Object overview

Object overview 1:

EtherCAT XML Device Description

The display matches that of the CoE objects from the EtherCAT XML Device Description. We recommend downloading the latest XML file from the download area of the Beckhoff website and installing it according to installation instructions.

Index (hex)

Name

Flags

Default value

1000

Device type

RO

0x00001389 (5001dec)

1008

Device name

RO

EP1518-0002

1009

Hardware version

RO

00

100A

Software version

RO

01.03

1011:0

Subindex

Restore default parameters

RO

0x01 (1dec)

1011:01

SubIndex 001

RW

0x00000000 (0dec)

1018:0

Subindex

Identity

RO

0x04 (4dec)

1018:01

Vendor ID

RO

0x00000002 (2dec)

1018:02

Product code

RO

0x05EE4052 (99500114dec)

1018:03

Revision

RO

0x00100002 (1048578dec)

1018:04

Serial number

RO

0x00000000 (0dec)

10F0:0

Subindex

Backup parameter handling

RO

0x01 (1dec)

10F0:01

Checksum

RO

0x00000000 (0dec)

1600:0

Subindex

CNT RxPDO-Map Outputs Ch.1

RO

0x05 (5dec)

1600:01

SubIndex 001

RO

0x0000:00, 2

1600:02

SubIndex 002

RO

0x7000:03, 1

1600:03

SubIndex 003

RO

0x7000:04, 1

1600:04

SubIndex 004

RO

0x0000:00, 12

1600:05

SubIndex 005

RO

0x7000:11, 32

1601:0

Subindex

CNT RxPDO-Map Outputs Ch.2

RO

0x05 (5dec)

1601:01

SubIndex 001

RO

0x0000:00, 2

1601:02

SubIndex 002

RO

0x7010:03, 1

1601:03

SubIndex 003

RO

0x7010:04, 1

1601:04

SubIndex 004

RO

0x0000:00, 12

1601:05

SubIndex 005

RO

0x7010:11, 32

1A00:0

Subindex

CNT TxPDO-Map InputsCh.1

RO

0x0A (10dec)

1A00:01

SubIndex 001

RO

0x0000:00, 2

1A00:02

SubIndex 002

RO

0x6000:03, 1

1A00:03

SubIndex 003

RO

0x6000:04, 1

1A00:04

SubIndex 004

RO

0x6000:05, 1

1A00:05

SubIndex 005

RO

0x6000:06, 1

1A00:06

SubIndex 006

RO

0x0000:00, 7

1A00:07

SubIndex 007

RO

0x6000:0E, 1

1A00:08

SubIndex 008

RO

0x6000:0F, 1

1A00:09

SubIndex 009

RO

0x6000:10, 1

1A00:0A

SubIndex 010

RO

0x6000:11, 32

Index (hex)

Name

Flags

Default value

1A01:0

Subindex

CNT TxPDO-Map Inputs Ch.2

RO

0x0A (10dec)

1A01:01

SubIndex 001

RO

0x0000:00, 2

1A01:02

SubIndex 002

RO

0x6010:03, 1

1A01:03

SubIndex 003

RO

0x6010:04, 1

1A01:04

SubIndex 004

RO

0x6010:05, 1

1A01:05

SubIndex 005

RO

0x6010:06, 1

1A01:06

SubIndex 006

RO

0x0000:00, 7

1A01:07

SubIndex 007

RO

0x6010:0E, 1

1A01:08

SubIndex 008

RO

0x6010:0F, 1

1A01:09

SubIndex 009

RO

0x6010:10, 1

1A01:0A

SubIndex 010

RO

0x6010:11, 32

1A02:0

Subindex

DIG TxPDO-Map Inputs

RO

0x09 (9dec)

1A02:01

SubIndex 001

RO

0x6020:01, 1

1A02:02

SubIndex 002

RO

0x6020:02, 1

1A02:03

SubIndex 003

RO

0x6020:03, 1

1A02:04

SubIndex 004

RO

0x6020:04, 1

1A02:05

SubIndex 005

RO

0x6020:05, 1

1A02:06

SubIndex 006

RO

0x6020:06, 1

1A02:07

SubIndex 007

RO

0x6020:07, 1

1A02:08

SubIndex 008

RO

0x6020:08, 1

1A02:09

SubIndex 009

RO

0x0000:00, 8

1A03:0

Subindex

DIG TxPDO-Map Inputs Device

RO

0x07 (7dec)

1A03:01

SubIndex 001

RO

0x0000:00, 1

1A03:02

SubIndex 002

RO

0xF600:02, 1

1A03:03

SubIndex 003

RO

0xF600:03, 1

1A03:04

SubIndex 004

RO

0x0000:00, 10

1A03:05

SubIndex 005

RO

0xF600:0E, 1

1A03:06

SubIndex 006

RO

0xF600:0F, 1

1A03:07

SubIndex 007

RO

0xF600:10, 1

1C00:0

Subindex

Sync manager type

RO

0x04 (4dec)

1C00:01

SubIndex 001

RO

0x01 (1dec)

1C00:02

SubIndex 002

RO

0x02 (2dec)

1C00:03

SubIndex 003

RO

0x03 (3dec)

1C00:04

SubIndex 004

RO

0x04 (4dec)

1C12:0

Subindex

RxPDO assign

RW

0x02 (2dec)

1C12:01

SubIndex 001

RW

0x1600 (5632dec)

1C12:02

SubIndex 002

RW

0x1601 (5633dec)

1C13:0

Subindex

TxPDO assign

RW

0x04 (4dec)

1C13:01

SubIndex 001

RW

0x1A00 (6656dec)

1C13:02

SubIndex 002

RW

0x1A01 (6657dec)

1C13:03

SubIndex 003

RW

0x1A02 (6658dec)

1C13:04

SubIndex 004

RW

0x1A03 (6659dec)

Index (hex)

Name

Flags

Default value

1C32:0

Subindex

SM output parameter

RO

0x20 (32dec)

1C32:01

Sync mode

RW

0x0001 (1dec)

1C32:02

Cycle time

RW

0x000F4240 (1000000dec)

1C32:03

Shift time

RO

0x00000000 (0dec)

1C32:04

Sync modes supported

RO

0xC007 (49159dec)

1C32:05

Minimum cycle time

RO

0x0003D090 (250000dec)

1C32:06

Calc and copy time

RO

0x00000000 (0dec)

1C32:07

Minimum delay time

RO

0x00000000 (0dec)

1C32:08

Command

RW

0x0000 (0dec)

1C32:09

Maximum delay time

RO

0x00000000 (0dec)

1C32:0B

SM event missed counter

RO

0x0000 (0dec)

1C32:0C

Cycle exceeded counter

RO

0x0000 (0dec)

1C32:0D

Shift too short counter

RO

0x0000 (0dec)

1C32:20

Sync error

RO

0x00 (0dec)

1C33:0

Subindex

SM input parameter

RO

0x20 (32dec)

1C33:01

Sync mode

RW

0x0022 (34dec)

1C33:02

Cycle time

RW

0x000F4240 (1000000dec)

1C33:03

Shift time

RO

0x00000000 (0dec)

1C33:04

Sync modes supported

RO

0xC007 (49159dec)

1C33:05

Minimum cycle time

RO

0x0003D090 (250000dec)

1C33:06

Calc and copy time

RO

0x00000000 (0dec)

1C33:07

Minimum delay time

RO

0x00000000 (0dec)

1C33:08

Command

RW

0x0000 (0dec)

1C33:09

Maximum delay time

RO

0x00000000 (0dec)

1C33:0B

SM event missed counter

RO

0x0000 (0dec)

1C33:0C

Cycle exceeded counter

RO

0x0000 (0dec)

1C33:0D

Shift too short counter

RO

0x0000 (0dec)

1C33:20

Sync error

RO

0x00 (0dec)

6000:0

Subindex

CNT Inputs

RO

0x11 (17dec)

6000:03

Set counter done

RO

0x00 (0dec)

6000:04

Counter inhibited

RO

0x00 (0dec)

6000:05

Status of input UD

RO

0x00 (0dec)

6000:06

Status of input clock

RO

0x00 (0dec)

6000:0E

Sync error

RO

0x00 (0dec)

6000:0F

TxPDO State

RO

0x00 (0dec)

6000:10

TxPDO Toggle

RO

0x00 (0dec)

6000:11

Counter value

RO

0x00000000 (0dec)

6010:0

Subindex

CNT Inputs

RO

0x11 (17dec)

6010:03

Set counter done

RO

0x00 (0dec)

6010:04

Counter inhibited

RO

0x00 (0dec)

6010:05

Status of input UD

RO

0x00 (0dec)

6010:06

Status of input clock

RO

0x00 (0dec)

6010:0E

Sync error

RO

0x00 (0dec)

6010:0F

TxPDO State

RO

0x00 (0dec)

6010:10

TxPDO Toggle

RO

0x00 (0dec)

6010:11

Counter value

RO

0x00000000 (0dec)

Index (hex)

Name

Flags

Default value

6020:0

Subindex

DIG Inputs

RO

0x08 (8dec)

6020:01

Input 0

RO

0x00 (0dec)

6020:02

Input 1

RO

0x00 (0dec)

6020:03

Input 2

RO

0x00 (0dec)

6020:04

Input 3

RO

0x00 (0dec)

6020:05

Input 4

RO

0x00 (0dec)

6020:06

Input 5

RO

0x00 (0dec)

6020:07

Input 6

RO

0x00 (0dec)

6020:08

Input 7

RO

0x00 (0dec)

7000:0

Subindex

CNT Outputs

RO

0x11 (17dec)

7000:03

Set counter

RO

0x00 (0dec)

7000:04

Inhibit counter

RO

0x00 (0dec)

7000:11

Set counter value

RO

0x00000000 (0dec)

7010:0

Subindex

CNT Outputs

RO

0x11 (17dec)

7010:03

Set counter

RO

0x00 (0dec)

7010:04

Inhibit counter

RO

0x00 (0dec)

7010:11

Set counter value

RO

0x00000000 (0dec)

8000:0

Subindex

CNT Settings

RW

0x13 (19dec)

8000:03

Enable reload

RW

0x00 (0dec)

8000:04

Count down

RW

0x00 (0dec)

8000:05

Operating mode

RW

0x01 (1dec)

8000:13

Counter reload value

RW

0x00000000 (0dec)

8010:0

Subindex

CNT Settings

RW

0x13 (19dec)

8010:03

Enable reload

RW

0x00 (0dec)

8010:04

Count down

RW

0x00 (0dec)

8010:05

Operating mode

RW

0x01 (1dec)

8010:13

Counter reload value

RW

0x00000000 (0dec)

8022:0

Subindex

DIG Filter Settings

RW

0x08 (8dec)

8022:01

Input 0

RW

0x00 (0dec)

8022:02

Input 1

RW

0x00 (0dec)

8022:03

Input 2

RW

0x00 (0dec)

8022:04

Input 3

RW

0x00 (0dec)

8022:05

Input 4

RW

0x00 (0dec)

8022:06

Input 5

RW

0x00 (0dec)

8022:07

Input 6

RW

0x00 (0dec)

8022:08

Input 7

RW

0x00 (0dec)

F000:0

Subindex

Modular device profile

RO

0x02 (2dec)

F000:01

Module index distance

RO

0x0010 (16dec)

F000:02

Maximum number of modules

RO

0x0003 (3dec)

F008

Code word

RW

0x00000000 (0dec)

F010:0

Subindex

Module list

RW

0x03 (3dec)

F010:01

SubIndex 001

RW

0x00000096 (150dec)

F010:02

SubIndex 002

RW

0x00000096 (150dec)

F010:03

SubIndex 003

RW

0x00000118 (280dec)

Index (hex)

Name

Flags

Default value

F600:0

Subindex

DIG Inputs

RO

0x10 (16dec)

F600:02

Error channel 1

RO

0x00 (0dec)

F600:03

Error channel 2

RO

0x00 (0dec)

F600:0E

Sync error

RO

0x00 (0dec)

F600:0F

TxPDO State

RO

0x00 (0dec)

F600:10

TxPDO Toggle

RO

0x00 (0dec)

Key

Flags:
RO (Read Only): this object can be read only