T_CP24IOA
Structured TwinCAT object address.
Syntax
TYPE T_CP24IOA:
STRUCT
ioMap : E_IEC870_5_101IOMappingType := MAP_AREA_NONE;
byteOffs : WORD := 0;
bitOffs : BYTE(0..7) := 0;
END_STRUCT
END_TYPEioMapType: TwinCAT PLC process data area. This parameter defines the mapping for the TwinCAT PLC and IEC application object process data.
byteOffs: TwinCAT PLC process data byte offset. Value range: 0..65535.
bitOffs: TwinCAT PLC process data bit offset. Value range: 0..7.
Requirements
Development environment | Target system type | PLC libraries to be linked (category group) |
|---|---|---|
TwinCAT v3.1.4012.0 | PC oder CX (x86, x64, Arm®) | Tc2_IEC60870_5_10x (Communication->IEC60870) |