:0 | Controlword | DS402 Controlword | UINT16 | RO | 0x0000 (0dec) |
Index 6041 Statusword
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6041:0 | Statusword | DS402 Statusword | UINT16 | RO | 0x0000 (0dec) |
Index 605E Fault reaction option code
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
605E:0 | Fault reaction option code | 0: Disable drive function, motor is free to rotate 1: Slow down by slow down ramp | ENUM16BIT | RW | 0 |
Index 6060 Modes of operation
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6060:0 | Modes of operation | permitted values: 0x08: Cyclic synchronous position mode (CSP) | UINT8 | RW | 0x00 (0dec) |
Index 6061 Modes of operation display
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6061:0 | Modes of operation display | permitted values: 8: Cyclic synchronous position mode (CSP) 9: Cyclic synchronous velocity mode (CSV) 10: Cyclic synchronous torque mode (CST) 11: Cyclic synchronous torque mode with commutation angle (CSTCA) | UINT8 | RO | 0x00 (0dec) |
Index 6064 Position actual value
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6064:0 | Position actual value | Position | UINT32 | RO | 0x00000000 (0dec) |
Index 6065 Following error window
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6065:0 | Following error window | Following error monitor: Following error window | UINT32 | RO | 0xFFFFFFFF (-1dec) |
Index 6066 Following error time out
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6066:0 | Following error time out | Following error monitor: Timeout If the following error is larger than the following error window for a time that exceeds the timeout, this leads to an error reaction | UINT16 | RO | 0x0000 (0dec) |
Index 606C Velocity actual value
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
606C:0 | Velocity actual value | Display of the current velocity value | INT32 | RO | 0x00000000 (0dec) |
Index 6071 Target torque
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6071:0 | Target torque | This object shall indicate the configured input value for the torque controller. Equation for index 0x2002:54 = 0 : Equation for index 0x2002:54 = 1 : | INT16 | RO | 0x0000 (0dec) |
Index 6072 Max torque
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6072:0 | Max torque | This object limits the target torque for the torque controller (bipolar limit). Equation for index 0x2002:54 = 0 : Equation for index 0x2002:54 = 1 : | UINT16 | RW | 0x7FFF (32767dec) |
Index 6075 Motor rated current
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6075:0 | Motor rated current | Motor rated current | UINT32 | RW | 0x000003E8 (1000dec) |
Index 6077 Torque actual value
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6077:0 | Torque actual value | This object shall provide the actual value of the torque. Equation for index 0x2002:54 = 0 : Equation for index 0x2002:54 = 1 : | INT16 | RO | 0x0000 (0dec) |
Index 6079 DC link circuit voltage
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6079:0 | DC link circuit voltage | DC link voltage g | UINT32 | RO | 0x00000000 (0dec) |
Index 607A Target position
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
607A:0 | Target position | This object shall provide the actual position. | UINT32 | RO | 0x00000000 (0dec) |
Index 6080 Max motor speed
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6080:0 | Max motor speed | Velocity limitation | UINT32 | RW | 0x00040000 (262144dec) |
Index 608F Position encoder resolution
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
608F:0 | Position encoder resolution | This object represents the configured encoder increments and the number of motor revolutions. The position encoder resolution is calculated according to the following equation: | UINT8 | RO | 0x02 (2dec) |
608F:01 | SubIndex 001 | Encoder increments | UINT32 | RO | 0x00000000 (0dec) |
608F:02 | SubIndex 002 | Motor revolutions | UINT32 | RO | 0x00000000 (0dec) |
Index 6090 Velocity Encoder Resolution
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6090:0 | Velocity Encoder Resolution | Display of configured encoder increments/s and motor revolutions/s. Velocity Encoder Resolution = | UINT32 | RO | 0x00000000 (0dec) |
Index 60B2 Torque offset
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60B2:0 | Torque offset | Torque value offset | UINT16 | RO | 0x0000 (0dec) |
Index 60B8 Touch probe function
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60B8:0 | Touch probe function | Touch probe function byte | UINT16 | RO | 0x0000 (0dec) |
Index 60B9 Touch probe status
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60B9:0 | Touch probe status | Touch probe status byte | UINT16 | RO | 0x0000 (0dec) |
Index 60BA Touch probe 1 positive edge
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60BA:0 | Touch probe 1 positive edge | Positive position value of TP 1 | INT32 | RO | 0x00000000 (0dec) |
Index 60BB Touch probe 1 negative edge
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60BB:0 | Touch probe 1 negative edge | Negative position value of TP 1 | INT32 | RO | 0x00000000 (0dec) |
Index 60BC Touch probe 2 positive edge
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60BC:0 | Touch probe 2 positive edge | Positive position value of TP 2 | INT32 | RO | 0x00000000 (0dec) |
Index 60BD Touch probe 2 negative edge
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60BD:0 | Touch probe 2 negative edge | Negative position value of TP 2 | INT32 | RO | 0x00000000 (0dec) |
Index 60C2 Interpolation time period
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60C2:0 | Interpolation time period | Maximum subindex x | UINT8 | RO | 0x02 (2dec) |
60C2:01 | Interpolation time period value | This object shall indicate the configured interpolation cycle time. The interpolation time period (sub-index 0x01) value shall be given in 10(interpolation time index) (second). | UINT8T8 | RO | 0x00 (0dec) |
60C2:02 | Interpolation time index | INT8 | RO | 0x00 (0dec) |
Index 60D9 Supported functions
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60D9:0 | Supported functions | This object shall provide information on the supported functions in the device. | UINT3232 | RO | 0x00000000 (0dec) |
Index 60DA Function settings
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60DA:0 | Function settings | This object shall enable/disable supported functions in the device. Bit 0: Enable TxPDOToggle-Bit in Statusword: Bit 10 Bit 1: Enable input cycle counter in Statusword: Bit 13 Bit 2-31: reserved | UINT32 | RW | 0x00000000 (0dec) |
Index 60EA Commutation angle
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60EA:0 | Commutation angle | Electrical commutation angle (for the CSTCA mode) | UINT16 | RO | 0x0000 (0dec) |
Index 60F4 Following error actual value
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60F4:0 | Following error actual value | Following error | INT32 | RO | 0x00000000 (0dec) |
Index 60FF Target velocity
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
60FF:0 | Target velocity | This object shall indicate the configured target velocity | INT32 | RO | 0x00000000 (0dec) |
Index 6403 Motor catalogue number
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6403:0 | Motor catalogue number | This is the order code from the electronic type plate of the motor, e.g. AM8121-0F20-0000 | STRING | RO |
|
Index 6502 Supported drive modes
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6502:0 | Supported drive modes | This object shall provide information on the supported drive modes. (DS402 Object 0x6502) Bit 0: PP | UINT32 | RO | 0x00000000 (0dec) |