Excel configuration

In general, the configuration can be done entirely via the visualization.

With larger systems it is recommended to carry out the configuration via Excel. In general, all worksheets are already available on the controller on delivery. Otherwise you can save them on the end device via Save basic settings on Settings page 2. You can copy these files to the USB flash drive using the Export USB function. All files are then located in the subfolder "Beckhoff" (the USB stick must not be write-protected). With network knowledge, the FTP directory ftp://192.168.2.10/ also lends itself. This is an example link; first adapt the IP to the corresponding device settings.

The limits of the input table must be adhered to!

The following files are created:

  • Group_Data.csv
  • Circuit_Data.csv
  • Lamp_Data.csv
  • Sensor_Data.csv
  • Switch_Data.csv
  • Switch_Dali_Data.csv
  • Schedule_Data.csv
  • HCL_Data.csv
  • Energy_Data.csv
  • Scenes_Data.cxv
  • Scene_Group_Data.csv

 

Note
Do not change the table names or the file format!

Do not change the table names or the file format ".csv". All files must always be available – even if they aren't used.

 

Group_Data:

Parameter

Input

Name

Naming

Set Value

Lowest value (see Settings).. 254

Basic Value

Lowest value (see Settings).. 254

Setpoint

5..5000

Overrun time 1 (Delay time 1)

1..600 in minutes.

Overrun time 2 (Delay time 2)

0..600 in minutes

Parameters blocked

0: Free

1: Blocked

Area

0..10

Light mode

1: Fixed Control

2: Daylight Control

Control mode

0: Sensor, push button or schedule

1: Sensor with activation via schedule or push button

2: Daylight Control

3: Fully automatic

4: Semi-automatic

5: Manual push button

6: Manual push button with overrun

HCL dimming position

0: Disabled

1: Enabled

Slave Gr.1-Gr.8

0..200

Activate

0: Disabled

1: Enabled

 

Circuit_Data:

Parameter

Input

Name

Naming

Group 1.. 4

0..200

Activate

0: Disabled

1: Enabled

 

Lamp_Data:

Parameter

Input

Name

Naming

Group 1.. 8

0..200

Activate

0: Disabled

1: Enabled

 

Sensor_Data:

Parameter

Input

Name

Naming

Group 1.. 4

0..200

Scene

0: Disabled

1..30: Enabled

Sensor type

1: Steinel Dali-2 IR

2: Steinel LiveLink HF/IR

3: Steinel LiveLink light sensor

4: Steinel LiveLink US

5: BEG Dali-2 Luxomat, Osram Dali-2

6: Tridonic MSensor

7: Extern Input

8: Esylux Dali-2

9: Lunatone CS

Range

0..255 (low - high)

Sensitivity

1..15 (high - low)

Activate

0: Disabled

1: Enabled

 

Switch_Data:

Parameter

Input

Name

Naming

Group 1...8

1..200

Scene

0: Disabled

1..30: Enabled

Area

0: Disabled

1..10: Enabled

Central off

0: Disabled

1: Enabled

Function as

0: Disabled

1 .. 100: Enabled

Activate

0: Disabled

1: Enabled

Switch_Dali_Data:

Parameter

Input

Name

Naming

Switch type

1: Lunatone MC+ Dali-2, Osram Push Coupler

2: Esylux Sensor

Groups 1&2 T1-T4

1..200

Scene T1-T4

0: Disabled

1..30: Enabled

Area T1-T4

0: Disabled

1..10: Enabled

Central off T1-T4

0: Disabled

1: Enabled

Activate

0: Disabled

1: Enabled

 

Schedule_Data:

Parameter

Input

Name

Naming

Mo-Su

0: Disabled

1: Enabled

Group 1.. 8

0..200

Scene

0: Disabled

1..30: Enabled

Scene Off

0: Disabled

1: Enabled

Area

0: Disabled

1..10: Enabled

On h

On m

On s

0..23

0..59

0..59

Off h

Off m

Off s

0..23

0..59

0..59

Activate

0: Disabled

1: Enabled

 

HCL_Data:

Parameter

Input

Time Hour

0..23

Time Minute

0..59

Color

2700..6500

Dimming position

10..100

Sunrise

0: Disabled

1: Enabled

Sunset

0: Disabled

1: Enabled

Drive time in min

3..240

Activate

0: Disabled

1: Enabled

Energy_Data:

Parameter

Input

Name

Naming

ct ratio

1..10000

Activate

0: Disabled

1: Enabled

 

 

Scenes_Data:

Parameter

Input

Name

Naming

Dimming

0: Disabled

1: Enabled

Scene off

0: Disabled

1: Enabled

Scene first off

(Scene first off)

0: Disabled

1: Enabled

Activate

0: Disabled

1: Enabled

 

Scene_Group_Data:

Parameter

Input

Group

(Display only: described by Scenes_Data)

Scene S1..S30

0: Disabled

1: Enabled

Value input

0..254