Excel configuration
In general, the configuration can be done entirely via the visualization.
With larger systems it is recommended to carry out the configuration via Excel. In general, all worksheets are already available on the controller on delivery. Otherwise you can save them on the end device via Save basic settings on Settings page 2. You can copy these files to the USB flash drive using the Export USB function. All files are then located in the subfolder "Beckhoff" (the USB stick must not be write-protected). With network knowledge, the FTP directory ftp://192.168.2.10/ also lends itself. This is an example link; first adapt the IP to the corresponding device settings.
The limits of the input table must be adhered to!
The following files are created:
- Group_Data.csv
- Circuit_Data.csv
- Lamp_Data.csv
- Sensor_Data.csv
- Switch_Data.csv
- Switch_Dali_Data.csv
- Schedule_Data.csv
- HCL_Data.csv
- Energy_Data.csv
- Scenes_Data.cxv
- Scene_Group_Data.csv
Do not change the table names or the file format ".csv". All files must always be available – even if they aren't used.
Group_Data:
Parameter | Input |
Name | Naming |
Set Value | Lowest value (see Settings).. 254 |
Basic Value | Lowest value (see Settings).. 254 |
Setpoint | 5..5000 |
Overrun time 1 (Delay time 1) | 1..600 in minutes. |
Overrun time 2 (Delay time 2) | 0..600 in minutes |
Parameters blocked | 0: Free 1: Blocked |
Area | 0..10 |
Light mode | 1: Fixed Control 2: Daylight Control |
Control mode | 0: Sensor, push button or schedule 1: Sensor with activation via schedule or push button 2: Daylight Control 3: Fully automatic 4: Semi-automatic 5: Manual push button 6: Manual push button with overrun |
HCL dimming position | 0: Disabled 1: Enabled |
Slave Gr.1-Gr.8 | 0..200 |
Activate | 0: Disabled 1: Enabled |
Circuit_Data:
Parameter | Input |
Name | Naming |
Group 1.. 4 | 0..200 |
Activate | 0: Disabled 1: Enabled |
Lamp_Data:
Parameter | Input |
Name | Naming |
Group 1.. 8 | 0..200 |
Activate | 0: Disabled 1: Enabled |
Sensor_Data:
Parameter | Input |
Name | Naming |
Group 1.. 4 | 0..200 |
Scene | 0: Disabled 1..30: Enabled |
Sensor type | 1: Steinel Dali-2 IR 2: Steinel LiveLink HF/IR 3: Steinel LiveLink light sensor 4: Steinel LiveLink US 5: BEG Dali-2 Luxomat, Osram Dali-2 6: Tridonic MSensor 7: Extern Input 8: Esylux Dali-2 9: Lunatone CS |
Range | 0..255 (low - high) |
Sensitivity | 1..15 (high - low) |
Activate | 0: Disabled 1: Enabled |
Switch_Data:
Parameter | Input |
Name | Naming |
Group 1...8 | 1..200 |
Scene | 0: Disabled 1..30: Enabled |
Area | 0: Disabled 1..10: Enabled |
Central off | 0: Disabled 1: Enabled |
Function as | 0: Disabled 1 .. 100: Enabled |
Activate | 0: Disabled 1: Enabled |
Switch_Dali_Data:
Parameter | Input |
Name | Naming |
Switch type | 1: Lunatone MC+ Dali-2, Osram Push Coupler 2: Esylux Sensor |
Groups 1&2 T1-T4 | 1..200 |
Scene T1-T4 | 0: Disabled 1..30: Enabled |
Area T1-T4 | 0: Disabled 1..10: Enabled |
Central off T1-T4 | 0: Disabled 1: Enabled |
Activate | 0: Disabled 1: Enabled |
Schedule_Data:
Parameter | Input |
Name | Naming |
Mo-Su | 0: Disabled 1: Enabled |
Group 1.. 8 | 0..200 |
Scene | 0: Disabled 1..30: Enabled |
Scene Off | 0: Disabled 1: Enabled |
Area | 0: Disabled 1..10: Enabled |
On h On m On s | 0..23 0..59 0..59 |
Off h Off m Off s | 0..23 0..59 0..59 |
Activate | 0: Disabled 1: Enabled |
HCL_Data:
Parameter | Input |
Time Hour | 0..23 |
Time Minute | 0..59 |
Color | 2700..6500 |
Dimming position | 10..100 |
Sunrise | 0: Disabled 1: Enabled |
Sunset | 0: Disabled 1: Enabled |
Drive time in min | 3..240 |
Activate | 0: Disabled 1: Enabled |
Energy_Data:
Parameter | Input |
Name | Naming |
ct ratio | 1..10000 |
Activate | 0: Disabled 1: Enabled |
Scenes_Data:
Parameter | Input |
Name | Naming |
Dimming | 0: Disabled 1: Enabled |
Scene off | 0: Disabled 1: Enabled |
Scene first off (Scene first off) | 0: Disabled 1: Enabled |
Activate | 0: Disabled 1: Enabled |
Scene_Group_Data:
Parameter | Input |
---|---|
Group | (Display only: described by Scenes_Data) |
Scene S1..S30 | 0: Disabled 1: Enabled |
Value input | 0..254 |