Description

P-AXIS-00014

Identification code for absolute path measurement system

Description

If an absolute path measurement system is used, then the parameter must be set to 1. So no homing is necessary.

Parameter

kenngr.abs_pos_gueltig

Data type

BOOLEAN

Data range

0/1

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

Drive types

Simulation, SERCOS, CANopen

Remarks

 

P-AXIS-00015

Axis mode

Description

Axes can be traversed in different operating modes.

Parameter

kenngr.achs_mode

Data type

UNS32

Data range

0x00000001 - 0x10000000

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0x00000001

Drive types

----

Remarks

 

The following operation modes can be parameterised(1):

Value

Meaning

Axis type

Interpolator type

 

Description

ACHSMODE_

 

path

spindle

0x00000001

The axis is operated as a linear axis; no modulo calculation is executed in the channel. For example, rotary axis with restricted motion range; must be set as default for linear axes.

..LINEAR(1)

T, R

X

 

0x00000004

A modulo calculation always takes place after the destination position has been reached. Regardless of the operation mode selected for rotary axes, a modulo calculation is always executed in the position controller. In this way, modulo circle compensation can be executed if required.

..MODULO(1)

R

X

X

0x00000040

Axis is used as a face turning axis (turning functions).

..PLANDREHEN

T

X

 

0x00000080

Axis is used as a longitudinal turning axis (turning functions).

..LAENGSDREHEN

T

X

 

0x00000100

For a spindle an automatic homing before positioning the spindle can be pre-vented. This is only relevant if the axis is not referenced. The function is drive-dependent.

..KEINE_AUTO_RPF

R

 

X

0x00000200

Axis for kinematic 'C axis' transformation.

..CAX

R

X

X

0x00000400

Modulo calculation for linear axis. (Example: conveyor belt with drive motor where the position on the belt is programmed in mm).

..MODULO_LINEAR

R

X

 

0x00000800

Axis is released for mechanical blocking by the PLC.

This axis mode is not available for TwinCAT systems.

..CLAMPABLE

T, R

X

 

0x00001000

Axis carries a rotary workpiece table.

..ROT_TABLE

T, R

X

 

0x00008000

Monitoring of axis collision.

..COLL_CHECK

T

X

 

0x00010000

Master axis of gantry coupling.

..GANTRY_MASTER

T, R

X

 

0x00020000

Slave axis of gantry coupling.

..GANTRY_SLAVE

T, R

X

 

0x00040000

Identifier for PLC spindle with axis interface

..SPINDLE_EXT_CTRL

R

 

X

0x00080000

Input axis for additional external position command values (e.g. distance control).

..EXT_CTRL_INPUT

T

X

 

0x00100000

Pure encoder axis, only to display actual values (e.g. conveyor belt).

..COUNTER

T, R

X

X

0x00200000

Lead axis in combination with single feed axis and G194 (contouring with DIST_MASTER)

..LEAD_AXIS

T, R

X

 

0x00400000

The resolution (wegaufz/wegaufn) of this axis can be changed.

..ALLOW_RESOLUTION_
CHANGE(2)

T, R

X

X

0x00800000

Path-dependent dynamic weighting for this axis is possible.

..DYNAMIC_WEIGHTING

T, R

X

 

0x02000000

Path axis for tool centre point path

..PATH_LENGTH_TCP

R

X

 

0x04000000

Path axis for contour path

..PATH_LENGTH_
CONTOUR

R

X

 

0x08000000

Virtual lead axis for path interpolation

..VIRT_LEAD_AXIS

R

X

 

0x10000000

Axis carries the pressure roller for edge banding.

..LAH_OFFSET_AXIS

R

X

 

(1) One of the following two axis modes must always be defined:

- ACHSMODE_LINEAR or
- ACHSMODE_MODULO

All other bits of the parameter achs_mode are additional specifications. For example, the ACHSMODE_MODULO_LINEAR bit is only useful if combined with the ACHSMODE_MODULO bit.

(2) Changing certain axis parameters may be critical while a controller is running, e.g. path resolution,. Therefore, this parameter can be enabled by setting the bit ALLOW_RESOLUTION_CHANGE in axis mode. Otherwise, these parameters (P-AXIS-00234, P-AXIS-00233) can no longer be changed after controller start-up.

When the bit ALLOW_RESOLUTION_CHANGE is set, a check is first made whether the axis is interpolated, also when other critical parameters change. If the axis is currently in motion, this parameter update is rejected.

P-AXIS-00036

Access to cam signals

Description

The parameter defines the access to cam signals.

Parameter

lr_hw[i].cam_direct_access

Data type

BOOLEAN

Data range

0/1

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

1

drive types.

Conventional, Terminal, Lightbus, Profidrive

Remarks

This entry is not adopted when the axis parameter list is updated. Updates only become effective when the controller is rebooted.

P-AXIS-00038

Level of cam signals

Description

The parameter defines the level of cam signals.

Parameter

lr_hw[i].cam_level

Data type

BOOLEAN

Data range

0: 0-signal is active level.

When the reference cam switch is actuated, the value of the control unit element
gpAx[axis_idx]^.lr_mc_control.reference_cam.command_w on the HLI is FALSE.

1: 1-signal is active level (default).

When the reference cam switch is actuated, the value of the control unit element
gpAx[axis_idx]^.lr_mc_control.reference_cam.command_w on the HLI is TRUE.

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

1

Drive types

Conventional, Terminal, Lightbus, Profidrive

Remarks

 

P-AXIS-00064

Slow / fast movement down from cam

Description

This parameter sets the velocity during reversion down from cam.

Parameter

kenngr.fast_from_cam

Data type

BOOLEAN

Data range

0: Slow movement down from cam

1: Fast movement down from cam (default)

Axis types

T, R

Dimension

T: ----

R: ----

Default value

1

drive types.

----

Remarks

For further hardware-specific parameters relating to homing with cam, see P-AXIS-00036 - P-AXIS-00039.

P-AXIS-00074

Suppress homing for gantry slave axis

Description

This parameter can suppress the homing of gantry slave axes. When homing of the master axis is completed, the reference positions entered in the axis parameter lists of the slave axes are also adopted and monitoring of the gantry difference is started.

Parameter

kenngr.gantry_slave_no_homing

Data type

BOOLEAN

Data range

0/1

Axis types

T, R

Dimension

T: ----

R: ----

Default value

0

drive types.

----

Remarks

This parameter is not supported in the case of spindle axes.

P-AXIS-00084

Homing only with cam (without zero pulse)

Description

The homing position is detected by travel on the cam.

Parameter

kenngr.homing_without_zero_pulse

Data type

BOOLEAN

Data range

0: Homing with zero pulse of rotary transducer (default value).

1: Homing without zero pulse of rotary transducer (low accuracy).

Axis types

T, R

Dimension

T: ----

R:----

Default value

0

drive types.

----

Remarks

For further hardware-specific parameters relating to homing with cam, see P-AXIS-00036 - P-AXIS-00039.

P-AXIS-00152

Position of the reference point

Description

If homing is completed, the value from the parameter P-AXIS-00152 is taken as the absolute position for the axis

Parameter

getriebe[i].pos_refpkt

Data type

SGN32

Data range

swe_neg < pos_refpkt < swe_pos

Axis types

T, R, S

Dimension

T: 0.1 µm

R,S: 0.0001 °

Default value

0

drive types.

Simulation, Conventional, Terminal, Lightbus, Profidrive, CANopen

Remarks

 

P-AXIS-00156

Homing without cam

Description

A changeover of homing strategy can be carried out so that homing is done without cam (e.g. only with zero pulse), i.e. without reverting.

In this case the parameter P-AXIS-00156 should be set to TRUE.

Parameter

kenngr.ref_ohne_nocken

Data type

BOOLEAN

Data range

0/1

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

Conventional, Terminal, Lightbus, Profidrive

Remarks

To be assigned for analogue spindles only. If P-AXIS-00156 is assigned with 1 (TRUE), then it is imperative that P-AXIS-00157 is assigned with 1 (TRUE).

P-AXIS-00157

Homing without reverting

Description

Via parameter P-AXIS-00157 a restriction of homing can occur that will prohibit any reverting.

Parameter

kenngr.ref_ohne_rev

Data type

BOOLEAN

Data range

0/1

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

Conventional, Terminal, Lightbus, Profidrive

Remarks

The speed during reversing is set with the parameter P-AXIS-00064 (fast_from_cam). By reverting, it is possible to repeatedly move to the reference cam at slow speed.

To be assigned for analogue spindles only. P-AXIS-00157 must be assigned with 1 (TRUE) if P-AXIS-00156 is assigned with 1 (TRUE).

P-AXIS-00158

Preferred direction of axis for homing

Description

The parameter P-AXIS-00158 specifies the direction of travel if the axis does not remain on a cam.

The declaration of the signal level when the reference switch is actuated is given by the axis parameter P-AXIS-00038.

Parameter

kenngr.ref_richt

Data type

BOOLEAN

Data range

0: Negative direction

1: Positive direction

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

Simulation, Conventional, Terminal, Lightbus, Profidrive

Remarks

Positive direction signifies that the coordinate values increase.

Negative direction signifies that the coordinate values decrease.

P-AXIS-00161

Tool path up to zero pulse during homing simulation

Description

The parameter defines the tool path up to zero pulse during homing simulation.

Parameter

antr.simu.rpf_weg_bis_nip

Data type

SGN32

Data range

MIN(SGN32) ≤ rpf_weg_bis_nip ≤ MAX(SGN32)

Axis types

T, R, S

Dimension

T: 0.1µm

R,S: 0.0001 °

Default value

10

drive types.

Simulation

Remarks

 

P-AXIS-00218

Slow velocity for exact detection of reference position

Description

Not only the traverse downwards of cam but also the traverse on cam with homing takes place at the velocity P-AXIS-00218.

Parameter

getriebe[i].vb_reflow

Data type

UNS32

Data range

1 ≤ vb_reflow ≤ P-AXIS-00219

Axis types

T, R, S

Dimension

T: µm/s

R,S: 0.001°/s

Default value

16666

drive types.

Simulation, Conventional, Terminal, Lightbus, Profidrive

Remarks

 

P-AXIS-00219

Fast velocity for detection of reference cam

Description

At start of homing, if the axis is not on the cam, then travel on the cam takes place at the velocity defined in P-AXIS-00219.

Parameter

getriebe[i].vb_refmax

Data type

UNS32

Data range

P-AXIS-00218 ≤ vb_refmax ≤ P-AXIS-00212

Axis types

T, R, S

Dimension

T: µm/s

R,S: 0.001°/s

Default value

83333

drive types.

Conventional, Terminal, Lightbus, Profidrive

Remarks

 

P-AXIS-00294

Selection of the homing method 'Evaluation of encoder overflow'

Description

This homing method is selected with the parameter P-AXIS-00294. To use this option, the parameter P-AXIS-00084 must be assigned the value 0.

The number of bits used to detect encoder overflow has to be set in parameter P-AXIS-00355 .

Parameter

kenngr.homing_overflow_evaluation

Data type

BOOLEAN

Data range

0: No evaluation of encoder overflow (default).

1: Evaluation of encoder overflow.

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

Lightbus

Remarks

This homing method only leads to a repeatable homing position of the axis when encoder overflow occurs every time at the same mechanical position of the axis. This is true for example for resolver encoders.

P-AXIS-00299

Homing type

Description

There are two different homing methods:

  1. NC-controlled homing
  2. Drive-controlled homing

With NC-controlled homing, the generation of command values and sequence control (evaluation of reference cams and zero pulses) are handled in the CNC.

With drive-controlled homing, motion generation and the evaluation of cam signals and zero pulses are handled in the drive.

The homing method can be set up for drives types (P-AXIS-00018) for which both homing methods are implemented with this parameter.

Parameter

kenngr.homing.homing_type *

(Note: see *-note below)

Data type

STRING

Data range

CNC_CONTROLLED: CNC-controlled homing is done.

DRIVE_CONROLLED: Drive-controlled homing is done.

TORQ: CNC-controlled homing to a fixed stop is executed, see Homing to fixed stop (as of V3.1.3080.11).

DISABLED: This axis cannot be homed. The CNC generates the error message ID 50685 or ID 60313 if homing is commanded for the axis (e.g. G74). This setting is only intended for axes with an absolute measuring system (see P-AXIS-00014).

IGNORE_ABS_POS: Axes with this setting are ignored during homing, i.e. the axis is not homed even if G74 <axis_name> is programmed. In this case the CNC generates no error message contrary to the setting DISABLED. The mode IGNORE_ABS_POS is only permitted for axis with an absolute position measuring system, meaning the parameter kenngr.abs_pos_gueltig (see P-AXIS-00014) must be set to 1. Otherwise the CNC generates the error warning ID 110584.

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

CNC_CONTROLLED

Drive types

----

Remarks

* alternative: kenngr.homing_type (old syntax)

If the homing command G74 involves multiple axes with different homing type setting e.g. G74 X1 Y1 Z2, the axis with kenngr.homing_type != IGNORE_ABS_POS/ DISABLED will move and try to find the homing switch while there is no movement on the homing suppressed axes. Therefore it must be ensured that no collision can occur.

If a homing type which is not supported by the drive type is set, the error message ID 110384 is output and the value is corrected to the default homing type.

If this entry is not present in the parameter list, the default homing type is used according to the drive type:

 

Drive type

CNC_CONTROLLED

DRIVE_CONTROLLED

 

simulation

X*

 

 

SERCOS

X

X*

 

Terminal

X*

 

 

Lightbus

X*

 

 

RT Ethernet

X*

 

 

PROFIDRIVE

X*

 

 

CANopen

X*

X

 

* Default homing_type

 

 

P-AXIS-00321

Input interface for reference cam signal

Description

In the default setting with CNC-controlled homing, the reference cam signal is read from the HLI [HLI].

For some drive types it is possible to use the drive digital inputs as reference cam input. In this case the appropriate input has to be configured in P-AXIS-00321.

If this parameter is not set, the reference cam signal is read from the PLC interface.

Parameter

antr.reference_cam_signal

Data type

STRING

Data range

Dependent on the drive type the following different names for the digital inputs are possible:

 

Drive type SERCOS:

PLC                  Read reference cam signal from HLI (default)

RT_STATUS_BIT_1 Read reference cam signal from real time status bit 1

RT_STATUS_BIT_2 Read reference cam signal from real time status bit 2

 

Drive type CANopen:

PLC            Read reference cam signal from HLI (default)

STATUS_DIG_INPUTS (*) Reference cam signal from object 0x60FD : Digital inputs

 

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

PLC

drive types.

SERCOS, Lightbus,CANopen

Remarks

Caution: It is only possible to use real-time status bits with NC-controlled homing, see also [CMS-A1].

 

If the drive digital inputs are used, they must also be parameterised using the drive manufacturer’s set-up tool.

The transmission of the digital inputs in the cyclic telegram must also be configured.

(*) For the transmission of the reference cam state, the object 0x60FD: Digital inputs must be configured (see DS402 drive profile). Otherwise, the error message with error code P-ERR-70292 is output.

P-AXIS-00354

Shifting of encoder overflow

Description

When homing with encoder overflow this parameter can shift the reference position. A positive value for P-AXIS-00354 will shift the reference position in the positive movement direction of the axis.

Parameter

antr.encoder_overflow_offset

Data type

SGN32

Data range

application-specific

Axis types

T, R, S

Dimension

T: 0.1 µm

R,S: 0.1 µm

Default value

0

drive types.

SERCOS, Lightbus,CANopen

Remarks

The reference position can only be shifted within one encoder revolution. If larger values for P-AXIS-00354 are defined, the error message P-ERR-70310 is output and P-AXIS-00354 is corrected to 0.

P-AXIS-00355

Number of bits for evaluation of encoder overflow

Description

When homing on encoder overflow, this parameter defines the number of bits of the drive's actual position value that are taken into account to detect encoder overflow.

The actual position value of the drive system is AND-combined with the value (2P-AXIS-00355 -1) and the underflow or overflow of the resulting value is considered as encoder overflow.

Parameter

antr.encoder_bit_range

Data type

UNS08

Data range

1 … 31

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

SERCOS, Lightbus,CANopen

Remarks

 

P-AXIS-00386

Drive supported execution of the CNC based homing (SERCOS)

Description

By default CNC-controlled homing for SERCOS drives is only executed in the controller; the drive-internal positions are not altered.

If the drive supports the SERCOS command S-0-146 (CNC-controlled homing), this parameter can enable the command S-0-146 for CNC-controlled homing. The advantage of this method is that, after homing is finished, the drive-internal positions are also referenced so that drive-internal software limit switches can be used, for example.

The reference position used for homing is P-AXIS-00152. This value is transferred to the drive during homing

Parameter

antr.sercos.drive_supports_cnc_homing

Data type

BOOLEAN

Data range

0/1

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

SERCOS

Remarks

This parameter is currently not supported for spindles.

In addition to command S-0-146 the drive must support the following commands:

  • S-0-171 (Calculate displacement)
  • S-0-172 (Displacement to referenced system)
  • S-0-191 (Cancel reference point procedure)

For further information please refer to the drive manufacturer's documentation..

P-AXIS-00387

Assignment of control and status bits for CNC based homing (SERCOS)

Description

To execute CNC-controlled homing with drive support, two control bits and two status bits are required. The real-time control and status bits can be used in the drive control and status word or alternatively as bits in the signal status and signal control word.

Parameter

antr.sercos.cnc_homing_rt_bit_layout

Data type

UNS16

Data range

1 ≤ cnc_homing_rt_bit_layout ≤ 16

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

drive types.

SERCOS

Remarks

When the status and control bits are transferred in the signal status and control words, they must be configured in the cyclic process data, otherwise the error message P-ERR-70295 is output.

Assign the values of P-AXIS-00387 to the possible bit assignments:

Value

Process data

Bit number

Meaning

Ident

1

Control word

Real-time bit 1 (S-0-301)

Homing enable

S-0-407

 

Real-time bit 2 (S-0-303)

Position command value referenced

S-0-404

Status word

Real-time bit 1 (S-0-305)

Position marker pulse detected

S-0-408

 

Real-time bit 2 (S-0-307)

Actual value referenced

S-0-403

2

Signal control word

Bit 0 (S-0-27[0])

Homing enable

S-0-407

 

Bit 1 (S-0-27[1])

Position command value referenced

S-0-404

Signal status word

Bit 0 (S-0-26[0])

Position marker pulse detected

S-0-408

 

Bit 1 (S-0-26[1])

Actual value referenced

S-0-403

3

Signal control word

Bit 1 (S-0-27[1])

Homing enable

S-0-407

 

Bit 2 (S-0-27[2])

Position command value referenced

S-0-404

Signal status word

Bit 1 (S-0-26[1])

Position marker pulse detected

S-0-408

 

Bit 2 (S-0-26[2])

Actual value referenced

S-0-403

4

Signal control word

Bit 2 (S-0-27[2])

Homing enable

S-0-407

 

Bit 3 (S-0-27[3])

Position command value referenced

S-0-404

Signal status word

Bit 2 (S-0-26[2])

Position marker pulse detected

S-0-408

 

Bit 3 (S-0-26[3])

Actual value referenced

S-0-403

5

Signal control word

Bit 3 (S-0-27[3])

Homing enable

S-0-407

 

Bit 4 (S-0-27[4])

Position command value referenced

S-0-404

Signal status word

Bit 3 (S-0-26[3])

Position marker pulse detected

S-0-408

 

Bit 4 (S-0-26[4])

Actual value referenced

S-0-403

6

Signal control word

Bit 4 (S-0-27[4])

Homing enable

S-0-407

 

Bit 5 (S-0-27[5])

Position command value referenced

S-0-404

Signal status word

Bit 4 (S-0-26[4])

Position marker pulse detected

S-0-408

 

Bit 5 (S-0-26[5])

Actual value referenced

S-0-403

7

Signal control word

Bit 5 (S-0-27[5])

Homing enable

S-0-407

 

Bit 6 (S-0-27[6])

Position command value referenced

S-0-404

Signal status word

Bit 5 (S-0-26[5])

Position marker pulse detected

S-0-408

 

Bit 6 (S-0-26[6])

Actual value referenced

S-0-403

8

Signal control word

Bit 6 (S-0-27[6])

Homing enable

S-0-407

 

Bit 7 (S-0-27[7])

Position command value referenced

S-0-404

Signal status word

Bit 6 (S-0-26[6])

Position marker pulse detected

S-0-408

 

Bit 7 (S-0-26[7])

Actual value referenced

S-0-403

9

Signal control word

Bit 7 (S-0-27[7])

Homing enable

S-0-407

 

Bit 8 (S-0-27[8])

Position command value referenced

S-0-404

Signal status word

Bit 7 (S-0-26[7])

Position marker pulse detected

S-0-408

 

Bit 8 (S-0-26[8])

Actual value referenced

S-0-403

10

Signal control word

Bit 8 (S-0-27[8])

Homing enable

S-0-407

 

Bit 9 (S-0-27[9])

Position command value referenced

S-0-404

Signal status word

Bit 8 (S-0-26[8])

Position marker pulse detected

S-0-408

 

Bit 9 (S-0-26[9])

Actual value referenced

S-0-403

11

Signal control word

Bit 9 (S-0-27[9])

Homing enable

S-0-407

 

Bit 10 (S-0-27[10])

Position command value referenced

S-0-404

Signal status word

Bit 9 (S-0-26[9])

Position marker pulse detected

S-0-408

 

Bit 10 (S-0-26[10])

Actual value referenced

S-0-403

12

Signal control word

Bit 10 (S-0-27[10])

Homing enable

S-0-407

 

Bit 11 (S-0-27[11])

Position command value referenced

S-0-404

Signal status word

Bit 10 (S-0-26[10])

Position marker pulse detected

S-0-408

 

Bit 11 (S-0-26[11])

Actual value referenced

S-0-403

13

Signal control word

Bit 11 (S-0-27[11])

Homing enable

S-0-407

 

Bit 12 (S-0-27[1]2)

Position command value referenced

S-0-404

Signal status word

Bit 11 (S-0-26[11])

Position marker pulse detected

S-0-408

 

Bit 12 (S-0-26[1]2)

Actual value referenced

S-0-403

14

Signal control word

Bit 12 (S-0-27[12])

Homing enable

S-0-407

 

Bit 13 (S-0-27[13])

Position command value referenced

S-0-404

Signal status word

Bit 12 (S-0-26[12])

Position marker pulse detected

S-0-408

 

Bit 13 (S-0-26[13])

Actual value referenced

S-0-403

15

Signal control word

Bit 13 (S-0-27[13])

Homing enable

S-0-407

 

Bit 14 (S-0-27[1]4)

Position command value referenced

S-0-404

Signal status word

Bit 13 (S-0-26[13])

Position marker pulse detected

S-0-408

 

Bit 14 (S-0-26[14])

Actual value referenced

S-0-403

16

Signal control word

Bit 14 (S-0-27[14])

Homing enable

S-0-407

 

Bit 15 (S-0-27[15])

Position command value referenced

S-0-404

Signal status word

Bit 14 (S-0-26[14])

Position marker pulse detected

S-0-408

 

Bit 15 (S-0-26[15])

Actual value referenced

S-0-403

P-AXIS-00388

Encoder, used for CNC controlled homing (SERCOS)

Description

Some drive types support the use of multiple encoders (motor encoder and external encoder). This parameter defines which encoder is used for homing.

Parameter

antr.cnc_homing_encoder

Data type

SGN16

Data range

0: Value is not configured. If P-AXIS-00386 is set to 1, set this parameter to a valid value (0, 1, 2).

1: The encoder used for homing is determined automatically, e.g. for SERCOS drives, by reading drive parameter S-0-147.

2: Motor encoder

3: External encoder

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

Drive types

SERCOS

Remarks

At the moment this parameter is supported only for SERCOS.

If the encoder set in S-0-147 for SERCOS drives fails to match the value set in P-AXIS-00388, the error message ID 70453 is output.

This value is only effective when P-AXIS-00386 has the value 1.

P-AXIS-00412

Maximum distance during homing

Description

This parameter defines a maximum distance for homing for spindles and rotary axes. If the maximum permissible homing distance is exceeded, homing is aborted and error message P-ERR-70394 is output.

It achieves that homing is aborted if, for example, the reference cam is not found due to a wiring error.

This parameter works only for spindles and rotary axes, see P-AXIS-00018. If this parameter is set for linear axes to a value unequal to zero, the error message P-ERR-110545 is output and the parameter is corrected to 0.

A value of 0 disables distance monitoring during homing.

Parameter

kenngr.distc.a_max

Data type

UNS32

Data range

0 ≤ homing_max_movement_dist ≤ MAX(UNS32)

Axis types

R, S

Dimension

 

R,S: 0.0001 °

Default value

0

drive types.

----

Remarks

This parameter has to be set to a value which is at least equal to the modulo range of the axis in order to complete homing successfully.

P-AXIS-00425

Bit number of signal 'Drive is referenced' during reference monitoring

Description

In this parameter enter the number of the bit which is used for transmission of the signal 'Drive is referenced' from the drive to the controller during active reference monitoring.

The least significant bit has bit number 0.

The maximum value depends on the length of the configured telegram element which is used for transmission.

Length of telegram element

Max. bit number

-1

No reference monitoring

2

15

4

31

Entering an invalid bit number in the parameter results in the output of error message ID 110549.

Parameter

antr.reference_check.bit_nr

Data type

SGN16

Data range

0 ≤ bit_nr ≤ Max. bit number

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

-1

Drive types

SERCOS, CANopen

Remarks

This parameter is used for SERCOS and CANopen drives only.

P-AXIS-00426

Element name of signal 'Drive is referenced' during reference monitoring

Description

In this parameter enter the name of the element of the cyclic input process data which is used for transmission of the signal 'Drive is referenced' from the drive.

If the parameter entered in P-AXIS-00426 is not found in the cyclic process data of the drive, an error message ID 70401 is output.

Parameter

antr.reference_check.element_name

Data type

STRING

Data range

<Empty string>: Reference monitoring is disabled

S-0-0135: When the SERCOS state word is used for transmission of the reference signal, the parameter has to be set to 'S-0-0135'…

<Telegram_element_Name>: ...or, alternatively, the name of a telegram element configured in the cyclic process data.

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

*

Drive types

SERCOS, CANopen

Remarks

* Note: The default value of variables is a blank string.

Reference monitoring is activated by assigning a value to this parameter. When reference monitoring is activated, the parameter P-AXIS-00425 must also be assigned a valid value.

This parameter is currently used for SERCOS and CANopen drives only.

It is not possible to change by a list update (ID 110550).

P-AXIS-00494

Delayed activation of zero pulse logic

Description

For CNC-controlled homing (see P-AXIS-00299) the parameter delays the activation of the zero pulse logic after the actuation of the reference switch. This can be useful if the reference cam and the zero pulse are situated closely together and the detection of the zero pulse is therefore not reliably possible. In this case the next or the next but one zero pulse after the reference cam could be detected depending on the actuation speed of the reference cam.

Parameter

kenngr.shift_offset_zero_pulse_activation

Data type

UNS32

Data range

0 ≤ shift_offset_zero_pulse_activation ≤ MAX_UNS32

Axis types

T, R, S

Dimension

T: 0.1 µm

R,S: 0.0001 °

Default value

0

drive types.

Conventional, SERCOS, Terminal, Lightbus, Profidrive, CANopen

Remarks