VREF0
ASCII - Command | VREF0 |
|
| |
Syntax Transmit | VREF0 [Data] |
| ||
Syntax Receive | VREF0 <Data> | Available in |
| |
Type | Variable rw | MMI | No | |
ASCII Format | Float | CANBus Object Number | 3698 (hex) | |
DIM | - | PROFIBUS PNU | 2008 (dec) IND = 0000xxxx (bin) | |
Range | 0.01 .. 2.0 | DPR | 408 (dec) | |
Default | 0.125 |
| ||
Opmode | 8 | Data Type Bus/DPR | Integer32 | |
Drive State | - | Weightning | 1000 | |
Start Firmware | 4.78 |
| ||
Configuration | No | Revision | 1.5 | |
Function Group | Position Controller | EEPROM | Yes | |
Short Description | Homing Mode Reduction factor | |||
Description
The parameter VREF0 reduces the homing speed, after the load reaches e.g. the reference switch, while searching for a zero pulse of an external encoder. The selection of the source of the zero pulse can be selected by REFMODE. The second homing speed can be reduced by VREF0 in % of VREF.
Example 1:
REFMODE=1 Zeropulse via digital input 1
NREF=1 Homing move with reference switch with zero pulse
VREF=10000 Homing speed 10000 µm/sec
VREF0=0.2 Reduction of the speed to 2000 µm/sec
Starting a homing move, the drive starts to find the reference switch with the speed of 10000 µm/sec. If the reference switch was found, the speed is reduced to 2000 µm/sec and then the search for the zero pulse is started. If the zero pulse was recognized at digital input 1(high level), the homing move is stopped.
Example 2:
REFMODE=2 Zero pulse via digiatl input 2
NREF=5 Zero pulse in one turn of the motor
VREF=10000
VREF0=0.2
The criteria for the search of the zero pulse is fulfilled, so the reference move is directly started with 2000 µm/sec.