Configuration data
Index 8000 RTD Settings Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8000:0 | RTD Settings Ch.1 | Maximum subindex | UINT8 | RO | 0x1B (27dec) | |
8000:01 | Enable user scale | User scaling is active. | BOOLEAN | RW | 0x00 (0dec) | |
8000:02 | Presentation | 0 | Signed presentation | BIT3 | RW | 0x00 (0dec) |
1 | Absolute value with MSB as sign | |||||
2 | High resolution (1/100°C) | |||||
8000:05 | Siemens bits | The S5 bits are displayed in the three low-order bits | BOOLEAN | RW | 0x00 (0dec) | |
8000:06 | Enable filter | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x00 (0dec) | |
8000:07 | Enable limit 1 | The status bits are set in relation to Limit 1 | BOOLEAN | RW | 0x00 (0dec) | |
8000:08 | Enable limit 2 | The status bits are set in relation to Limit 2 | BOOLEAN | RW | 0x00 (0dec) | |
8000:09 | Enable automatic calibration | not implemented | BOOLEAN | RW | 0x00 (0dec) | |
8000:0A | Enable user calibration | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) | |
8000:0B | Enable vendor calibration | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) | |
8000:11 | User scale offset | User scaling offset | INT16 | RW | 0x0000 (0dec) | |
8000:12 | User scale gain | This is the gain of the user scaling. | INT32 | RW | 0x00010000 (65536dec) | |
8000:13 | Limit 1 | First limit value for setting the status bits (resolution 0.1 °C) | INT16 | RW | 0x0000 (0dec) | |
8000:14 | Limit 2 | Second limit value for setting the status bits (resolution 0.1 °C) | INT16 | RW | 0x0000 (0dec) | |
8000:15 | Filter settings | This object determines the digital filter settings if it is active via Enable filter (Index 0x8000:06). | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz | |||||
1 | 60 Hz | |||||
2 | 100 Hz | |||||
3 | 500 Hz | |||||
4 | 1 kHz | |||||
5 | 2 kHz | |||||
6 | 3.75 kHz | |||||
7 | 7.5 kHz | |||||
8 | 15 kHz | |||||
9 | 30 kHz | |||||
10 | 5 Hz | |||||
11 | 10 Hz | |||||
![]() | The filter properties are set only via index 0x8000:15 The filter frequencies are set for all RTD channels of the EL3204-0162 terminals centrally via index 0x8000:15 (channel 1). |
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8000:16 | Calibration interval | not implemented | UINT16 | RW | 0x0000 (0dec) | |
8000:17 | User calibration offset | User calibration offset | INT16 | RW | 0x0000 (0dec) | |
8000:18 | User calibration gain | User calibration gain | UINT16 | RW | 0xFFFF (65535dec) | |
8000:19 | RTD element | UINT16 | RW | 0x0000 (0dec) | ||
0 | Pt100 | |||||
1 | Ni100 | |||||
2 | Pt1000 | |||||
3 | Pt500 | |||||
4 | Pt200 | |||||
5 | Ni1000 | |||||
6 | Ni1000 | |||||
7 | Ni120 | |||||
8 | Output in ohm | |||||
9 | Output in ohm | |||||
10-32 | KT100/110/130/210/230 KTY10/11/13/16/19 | |||||
8000:1A | Connection technology | UINT16 | RW | 0x0000 (0dec) | ||
0 | Two-wire connection | |||||
1 | 3-wire connection (without effect, not to be used) | |||||
2 | 4-wire connection (without effect, not to be used) | |||||
3 | not connected: sets the process data to 0 and switches off the LED | |||||
8000:1B | Calibration of the supply lines | INT16 | RW | 0x0000 (0dec) | ||
Index 8010 RTD Settings Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8010:0 | RTD Settings Ch.2 | Maximum subindex | UINT8 | RO | 0x1B (27dec) | |
8010:01 | Enable user scale | User scaling is active. | BOOLEAN | RW | 0x00 (0dec) | |
8010:02 | Presentation | 0 | Signed presentation | BIT3 | RW | 0x00 (0dec) |
1 | Absolute value with MSB as sign | |||||
2 | High resolution (1/100 C°) | |||||
8010:05 | Siemens bits | The S5 bits are displayed in the three low-order bits | BOOLEAN | RW | 0x00 (0dec) | |
8010:06 | Enable filter | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x00 (0dec) | |
8010:07 | Enable limit 1 | The status bits are set in relation to Limit 1 | BOOLEAN | RW | 0x00 (0dec) | |
8010:08 | Enable limit 2 | The status bits are set in relation to Limit 2 | BOOLEAN | RW | 0x00 (0dec) | |
8010:09 | Enable automatic calibration | not implemented | BOOLEAN | RW | 0x00 (0dec) | |
8010:0A | Enable user calibration | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) | |
8010:0B | Enable vendor calibration | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) | |
8010:11 | User scale offset | User scaling offset | INT16 | RW | 0x0000 (0dec) | |
8010:12 | User scale gain | This is the gain of the user scaling. | INT32 | RW | 0x00010000 (65536dec) | |
8010:13 | Limit 1 | First limit value for setting the status bits (resolution 0.1°C) | INT16 | RW | 0x0000 (0dec) | |
8010:14 | Limit 2 | Second limit value for setting the status bits (resolution 0.1°C) | INT16 | RW | 0x0000 (0dec) | |
8010:15 | Filter settings | (see note below) | UINT16 | RW | 0x0000 (0dec) | |
![]() | The filter properties are set only via index 0x8000:15 The filter frequencies are set for all RTD channels of the EL3204-0162 terminals centrally via index 0x8000:15 (channel 1). |
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8010:16 | Calibration interval | not implemented | UINT16 | RW | 0x0000 (0dec) | |
8010:17 | User calibration offset | User calibration offset | INT16 | RW | 0x0000 (0dec) | |
8010:18 | User calibration gain | User calibration gain | UINT16 | RW | 0xFFFF (65535dec) | |
8010:19 | RTD element | UINT16 | RW | 0x0000 (0dec) | ||
0 | Pt100 | |||||
1 | Ni100 | |||||
2 | Pt1000 | |||||
3 | Pt500 | |||||
4 | Pt200 | |||||
5 | Ni1000 | |||||
6 | Ni1000 | |||||
7 | Ni120 | |||||
8 | Output in ohm | |||||
9 | Output in ohm | |||||
10 - 32 | KT100/110/130/210/230 KTY10/11/13/16/19 | |||||
8010:1A | Connection technology | UINT16 | RW | 0x0000 (0dec) | ||
0 | Two-wire connection | |||||
1 | 3-wire connection (without effect, not to be used) | |||||
2 | 4-wire connection (without effect, not to be used) | |||||
3 | not connected: sets the process data to 0 and switches off the LED | |||||
8010:1B | Calibration of the supply lines | INT16 | RW | 0x0000 (0dec) | ||
Index 8020 AI Settings Ch. 3
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8020:0 | AI Settings Ch. 3 | Maximum subindex | UINT8 | RO | 0x19 (25dec) |
8020:01 | Enable user scale | User scaling is active. | BOOLEAN | RW | 0x00 (0dec) |
8020:02 | Presentation | 0: Signed presentation | BIT3 | RW | 0x00 (0dec) |
8020:05 | Siemens bits | The S5 bits are displayed in the three low-order bits | BOOLEAN | RW | 0x00 (0dec) |
8020:06 | Enable filter | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x01 (1dec) |
8020:07 | Enable limit 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8020:08 | Enable limit 2 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8020:0A | Enable user calibration | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8020:0B | Enable vendor calibration | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8020:0E | Swap limit bits | Reversal of the limit bits | BOOLEAN | RW | 0x00 (1dec) |
8020:11 | User scale offset | User scaling offset | INT16 | RW | 0x0000 (0dec) |
8020:12 | User scale gain | Gain of the user scaling. | INT32 | RW | 0x00010000 (65536dec) |
8020:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) |
8020:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) |
8020:15 | Filter settings | This object determines the digital filter settings if it is active via Enable filter (Index 0x8020:06). | UINT16 | RW | 0x0000 (0dec) |
![]() | The filter characteristics are set via index 0x8020:15 The filter frequencies are set for all AI channels of the EL3204-0162 terminals centrally via index 0x8020:15 (channel 1). |
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8020:17 | User calibration offset | User calibration offset | INT16 | RW | 0x0000 (0dec) |
8020:18 | User calibration gain | User calibration gain | INT16 | RW | 0x4000 (16384dec) |
8020:19 | Range | Setting the input range | INT32 | RW | 0x00000006 (6dec) |
Index 8030 AI Settings Ch. 4
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8030:0 | AI Settings Ch. 4 | Maximum subindex | UINT8 | RO | 0x19 (25dec) |
8030:01 | Enable user scale | User scaling is active. | BOOLEAN | RW | 0x00 (0dec) |
8030:02 | Presentation | 0: Signed presentation | BIT3 | RW | 0x00 (0dec) |
8030:05 | Siemens bits | The S5 bits are displayed in the three low-order bits | BOOLEAN | RW | 0x00 (0dec) |
8030:06 | Enable filter | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x01 (1dec) |
8030:07 | Enable limit 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8030:08 | Enable limit 2 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8030:0A | Enable user calibration | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8030:0B | Enable vendor calibration | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8030:0E | Swap limit bits | Reversal of the limit bits | BOOLEAN | RW | 0x00 (1dec) |
8030:11 | User scale offset | User scaling offset | INT16 | RW | 0x0000 (0dec) |
8030:12 | User scale gain | Gain of the user scaling. | INT32 | RW | 0x00010000 (65536dec) |
8030:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) |
8030:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) |
8030:15 | Filter settings | (see note below) | UINT16 | RW | 0x0000 (0dec) |
![]() | The filter characteristics are set via index 0x8020:15 The filter frequencies are set for all AI channels of the EL3204-0162 terminals centrally via index 0x8020:15 (channel 1). |
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8030:17 | User calibration offset | User calibration offset | INT16 | RW | 0x0000 (0dec) |
8030:18 | User calibration gain | User calibration gain | INT16 | RW | 0x4000 (16384dec) |
8030:19 | Range | Setting the input range | INT32 | RW | 0x00000006 (6dec) |