MC_ReadMoveModulo

MC_ReadMoveModulo 1:

This function block provides a read-only view on the parameters and status of the move modulo command attached to CommandHandle. While Enable is TRUE the outputs are updated on every call. Valid signals that they describe a move modulo command. The Command* outputs stay FALSE until the axis has processed the command.

Syntax

Definition:

FUNCTION_BLOCK MC_ReadMoveModulo
VAR_IN_OUT
    CommandHandle   : Reference To MC_CommandHandle;
END_VAR
VAR_INPUT
    Enable          : BOOL;
END_VAR
VAR_OUTPUT
    Valid           : BOOL;
    Error           : BOOL;
    ErrorId         : UDINT;
    Position        : LREAL;
    AdditionalTurns : UDINT;
    Velocity        : LREAL;
    Acceleration    : LREAL;
    Deceleration    : LREAL;
    Jerk            : LREAL;
    BufferMode      : EBufferMode;
    Direction       : EModuloDirection;
    CommandQueued   : BOOL;
    CommandDone     : BOOL;
    CommandActive   : BOOL;
    CommandAborted  : BOOL;
    CommandError    : BOOL;
    CommandErrorId  : UDINT;
END_VAR

MC_ReadMoveModulo 2: Inputs

Name

Type

Default

Description

Enable

BOOL

 

The outputs are updated while TRUE.

MC_ReadMoveModulo 3: In/Outputs

Name

Type

Description

CommandHandle

Reference To MC_CommandHandle

Handle of the command to observe

MC_ReadMoveModulo 4: Outputs

Name

Type

Description

Valid

BOOL

The outputs describe the move modulo command attached to CommandHandle.

Error

BOOL

Error occurred within function block, e.g. no command attached to CommandHandle or not a move modulo command.

ErrorId

UDINT

Error identifier

Position

LREAL

Commanded modulo position ([PosUnit])

AdditionalTurns

UDINT

Number of additional modulo turns in the commanded direction.

Velocity

LREAL

Maximum velocity ([PosUnit]/s, positive)

Acceleration

LREAL

Maximum acceleration ([PosUnit]/s^2, positive)

Deceleration

LREAL

Maximum deceleration ([PosUnit]/s^2, positive)

Jerk

LREAL

Maximum jerk ([PosUnit]/s^3, positive)

BufferMode

EBufferMode

Chronological sequence of the command

Direction

EModuloDirection

Commanded direction. Must have value <> EModuloDirection.ShortestDistance if AdditionalTurns has value > 0.

CommandQueued

BOOL

Command is queued for execution.

CommandDone

BOOL

Commanded position reached.

CommandActive

BOOL

The command is currently active.

CommandAborted

BOOL

Command is aborted by another command.

CommandError

BOOL

Error occurred while executing the command.

CommandErrorId

UDINT

Error identifier of the command

Possible error codes

For this function block, the following values, among others, are possible for the ErrorId output:

Error(Hex)

Error(Dec)

Error type

Description

0x8189

33161

Function Block

Invalid reference passed to function block. An invalid reference (or pointer) was used in a function block call. This can happen if a reference type is used before it was initialized.

0x81ba

33210

Function Block

Invalid command type passed to function block. The command type passed to the function block does not match the command expected by it (e.g., a Read function block is given a command of a different type than the one it reads).

0x81c9

33225

Function Block

Command handle is not initialized. The MC_CommandHandle object does not contain an attached command.

An overview of all NC error codes can be found here:

If the data size is invalid, the error ADSERR_DEVICE_INVALIDSIZE (0x705; 1797) may occur.

You can find an overview of all ADS return codes here:

Possible error codes

For this function block, the following values, among others, are possible for the ErrorId output:

Error(Hex)

Error(Dec)

Error type

Description

0x8189

33161

Function Block

Invalid reference passed to function block. An invalid reference (or pointer) was used in a function block call. This can happen if a reference type is used before it was initialized.

0x81ba

33210

Function Block

Invalid command type passed to function block. The command type passed to the function block does not match the command expected by it (e.g., a Read function block is given a command of a different type than the one it reads).

0x81c9

33225

Function Block

Command handle is not initialized. The MC_CommandHandle object does not contain an attached command.

An overview of all NC error codes can be found here:

If the data size is invalid, the error ADSERR_DEVICE_INVALIDSIZE (0x705; 1797) may occur.

You can find an overview of all ADS return codes here:

Version information

  • TwinCAT Standard >= v3.1.4026.23.1
  • TF5500 MC3 Base >= v4.0.24