PDO Assignment

PDO Assignment 1:

Setting the oversampling factor and position data via the "DC" tab

Set the oversampling factor via the "DC" tab (see chapter "Oversampling settings distributed clocks (DC)".
The correct sampling ratio at distributed clocks level and the correct number of process data to be transmitted are then set automatically.

The process date "StartTimeNextLatch" (0x1A01) is enabled by default. To disable it,

PDO assignment of Sync Managers, EL5031-0011

SM3, PDO Assignment 0x1C13

Index

Size (byte.bit)

Name

PDO Content, Index

Size (byte.bit)

0x1A00 (default)
FB Inputs Status

2.0

Status_Error

0x6000:02

0.1

Status_Ready

0x6000:03

0.1

[Offset]

-

0.5

[Offset]

-

0.4

Status_Diag

0x6000:0D

0.1

Status_TxPDO State

0x6000:0E

0.1

Status_Input Cycle counter

0x6000:0F

0.2

0x1A01 (default)
FB Inputs NextSyncTime

8.0

StartTimeNextLatch

0x6000:16

8.0

0x1A10 (default)
FB Inputs 1 Samples Position

8.0

Position_ARRAY [0]

0x6000:11

8.0

0x1A11
FB Inputs 1 Samples Position compact

4.0

Position_ARRAY [0]

0x6000:12

4.0

0x1A12
FB Inputs 2 Samples Position

16.0

Position_ARRAY [0]

0x6000:11

8.0

Position_ARRAY [1]

0x6000:11

8.0

0x1A13
FB Inputs 2 Samples Position compact

8.0

Position_ARRAY [0]

0x6000:12

4.0

Position_ARRAY [1]

0x6000:12

4.0

0x1A14
FB Inputs 4 Samples Position

32.0

Position_ARRAY [0]

0x6000:11

8.0

Position_ARRAY [1]

0x6000:11

8.0

Position_ARRAY [2]

0x6000:11

8.0

Position_ARRAY [3]

0x6000:11

8.0

0x1A15
FB Inputs 4 Samples Position compact

16.0

Position_ARRAY [0]

0x6000:12

4.0

Position_ARRAY [1]

0x6000:12

4.0

Position_ARRAY [2]

0x6000:12

4.0

Position_ARRAY [3]

0x6000:12

4.0

0x1A16
FB Inputs 5 Samples Position

40.0

Position_ARRAY [0]

0x6000:11

8.0

…

 

 

Position_ARRAY [4]

0x6000:11

8.0

0x1A17
FB Inputs 5 Samples Position compact

20.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [4]

0x6000:12

4.0

0x1A18
FB Inputs 8 Samples Position

64.0

Position_ARRAY [0]

0x6000:11

8.0

…

 

 

Position_ARRAY [7]

0x6000:11

8.0

0x1A19
FB Inputs 8 Samples Position compact

32.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [7]

0x6000:12

4.0

0x1A1A
FB Inputs 10 Samples Position

80.0

Position_ARRAY [0]

0x6000:11

8.0

…

 

 

Position_ARRAY [9]

0x6000:11

8.0

0x1A1B
FB Inputs 10 Samples Position compact

40.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [9]

0x6000:12

4.0

0x1A1C
FB Inputs 16 Samples Position

80.0

Position_ARRAY [0]

0x6000:11

8.0

…

 

 

Position_ARRAY [15]

0x6000:11

8.0

0x1A1D
FB Inputs 16 Samples Position compact

40.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [15]

0x6000:12

4.0

SM3, PDO Assignment 0x1C13

Index

Size (byte.bit)

Name

PDO Content
Index

Size (byte.bit)

0x1A1E
FB Inputs 20 Samples Position

160.0

Position_ARRAY [0]

0x6000:11

8.0

…

 

 

Position_ARRAY [19]

0x6000:11

8.0

0x1A1F
FB Inputs 20 Samples Position compact

80.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [19]

0x6000:12

4.0

0x1A20
FB Inputs 25 Samples Position

200.0

Position_ARRAY [0]

0x6000:11

8.0

…

 

 

Position_ARRAY [24]

0x6000:11

8.0

0x1A21
FB Inputs 25 Samples Position compact

100.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [24]

0x6000:12

4.0

0x1A23
FB Inputs 32 Samples Position compact

128.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [31]

0x6000:12

4.0

0x1A25
FB Inputs 40 Samples Position compact

160.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [39]

0x6000:12

4.0

0x1A27
FB Inputs 50 Samples Position compact

200.0

Position_ARRAY [0]

0x6000:12

4.0

…

 

 

Position_ARRAY [49]

0x6000:12

4.0