FB_GseMsvCBPublisherClass

Publisher implementation of the SV control block.

Namespace: Tc3_Gse
Library: Tc3_Gse (Tc3_Gse.compiled-library)

Inheritance hierarchy

FB_ServiceErrorClass -> FB_GseMsvCBPublisherClass

FUNCTION_BLOCK FB_GseMsvCBPublisherClass EXTENDS FB_ServiceErrorClass IMPLEMENTS I_GseMsvCBPublisherClass
VAR_OUTPUT
    stTx : ST_GseMsvCBPublisherTx;
END_VAR

FB_GseMsvCBPublisherClass 1: Interfaces

Type

Description

I_GseMsvCBPublisherClass

Interface of the SV control block implementation.

FB_GseMsvCBPublisherClass 2: Outputs

Name

Type

Description

stTx

ST_GseMsvCBPublisherTx

Information sent in the last SV message.

FB_GseMsvCBPublisherClass 3: Methods

Name

Description

Execute

Executes the Publisher state machine.

Start

Starts sending SV messages.

Stop

Stops sending SV messages.

Update

Triggers an immediate sending of an SV message.

FB_GseMsvCBPublisherClass 4: Properties

Name

Type

Access

Description

ipAdapter

I_GseAdapterClass

Set

Interface of the SV network adapter.