Input data

Index 60n0 IND Boolean Inputs Ch.n+1 (for n=0 [channel 1], n=1 [channel 2])

Index (hex)

Name

Meaning

Data type

Flags

Default

60n0:0

IND Boolean Inputs Ch.n+1

Maximum subindex

UINT8

RO

0x0F (15dec)

60n0:01

Underrange

Measurement is below range

BOOLEAN

RO

0x00 (0dec)

60n0:02

Overrange

Measuring range exceeded

BOOLEAN

RO

0x00 (0dec)

60n0:03

Excitation error

Short circuit on primary side on channel n or overload of excitation source was detected

BOOLEAN

RO

0x00 (0dec)

60n0:04

Input error

Wire breakage on secondary side or amplitude error on channel n was detected

BOOLEAN

RO

0x00 (0dec)

60n0:08

Digital input

Status of the digital input

BOOLEAN

RO

0x00 (0dec)

60n0:0A

Latch extern valid

The counter value was locked via the external latch.

The data in index 0x60n1:02 "Latch value" corresponds to the latched value when the bit is set.
To re-enable the latch input, index 0x70n0:03 "Enable latch on digital input" must first be disabled and then reset.

BOOLEAN

RO

0x00 (0dec)

60n0:0B

Set position done

0: a new position value can be written to index 0x60n1:01 "Position"

1: A value was set in index 0x60n1:01 "Position". A new position value can only be set after "Set position done" has been reset to 0.

BOOLEAN

RO

0x00 (0dec)

60n0:0D

Diag

Indicates that a new message is available in the "Diag History"

BOOLEAN

RO

0x00 (0dec)

60n0:0E

TxPDO State

Validity of the data of the associated TxPDO

0: valid
1: invalid

BOOLEAN

RO

0x00 (0dec)

60n0:0F

Input cycle counter

2-bit counter for synchronization (increments only when a new process data is ready)

BIT2

RO

0x00 (0dec)

Index 60n1 IND Inputs Ch. n+1 (for n=0 [channel 1], n=1 [channel 2])

Index (hex)

Name

Meaning

Data type

Flags

Default

60n1:0

IND Inputs Ch.n+1

Maximum subindex

UINT8

RO

0x02 (2dec)

60n1:01

Position

Position value

DINT

RO

0x00000000 (0dec)

60n1:02

Latch value

Latch value

DINT

RO

0x00000000 (0dec)

Index 60n2 IND Latch Timestamp Ch. n+1 (for n=0 [channel 1], n=1 [channel 2])

Index (hex)

Name

Meaning

Data type

Flags

Default

60n2:0

IND Latch Timestamp Ch.n+1

Maximum subindex

UINT8

RO

0x01 (1dec)

60n2:01

Latch event Timestamp

Timestamp of the stored position value via the digital input

ULINT64

RO

0x00000000 (0dec)