Operating hour and switching cycle counter

The terminal internally counts the duty cycle (Index 0x9000:11) (resolution: 1 minute, accuracy: approx. 50 µs) and the number of switching cycles (Index 0x9000:12) of the connected load. These values are cyclically saved every 15 minutes in the internal memory if "Enable automatic saving of counter" (Index 0x8002:06) is activated.

For the application it may be necessary for this saving to be acyclically triggered as well. The user can use the "Command" object (Index FB00) for this. The two counters can be saved or deleted with the commands 0x0001 and 0x0002 respectively.