Supported encoders / signal types
Differential signals according to RS422 are intended as encoder connection. Single-ended signals from TTL encoders and also signals from Open Collector encoders are also options, through internal pull-up resistances.
The following signal types are supported:
Encoder  | Signal type  | Setting in  | Cut-off frequency  | Comments  | 
|---|---|---|---|---|
Encoder  | RS422  | 0  | 20 million increments/s  | Signal levels according to RS422 are expected  | 
Counter/pulse generator  | 1  | |||
Encoder  | TTL  | 2  | 4 million increments/s  | A voltage level of nominally 2.0 V to 6.0 V with a current of 2.1 mA or higher is expected. No wire break detection  | 
Counter/pulse generator  | 3  | |||
Encoder  | open collector  | 4  | 400,000 increments/s  | No wire break detection  | 
Counter/pulse generator  | 5  | |||
*) depending on the number of channels (n = 0 for channel 1 and n = 1 for channel 2)  | ||||
The correct wiring for the respective encoder can be found in chapter Connection.