Motor chokes AX2090-MD50

Motor chokes AX2090-MD50 1:

Order no.

Description

AX2090-MD50-0012
up to 12 A rated current, necessary for motor cable ≥ 25 m with a max. cable length of 100 m.

A motor choke must be installed between the AX5000 and the motor from a certain motor cable length onwards. The motor choke reduces the commutation current flowing via the shield back into the AX5000 to a permissible value and can also provide a solution to EMC problems.

AX2090-MD50-0025
up to 25 A rated current, necessary for motor cable ≥ 25 m with a max. cable length of 50 m.