MC_WaitForStableActualPosition
This function block waits for a stable actual position. The command is always buffered and may only be triggered when the previous command ends with zero dynamics.
Syntax
Definition:
FUNCTION_BLOCK MC_WaitForStableActualPosition
VAR_IN_OUT
Axis : Reference To AXIS_REF;
END_VAR
VAR_INPUT
Execute : BOOL;
PositionTolerance : LREAL;
WaitDuration : LREAL;
TimeoutDuration : LREAL;
END_VAR
VAR_OUTPUT
InPositionWindow : BOOL;
Done : BOOL;
Busy : BOOL;
Active : BOOL;
CommandAborted : BOOL;
Error : BOOL;
ErrorId : UDINT;
END_VAR
Inputs
Name | Type | Default | Description |
|---|---|---|---|
Execute | BOOL |
| Triggers the command on a rising edge. |
PositionTolerance | LREAL | #Invalid | Position tolerance around the set position ([PosUnit], positive). The actual position must remain within this window for the command to succeed. |
WaitDuration | LREAL | #Invalid | Duration (in seconds) that the actual position needs to consecutively stay inside the position window. Must have a value >= 0. |
TimeoutDuration | LREAL | #Ignore | Duration (in seconds) after which an error is triggered if the actual position is not inside the position window. Set to 'Ignore' if no timeout is desired. Otherwise must have a value > WaitDuration. |
Outputs
Name | Type | Description |
|---|---|---|
InPositionWindow | BOOL | Actual position is currently inside the position window. |
Done | BOOL | Actual position has been consecutively inside the position window for at least WaitDuration. |
Busy | BOOL | Function block is not finished and new output values are to be expected. |
Active | BOOL | Function block has active control on the axis. While Active is TRUE, the set position remains on the final position of the previous command and the set dynamics remain zero. |
CommandAborted | BOOL | Command is aborted by another command. |
Error | BOOL | Error occurred within function block. |
ErrorId | UDINT | Error identifier |
Possible error codes
For this function block, the following values, among others, are possible for the ErrorId output:
Error(Hex) | Error(Dec) | Error type | Description |
|---|---|---|---|
0x8145 | 33093 | Function Block | Mapping of cyclic interface between NC and PLC is missing (e.g., AXIS_REF, AXES_GROUP_REF, ...). A reference used by the function block (e.g., to an axis, group, mover or other motion object) is not linked to the corresponding NC object, or its cyclic mapping is incomplete. |
0x8151 | 33105 | State | Command is not allowed in current axis state. If the axis has no controller enable, is in error or has been added to a group, some commands are not permitted. |
0x8196 | 33174 | Initialization | Invalid position or distance. The actual or specified position or distance could not be determined or is invalid. |
0x81b7 | 33207 | Function Block | The specified time or duration is invalid. |
An overview of all NC error codes can be found here:
Version information
- TwinCAT Standard >= v3.1.4026.23.1
- TF5500 MC3 Base >= v4.0.6