Limit 1 (index 0x8020:13 / 0x8030:13) and limit 2 (index 0x8020:14 / 0x8030:14)
A range of values can be set which is compared with the values in the indices 0x8020:13 / 0x8030:13 and 0x8020:14 / 0x8030:14. The bits are set in the process data if the limit values are undershot or exceeded.
The limit evaluation takes place after taking into account the set characteristic curve and negative values.
Limit [2 Bit] Interpretation (default), Index 0x6020:03 / 0x6030:03, 0x6020:05 / 0x6030:05:
00bin, 0: not active
01bin, 1: value is greater than limit value
10bin, 2: value is smaller than limit value
11bin, 3: value is equal to limit value