Errors in the function block
|
No. |
Message text |
Cause |
Remedy |
|---|---|---|---|
|
501 |
INTERNAL ERROR |
Internal exceptional error |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
502 |
INVALID BUFFER_MODE |
BufferMode 0: DIRECT is not permissible for this function block. |
Program the correct mode:
(>>> BufferMode) |
|
503 |
INVALID MXA VERSION |
The software versions of the mxA interface and PLC library are not compatible. |
Install compatible software versions on the robot controller and PLC. |
|
504 |
INVALID OVERRIDE |
Invalid override value in the function block KRC_SetOverride |
Program a valid value (parameter Override):
|
|
505 |
MAX GROUP REF IDX REACHED |
The axis group index specified in the function block KRC_ReadAxisGroup is already assigned. |
Only instance the KRC_ReadAxisGroup function block once in a program. |
|
506 |
INVALID GROUPREFIDX |
The axis group index specified in the function block is invalid. |
Specify a valid index for the axis group (parameter AxisGroupIdx). |
|
507 |
INVALID FB ORDER |
The order in which the function blocks are called is invalid. |
Program the function blocks in the correct order. |
|
508 |
CONNECTION NOT INITIALIZED |
No statements can be transferred, as the mxA interface has not been initialized. |
Initialize the mxA interface. |
|
509 510 |
NO CONNECTION TO KRC TIMEOUT HEARTBEAT FROM KRC |
Connection to robot controller interrupted |
Restore connection, then acknowledge error. |
|
The robot controller is switched off. |
Reboot the robot controller. | ||
|
Submit interpreter deselected or stopped |
Restart submit interpreter. | ||
|
Bus error or I/O configuration faulty |
Check I/O configuration. | ||
|
Connecting cable defective or not connected correctly. |
Exchange connecting cable or connect it correctly. | ||
|
Maximum cycle time of the submit interpreter is too short (only for message no. 510) |
Increase the value for MaxSubmitCycle in the KRC_Diag function block. | ||
|
A function was called by the input ExecuteCmd before the interface was initialized. |
Wait for the output KRC_Initialize.Done before calling a function with ExecuteCmd. To reset the error, set the input ExecuteCmd to the value FALSE. | ||
|
511 |
TIMEOUT CMD INTERFACE BLOCKED |
The ExecuteCmd input was reset before the Busy signal was set. |
Acknowledge the message and in the future do not reset the input ExecuteCmd until the Done, Error or Aborted signal has been set. |
|
512 |
INVALID CHECKSUM KRC -> PLC |
The checksum for data transmission from the robot controller to the PLC is invalid. | |
|
Error on booting:
|
Check configuration in iiQWorks.Sim and CODESYS and configure PROFINET correctly. | ||
|
Error during operation:
|
Contact KUKA Deutschland GmbH. (>>> KUKA Service) | ||
|
513 |
INVALID POSITION INDEX |
An invalid number for the position to be taught has been transferred in the KRC_TouchUP function block. |
Program a valid value (parameter Index):
|
|
514 |
POS_ACT INVALID |
The current position cannot be taught, as the position data are invalid (no BCO). |
Establish BCO with a RESET in the KRC_AutomaticExternal function block. |
|
517 |
INVALID COMMAND SIZE |
Internal exceptional error |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
518 |
KRC STOPMESS ACTIVE |
Group error which prevents motion enable |
Check how the error was triggered and eliminate the error.
|
|
519 |
INVALID ABSOLUTE VELOCITY |
An invalid value has been programmed for the parameter AbsoluteVelocity in a KRC_Move function block. |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
520 |
VELOCITY CONFLICT |
Multiple values have been programmed for the speed in a KRC_Move function block. |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
521 |
INVALID PARAMETER COUNT |
An invalid value has been programmed for the parameter ParameterCount in a KRC_TechFunction function block. |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
522 |
INVALID PARAMETER USAGE |
The parameter ParameterCount has been incorrectly configured in the KRC_TechFunction function block. |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
523 |
INVALID OPERATION MODE |
The robot is in the incorrect operating mode. |
Select Automatic External mode. |
|
524 |
USER_SAF SIGNAL NOT ACTIVE |
The operator safety is violated. |
Close the safeguard and acknowledge the closed state. |
|
525 |
ALARM_STOP SIGNAL NOT ACTIVE |
The safety configuration is incorrect and an EMERGENCY STOP has been triggered. |
Check and modify the safety configuration of the system (robot controller and PLC). |
|
No connection to the EMERGENCY STOP of the system |
Check the EMERGENCY STOP of the system and reestablish the connection. | ||
|
The inputs and outputs of the Automatic External interface are incorrectly configured. |
| ||
|
526 |
APPL_RUN SIGNAL ACTIVE |
RESET cannot be carried out because a robot program is being executed. |
|
|
527 |
TIMEOUT MESSAGE CONFIRM |
The message cannot be acknowledged by the PLC. |
Acknowledge the message on the robot controller. |
|
528 |
TIMEOUT MXA MESSAGE CONFIRM |
An error cannot be acknowledged in the KRC_AutoStart function block. |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
529 |
TIMEOUT SWITCHING DRIVES ON |
Internal exceptional error |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
530 |
TIMEOUT PROGRAM SELECTION |
Internal exceptional error | |
|
531 |
TIMEOUT PROGRAM START |
Internal exceptional error | |
|
532 |
MOVE_ENABLE SIGNAL NOT ACTIVE |
The robot does not have a motion enable |
Issue motion enable with the parameter MOVE_ENABLE. |
|
533 |
INVALID AXIS_VALUES |
Not all axis angles required for execution are defined in the KRC_Forward function block. |
Define the missing axis angles in the KRC_Forward function block. |
|
534 |
INVALID $BASE |
Internal exceptional error |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
535 |
INVALID $TOOL |
Internal exceptional error | |
|
536 |
INVALID SOFTEND |
Error in the function block KRC_Forward: The specified axis angles lie outside the software limit switches. |
Enter axis angles that lie within the software limit switches (parameter Axis_Values). or: Modify the software limit switches. |
|
537 |
ERR MATH TRAFO |
Error in the function block KRC_Forward: The robot cannot reach the specified axis angles. |
Enter axis angles that the robot can reach (parameter Axis_Values). |
|
538 |
INVALID AXIS_VALUES |
Error in the function block KRC_Inverse:
|
|
|
539 |
INVALID $BASE |
Internal exceptional error |
Contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
540 |
INVALID $TOOL |
Internal exceptional error | |
|
541 |
INVALID SOFTEND |
Error in the function block KRC_Inverse: The axis-specific values at the start point of the motion lie outside the software limit switches. |
Enter values that lie within the software limit switches (parameter Start_Axis). Or: Modify the software limit switches. |
|
542 |
ERR MATH TRAFO |
Error in the function block KRC_Inverse: The robot cannot reach the specified axis-specific values at the start point of the motion. |
Enter values that the robot can reach (parameter Start_Axis). |
|
543 |
INVALID EXECUTE |
During a linked motion capable of being approximated, the Execute input was reset before the ComAcpt signal was set by the function block. |
Acknowledge the message and in the future do not reset the input “Execute” until the ComAcpt signal has been set. |
|
544 |
INVALID DEV_VEL_CP |
Initialization of the mxA interface on the robot controller has not yet been completed or has an error. |
Check whether the output Done is active in the KRC_Initialize function block. |
|
547 |
INVALID TURN |
Error in the function block KRC_Inverse: With the specified Turn, the axis-specific values at the specified position are located outside the software limit switches. |
Enter values that lie within the software limit switches (parameter Position). Or: Modify the software limit switches. |
|
548 |
InvJogCmd |
Error in the function block KRC_Jog or KRC_JogAdvanced: Two jog keys have been pressed simultaneously. |
To jog, press only one jog key at a time. |
|
550 |
Internal error: initializing LDD failed. |
Error in the function block KRC_LDDconfig or KRC_LDDstart: Initalization of load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
551 |
Applying manual mass settings for LDD failed. |
Error in the function block KRC_LDDconfig: The manual setting of the mass for load data determination has failed. |
|
|
552 |
Setting start position for LDD failed. |
Error in the function block KRC_LDDconfig: The current axis position is not a valid start position for load data determination. |
Further information on the start position for load data determination can be found in the documentation for iiQKA.LoadDataDetermination. |
|
Error in the function block KRC_LDDstart: The axis position used when calling the function block KRC_LDDconfig is not a valid start position for load data determination. |
Further information on the start position for load data determination can be found in the documentation for iiQKA.LoadDataDetermination. | ||
|
553 |
Setting supplementary load for LDD failed. |
Error in the function block KRC_LDDconfig: The current supplementary load setting is not valid. |
Pass a valid supplementary load configuration and execute the function block again. Further information on the supplementary load configuration can be found in the documentation for iiQKA.LoadDataDetermination. |
|
Error in the function block KRC_LDDstart: The configuration used when calling the function block KRC_LDDconfig is not a valid supplementary load setting. |
Further information on the supplementary load configuration can be found in the documentation for iiQKA.LoadDataDetermination. | ||
|
554 |
Internal error: Setting acceleration scaling factor for LDD failed. |
Error in the function block KRC_LDDconfig or KRC_LDDstart: Setting the acceleration factor for load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
555 |
Internal error: Finalizing configuration of LDD failed. |
Error in the function block KRC_LDDconfig or KRC_LDDstart: Finalizing the configuration for load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
556 |
Invalid supplementary load option selected for LDD (*LoadA3Settings* parameter). |
Error in the function block KRC_LDDconfig: An invalid value has been set for the parameter LoadA3Settings. |
|
|
557 |
Override must be 100 to execute LDD run. |
Error in the function block KRC_LDDstart: Function block has been executed with a program override < 100%. |
|
|
558 |
Internal error: Setting run mode for LDD failed. |
Error in the function block KRC_LDDtestRun or KRC_LDDstart: Setting the internal run mode for load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
559 |
Internal error: Getting number of identification runs of LDD failed. |
Error in the function block KRC_LDDtestRun or KRC_LDDstart: Retrieving the number of identification runs for load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
560 |
Internal error: Getting starting position for next movement during LDD failed. |
Error in the function block KRC_LDDtestRun or KRC_LDDstart: Retrieving the start position for the next movement during load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
561 |
Internal error: Calculation step during LDD failed. |
Error in the function block KRC_LDDtestRun or KRC_LDDstart: A calculation step during load data determination has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
562 |
Internal error: Getting load identified via LDD failed. |
Error in the function block KRC_LDDstart or KRC_LDDwriteLoad: Retrieving the identified load has failed. |
Execute the function block again. If the error persists, contact KUKA Deutschland GmbH. (>>> KUKA Service) |
|
563 |
Override must be smaller than or equal to 10 to execute LDD test run. |
Error in the function block KRC_LDDtestRun: Function block has been executed with a program override ≥ 10%. |
|
|
590 |
InvMoveType |
Error in the function block KRC_Jog or KRC_JogAdvanced: An invalid value has been programmed for the parameter MoveType. |
Program a valid value for the parameter MoveType. (>>> Jogging to an end position) (>>> Jogging to the end position (advanced)) |