FB_BA_ActuatorMdlt

FB_BA_ActuatorMdlt 1:

The template is used to control modulating aggregates. It essentially consists of an AO object for controlling an aggregate, the priority switch PrioSwiVal for determining the modulation command, the multiplexer MuxMdlt for determining the control value and the function block PlantLock, which collects all safety-related faults.

FB_BA_ActuatorMdlt 2:

The initialization of the template takes place within the method FB_Init.

Block diagram

FB_BA_ActuatorMdlt 3:

Syntax

FUNCTION_BLOCK FB_BA_ActuatorMdlt EXTENDS FB_BA_View
VAR_INPUT
  stCmd             : ST_BA_Mdlt;
  fValPgm           : REAL;
END_VAR
VAR_OUTPUT
  fMdlt             : REAL;
  bDst              : BOOL;
  eActivePrio       : E_BA_Priority;
END_VAR
VAR_INPUT CONSTANT PERSISTENT
  {attribute 'parameterCategory'  := 'Behaviour'}
  fMinModulation    : REAL := 20;
  {attribute 'parameterCategory'  := 'Behaviour'}
  fMaxModulation    : REAL := 100;
END_VAR
VAR_INPUT CONSTANT
  Mdlt              : FB_BA_AO_Raw;
  PlantLock         : FB_BA_PlantLock;
END_VAR
VAR
  bPrioSfty         : BOOL;
  bPrioCrit         : BOOL;

  PrioSwiVal        : FB_BA_PrioSwi_UDI04;
  MuxMdlt           : FB_BA_MMUX_R04;
END_VAR

FB_BA_ActuatorMdlt 4: Inputs

Name

Type

Description

stCmd

ST_BA_Mdlt

The enables and modulation commands are transmitted to the template via the command structure stCmd. The command with the highest priority determines the switching command at the binary output object Cmd and the control command at the analog output object Mdlt.

fValPgm

REAL

The control signal for modulation command E_BA_MdltCmd.eOn is transmitted to the template via the input variable fValPgm.

FB_BA_ActuatorMdlt 5: Outputs

Name

Type

Description

fMdlt

REAL

Current value of the analog output object.

bDst

BOOL

The variable is an evaluation of the lock priorities "Safety" and "Critical" of the project structure and indicates a triggered event.

eActivePrio

E_BA_Priority

Display of the active priority.

FB_BA_ActuatorMdlt 6: Inputs CONSTANT PERSISTENT

Name

Type

Description

fMinModulation

REAL

Constant minimum value when modulation command E_BA_MdltCmd.eMin is pending.

fMaxModulation

REAL

Constant maximum value when modulation command E_BA_MdltCmd.eMax is pending.

FB_BA_ActuatorMdlt 7: Inputs CONSTANT

Name

Type

Description

Mdlt

FB_BA_AO_Raw

Current value of the analog output object.

PlantLock

FB_BA_PlantLock

The function block PlantLock collects all safety-relevant faults at this level of the project structure and triggers switching commands in the template accordingly.

Variables

Name

Type

Description

bPrioSfty

BOOL

The variable is an evaluation of the "Safety" lock priority of the project structure.

bPrioCrit

BOOL

The variable is an evaluation of the "Critical" lock priority of the project structure.

bPrioSwiVal

FB_BA_PrioSwi_UDI04

The priority switch PrioSwiVal uses the command structure stCmd to determine the modulation command for the multiplexers MuxCmd and MuxMdlt.

MuxMdlt

FB_BA_MMUX_R04

The multiplexer MuxMdlt determines the current control value from the modulation values fValPgm, fMinModulation and fMaxModulation and the modulation command of the priority switch PrioSwiVal. The result is sent to the analog output object Mdlt.