FB_BA_EvtCategory

The template contains a Notification Class Object.
Each BACnet object that is to generate messages by means of Intrinsic Reporting or Algorithmic Change Reporting must be assigned a Notification Class Object that contains the information for the distribution of the event messages.
The Notification Class Object defines which priorities are assigned to the event messages, whether the events require acknowledgement and which recipients should receive the messages.
![]() | The initialization of the template takes place within the method FB_Init. |
Block diagram

Syntax
FUNCTION_BLOCK FB_BA_EvtCategory EXTENDS FB_BA_View
VAR_INPUT CONSTANT
EC : FB_BA_EC;
END_VAR
Inputs CONSTANT