ValveCharacterizationOptions

Contains additional options for MC_ValveCharacterization

Syntax

Definition:

TYPE ValveCharacterizationOptions :
STRUCT
    WaitTimeAfterVelocityStep   : LREAL;
    WaitTimeAtPositionLimit     : LREAL;
    MinimumTravelPerMeasurement : LREAL;
    Acceleration                : LREAL;
    Deceleration                : LREAL;
    Jerk                        : LREAL;
    OutputLimit                 : LREAL;
END_STRUCT
END_TYPE

Parameters

Name

Type

Default

Description

WaitTimeAfterVelocityStep

LREAL

0.2

Wait time after velocity step ([sec]). Wait time should be large enough for velocity oscillations to settle. Must have value >= 0.0 s. Default: 0.2.

WaitTimeAtPositionLimit

LREAL

0.5

Wait time at a position limit ([sec]). Wait time should be large enough for the axis to come to a complete stop. Must have value >= 0.0 s. Wait time can be extended using the Wait input if it depends on external processes (e.g. switching valves). Default: 0.5.

MinimumTravelPerMeasurement

LREAL

10.0

Minimum position distance per velocity measurement ([PosUnit]). Must have value >= 0.0. Default 10.0.

Acceleration

LREAL

#Default

Maximum acceleration ([PosUnit]/s^2, positive)

Deceleration

LREAL

#Default

Maximum deceleration ([PosUnit]/s^2, positive)

Jerk

LREAL

#Default

Maximum jerk ([PosUnit]/s^3, positive)

OutputLimit

LREAL

1.0

Maximum valve output during valve characterization. Valid values: [0..1]. Valve characterization may exceed this value by up to OutputStepSize value.

Version information

  • TwinCAT Standard >= v3.1.4026.23.1
  • TF5560 MC3 FluidPower >= v4.0.6 (includes TF5500 MC3 Base >= v4.0.6)