Configuration data

Index 8000 ENC Settings (EL5101-0010)

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

ENC Settings

Maximum subindex

UINT8

RO

0x17 (23dec)

8000:01

Enable C reset

The counter is reset via the C input.

BOOLEAN

RW

0x00 (0dec)

8000:02

Enable extern reset

A counter reset is triggered via the external latch input (24 V)

BOOLEAN

RW

0x00 (0dec)

8000:04

Gate polarity

0: Disable gate

1: Enable pos. gate (gate locks with HIGH level)

2: Enable neg. gate (gate locks with LOW level)

BIT2

RW

0x01 (1dec)

8000:0B

Open circuit detection A

An open circuit on track A is indicated in index 0x6000:07 and as process data. Diagnosis is only possible if the corresponding input is wired differentially. A differential voltage -0.475 V > Vid > +0.475 V (typical, subject to change) is detected as a broken wire.

BOOLEAN

RW

0x01 (1dec)

8000:0C

Open circuit detection B

An open circuit on track B is indicated in index 0x6000:07 and as process data. Diagnosis is only possible if the corresponding input is wired differentially. A differential voltage -0.475 V > Vid > +0.475 V (typical, subject to change) is detected as a broken wire.

BOOLEAN

RW

0x01 (1dec)

8000:0D

Open circuit detection C

An open circuit on track C is indicated in index 0x6000:07 and as process data. Diagnosis is only possible if the corresponding input is wired differentially. A differential voltage -0.475 V > Vid > +0.475 V (typical, subject to change) is detected as a broken wire.

BOOLEAN

RW

0x00 (0dec)

8000:0E

Reversion of rotation

Activates reversion of rotation

BOOLEAN

RW

0x00 (0dec)

8000:10

Extern reset polarity

0: Fall (the counter is set to zero with a falling edge)

1: Rise (the counter is set to zero with a rising edge)

BIT1

RW

0x01 (1dec)

8000:11

Frequency window

This is the minimum time over which the frequency is determined. Default 10 ms [resolution: 1 µs]
The number of pulses in the time window + the following is measured. The maximum waiting time is specified in the “Frequency Wait Time” parameter. The number of pulses is divided by the actual time window size. The determined frequency is output in index 0x6000:13 and as a process data.
The frequency calculation is carried out locally without distributed clocks function.

UINT16

RW

0x2710 (10000dec)

8000:13

Frequency scaling

Scaling of the frequency measurement (must be divided by this value to obtain the unit in Hz):

100: “0.01 Hz”

UINT16

RW

0x0064 (100dec)

8000:14

Period scaling

Resolution of the period in the process data:

100: “100 ns” period value is a multiple of 100 ns

500: “500 ns” period value is a multiple of 500 ns

UINT16

RW

0x0064 (100dec)

8000:15

Frequency resolution

Resolution of the frequency measurement:

100: “0.01 Hz”

UINT16

RW

0x0064 (100dec)

Index 8000 ENC Settings (EL5101-0010)

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:16

Period resolution

Internal resolution of the period measurement:

100: “100 ns” period value is a multiple of 100 ns
The period is calculated internally with a resolution of 100 ns. The max. measurable period can then be approx. 1.6 seconds.

500: “500 ns” period value is a multiple of 500 ns
Internally the period is calculated with 500 ns resolution. The maximum measurable period is approx. 32.7 ms. The resolution of process data continues to be the value according to index 0x8000:14 (e.g. 100 ns [default]).

UINT16

RW

0x0064 (100dec)

8000:17

Frequency Wait Time

Waiting time [ms] for frequency measurement

Once the time specified in the “Frequency window” has elapsed, the system waits for the next positive edge from track A. This enables the update speed for the Frequency process data to be optimized, depending on the expected frequencies. At least double the period of the minimum frequency to be measured should be entered here. t >= 2* (1 / fmin)

UINT16

RW

0x0190 (400dec)