FB_BA_SunBldPosHMI

FB_BA_SunBldPosHMI 1:

The function block FB_BA_SunBldPosHMI is used for position and angle specification via a user interface. With each rising edge at bStart an active positioning telegram with the target position fPos and the slat angle fAngl is output at stSunBld.

The input bRstManFnct is used to reset the output telegram. The telegram is described as follows:

stSunBld.bActv := FALSE;
stSunBld.fPos  := 0.0;
stSunBld.fAngl := 0.0;

The input bRstManFnct has a static effect: as long as it is TRUE, the output telegram is set to the values mentioned above.

In addition, the function block output bActv is set to FALSE. This is to indicate whether an active telegram is output.

FB_BA_SunBldPosHMI 2: Inputs

VAR_INPUT
  fPos         : REAL;
  fAngl        : REAL;
  bStart       : BOOL;
  bRstManFnct  : BOOL;
END_VAR

Name

Type

Description

fPos

REAL

Input of the target position.

fAngl

REAL

Input of the lamella angle.

bStart

BOOL

A rising edge at this input outputs an active telegram with the entered target position fPos and the lamella angle fAngl.

bRstManFnct

BOOL

A TRUE at this input deletes the telegram at the output (stSunBld.bActv = FALSE, bActv = FALSE, stSunBld.fPos = 0, stSunBld.fAngl = 0) and no new values are passed through. The output bActv then also goes to FALSE.

FB_BA_SunBldPosHMI 3: Inputs CONSTANT PERSISTENT

VAR_INPUT CONSTANT PERSISTENT
  ePrio  : E_BA_SunBldPrio := E_BA_SunBldPrio.eManualActuator;
END_VAR

Name

Type

Description

ePrio

E_BA_SunBldPrio

Priority of the output telegram.

FB_BA_SunBldPosHMI 4: Outputs

VAR_OUTPUT
  stSunBld  : ST_BA_SunBld;
  bActv     : BOOL;
END_VAR

Name

Type

Description

stSunBld

ST_BA_SunBld

Output telegram, for the position and angle of the lamella.

bActv

BOOL

Corresponds to the boolean value bActv in the blind telegram ST_BA_SunBld and is solely used to indicate whether the function block sends an active telegram.

Requirements

Development environment

Required PLC library

TwinCAT from v3.1.4024.22

Tc3_BA2 from v5.2.5.0