Calling a brake test

Description

The function block KRC_BrakeTest calls the program for the brake test. The brake test is started at the position at which the robot is located when the program is called.

Calling a brake test 1:

The brake test must be performed with a program override of 100% (function block KRC_SetOverride).

During the brake test, all brakes are checked to see whether the wear limit has been reached. For this purpose, the robot accelerates to a defined velocity limit. Once the robot has reached the velocity, the brake is applied and the result for this braking operation is displayed.

If the brake test is successful, the robot is located back at the start position at the end of the measurement.

If the brake test fails, i.e. a brake has been identified as being defective, the robot moves directly to a parking position. The coordinates of the parking position must be specified in the function block.

Parking position

The parking position must be selected in a position where no persons are endangered if the robot sags because of the defective brake. The transport position, for example, can be selected as the parking position.

Calling a brake test 2:

Further information about the transport position is contained in the robot operating or assembly instructions.

Calling a brake test 3:

Detailed information about the brake test can be found in the system software documentation.

Calling a brake test 4:

Inputs

Parameter

Type

Description

AxisGroupIdx

INT

Index of axis group

  • 1 … 5

ExecuteCmd

BOOL

Starts/buffers the motion in the case of a rising edge of the signal.

ParkPosition

E6POS

Coordinates of the Cartesian parking position

(>>> E6POS)

The data structure E6POS contains all components of the parking position (= position of the TCP relative to the origin of the selected coordinate system).

ParkVelocity

INT

Speed

  • 0 … 100%

Refers to the maximum value specified in the machine data. The maximum value is dependent on the robot type.

Default: 0% (= speed is not changed)

ParkAcceleration

INT

Acceleration

  • 0 … 100%

Refers to the maximum value specified in the machine data. The maximum value is dependent on the robot type.

Default: 0% (= acceleration is not changed)

ParkCoordinateSystem

COORDSYS

Coordinate system to which the Cartesian coordinates of the parking position refer

(>>> COORDSYS)

BufferMode

INT

Mode in which the statement is executed

  • 1: ABORTING
  • 2: BUFFERED

(>>> BufferMode)

Outputs

Parameter

Type

Description

Busy

BOOL

TRUE = statement is currently being transferred or has already been transferred

Active

BOOL

TRUE = motion is currently being executed

Done

BOOL

TRUE = motion has stopped

Aborted

BOOL

TRUE = statement/motion has been aborted

Result

DINT

Result of the brake test

  • 0: brake test failed (brake identified as defective or no connection to robot controller)
  • 1: brake test successful (no brake defective, but at least one brake has reached the wear limit)
  • 2: brake test successful (no brake defective or reached wear limit)

Error

BOOL

TRUE = error in function block

ErrorID

DINT

Error number

OrderID

DINT

OrderID number