Zero pulse from the C track of the encoder

Referencing to the zero pulse of the encoder is only possible in addition to referencing to a referencing cam.

To ensure that the motor does not stop until the zero pulse is received after it has moved down from the referencing cam, configure the terminal as follows:

1. Configure homing with referencing cams:
switching signal from a digital input of the EJ7411
or
switching signal from the PLC (PLC Camming)
2. Set the CoE parameter 0x8001:11 "Touch probe 1 source" to "Hardware zero impulse".
Zero pulse from the C track of the encoder 1:
Set 0x8001:11 "Touch probe 1 source" to "Hardware zero impulse".
3. Activate the process data objects 0x1607, 0x1A07, 0x1A08 for the function "Touch Probe":
Zero pulse from the C track of the encoder 2:
Activate 0x1607 "FB Touch probe control"
Zero pulse from the C track of the encoder 3:
Activate 0x1A07 "FB Touch probe status" and 0x1A08 "FB Touch probe 1 pos position"
A dialog box appears after each activation of a process data object (see figure below).
Zero pulse from the C track of the encoder 4:
4. Confirm each dialog box with "Yes".