IDN 3005 (P-0-3005) Configurable I/O: Digital Output 1 Mode
Sets the functionality of the digital outputs.
The digital outputs may be read through IDN 3036 and IDN 3037
A new digital output mode will not be active until the parameter set is saved to non-volatile memory and a coldstart or warmstart ( IDN 128 procedure is initiated. The following functions are available:
Data Length: | 2 bytes | Non-Volatile: | Yes |
Data Type: | Unsigned decimal | Write Access: | CP2, CP3 |
Minimum: |
| Run-Up Check: |
|
Maximum: |
| Cyclic Transfer: |
|
Default: |
| Serial Equiv: | O1MODE, O2MODE |
Units: |
| Version: | |
IDN Type: | IO | ADS Index Group (hex.): | 0x8BBD |
Definition:
Mode | Description | Logic |
| Mode | Description | Logic |
|---|---|---|---|---|---|---|
0 | Reserved | – |
| 22 | Zero_pulse | High |
1 | V_act |
| 23 | Slot-DPR |
| |
2 | V_act>x |
| 24 | Ref_OK | High | |
3 | Mains-RTO | High | 25-27 | Reserved |
| |
4 | Regen off | Low | 28 | Posreg.0 |
| |
5 | Sw_limit |
| 29 | Posreg.5 |
| |
6 | Pos.>x |
| 30 | OR-Operation of all Posreg. |
| |
7 | InPos | High | 31-34 | Reserved |
| |
8 | I_act |
| 35 | Internal Enable |
| |
9 | I_act>x |
| 36 | Logical OR: DRVSTAT – x |
| |
10 | Ferror |
| 37 | Logical AND: DRVSTAT – x |
| |
11 | I2t | High | 38 | Logical OR: TRJSTAT -x |
| |
12 | Posreg.1 |
| 39 | Logical AND: TRJSTAT -x |
| |
13 | Posreg.2 |
| 40 | Logical OR: POSRSTAT -x |
| |
14 | Posreg.3 | High | 41 | Logical AND: POSRSTAT - x |
| |
15 | Posreg.4 | High | 42 |
|
| |
16 | Next-InPos |
| 43 | The sign of the actual speed |
| |
17 | Error/Warn |
| 44 | Velocity In-Position (active high) |
| |
18 | Error |
| 45 | Velocity In-Position (active low) |
| |
19 | DC_Link>x |
| 46 | Current in Window (low active) |
| |
20 | DC_Link>x |
| 47 | Current not in Window (low active) |
| |
21 | ENABLE | High |
|
|
|