Priority

The global variable list uses XBA_BACnetParam from the Tc3_XBA library to determine the BACnet plant priorities.

The chapter Commanding contains further information on the subject of priorities.

Syntax

VAR_GLOBAL
  nProgram             : UDINT := TO_UDINT(LIMIT(1,XBA_BACnetParam.aPriority[2],16));
  nManualRemote        : UDINT := TO_UDINT(LIMIT(1,XBA_BACnetParam.aPriority[3],16));
  nManualLocal         : UDINT := TO_UDINT(LIMIT(1,XBA_BACnetParam.aPriority[4],16));
  nCritical            : UDINT := TO_UDINT(LIMIT(1,XBA_BACnetParam.aPriority[5],16));
  nLifeSafety          : UDINT := TO_UDINT(LIMIT(1,XBA_BACnetParam.aPriority[6],16));
END_VAR

Name

Type

Description

nProgram

UDINT

Priority "Program", program control.

nManualRemote

UDINT

Priority "Manual Remote", remote manual override (MBE).

nManualLocal

UDINT

Priority "Manual Local", local manual override (LVB).

nCritical

UDINT

Priority "Critical", plant safety.

nLifeSafety

UDINT

Priority "Life Safety", personal safety.