Axis deceleration ramps

DANGER

Serious injuries caused by moving axes!

The deceleration ramps of the AX5000 servo drive are purely functional and not suitable for personal protection purposes!

A fault in the drive system may have the following effects:

- it may not be possible to enable the functional deceleration ramps;

- it may not be possible to bring the axes to a standstill.

In other words, the axes may not respond. This could cause serious injury.

Before commissioning ensure that all external personal protection measures were applied.

The AX5000 servo drive has functional deceleration ramps, which brake or coast down the connected motors in the event of fault.

Both ramps are configured via the parameters:

.

When configuring the parameters, the braking energy balance of the whole system has to be taken into account. Mechanical and electrical limits affect the maximum deceleration.

Electrical limits result from:

Testing the deceleration ramps

During operation the deceleration ramps are activated automatically in the event of an error reaction of the drive system. To assess these processes, it is necessary to trigger and test the functional ramps manually during commissioning.

Proceed as follows:

Parameter S-0-0372 (Drive Halt Acceleration Bipolar)

Parameter S-0-0429 (Emergency Stop Deceleration)

Axis deceleration ramps 1:

Further information on axis deceleration ramps.

Settings and configuration instructions for the deceleration ramps can be found in this manual under digital inputs and outputs → hardware enable and
limit switch monitoring.