Error messages of the mxA interface in the submit interpreter
No. | Message text | Cause | Remedy |
|---|---|---|---|
401 | INTERNAL ERROR | Internal exception error | Contact service. |
402 | ASSERT FAILED | Internal exception error | |
403 | INVALID COMMAND ID | Internal exception error | |
404 | INVALID COMMAND STATE | Internal exception error | |
405 | OVERFLOW COMMAND QUEUE | Internal exception error | |
406 | INVALID COMMAND QUEUE INDEX | Internal exception error | |
407 | INVALID COMMAND (PRE) QUEUE INDEX | Internal exception error | |
408 | INVALID WRITE_Q_IDX AND WRITE_PRE_Q_IDX | Internal exception error | |
409 | OVERFLOW STATUS RETURN QUEUE (SUBMIT) | There are more than 100 status change feedback messages to be transmitted from the robot controller to the PLC. The data transfer rate is much smaller than the processing speed. | Reduce the number of instructions that are buffered simultaneously. Contact service if this is not possible. |
410 | INVALID FIELDBUS TELEGRAMM LENGTH | Internal exception error | Contact service. |
411 | TIMEOUT ABORT_REQUEST | Internal exception error | |
412 | INVALID CHECKSUM PLC -> KRC | The checksum during data transmission from the PLC to the robot controller is invalid: | |
Error during commissioning:
| Check configuration in WorkVisual and TwinCAT and configure EtherCAT correctly. | ||
Error during operation:
| Contact service. | ||
413 | INVALID MOVE TYPE | Internal exception error | Contact service. |
414 | TIMEOUT HEARTBEAT FROM PLC | Connection to PLC interrupted | Reconnect, then acknowledge error. |
PLC program stopped | Restart PLC program. | ||
Submit Interpeter deselected or stopped | Restart Submit Interpeter. | ||
Connecting line defective or not connected correctly | Replace connecting line or connect correctly. | ||
416 | SYS VAR NOT INITIALIZED | An error occurred while reading a system variable. The specified system variable does not exist or may not be read in the current operating state. Example: $POS_ACT can only be accessed after a BCO run. | |
417 | UNDERFLOW OF NIBBLE | Internal exception error | Contact service. |
418 | OVERFLOW OF NIBBLE | Internal exception error | |
419 | UNDERFLOW OF BYTE | Internal exception error | |
420 | OVERFLOW OF BYTE | Internal exception error | |
421 | UNDERFLOW OF INT16 | Internal exception error | |
422 | OVERFLOW OF INT16 | Internal exception error | |
423 | UNDERFLOW OF INT32 | Internal exception error | |
424 | OVERFLOW OF INT32 | Internal exception error | |
425 | UNDERFLOW OF REAL | Internal exception error | |
426 | OVERFLOW OF REAL | Internal exception error | |
430 | INVALID PTP APO | An invalid contour parameter was transferred for a PTP movement. | Program valid value (parameter Approximate). (>>> APO) |
431 | INVALID CP APO | An invalid contour parameter was transferred for a CP movement (LIN, CIRC). | |
432 | INVALID BASE NUMBER | An invalid number for the BASE coordinate system has been programmed in a KRC_ReadBaseData or KRC_WriteBaseData function block. | Specify the number of the BASE coordinate system currently used in the robot controller (parameter BaseNo).
|
An invalid number for the BASE coordinate system has been programmed in a KRC_Move or KRC_Jog function block. | Specify the number of the BASE coordinate system currently used in the robot controller (parameter CoordinateSystem - COORDSYS.Base). (>>> COORDSYS) | ||
433 | INVALID TOOL NUMBER | An invalid number for the TOOL coordinate system has been programmed in a KRC_ReadToolData or KRC_WriteToolData function block. | Specify the number of the TOOL coordinate system currently used in the robot controller (parameter ToolNo).
|
An invalid number for the TOOL coordinate system has been programmed in a KRC_Move or KRC_Jog function block. | Specify the number of the TOOL coordinate system currently used in the robot controller (parameter CoordinateSystem - COORDSYS.Tool). (>>> COORDSYS) | ||
434 | INVALID VELOCITY | An invalid value for the velocity has been programmed in a function block. | Program valid value (parameter Velocity):
|
435 | INVALID ACCELERATION | An invalid value for the acceleration has been programmed in a function block. | Program valid value (parameter Acceleration):
|
436 | INVALID C_PTP | An invalid approximation distance was transferred for a PTP movement. | Program valid value (parameter Approximate). (>>> APO) |
437 | INVALID C_DIS | An invalid distance parameter was transferred for a contouring motion. | |
438 | INVALID C_VEL | An invalid velocity parameter was transferred for a contouring motion. | |
439 | INVALID C_ORI | An invalid orientation parameter was transferred for a contouring motion. | |
440 | INVALID ORI_TYPE | An invalid value for the orientation control of the TCP has been programmed in a KRC_Move or KRC_Jog function block. | Program valid value (parameter OriType). (>>> OriType) |
441 | POSITION DATA NOT INITIALIZED | No target position was transferred when calling a KRC_Move function block. | Define at least 1 element of the target position (parameter Position). (>>> E6POS) |
442 | AXISPOSITION DATA NOT INITIALIZED | No axis position was transferred when calling a KRC_MoveAxis function block. | Define at least 1 axis position (parameter AxisPosition). (>>> E6AXIS) |
443 | INVALID TRIGGER DISTANCE | An invalid value for the switching point of the trigger has been programmed in the KRC_SetDistanceTrigger function block. | Program valid value (parameter Distance):
|
444 | INVALID TRIGGER IO | An invalid output has been programmed in a KRC_SetDistanceTrigger or KRC_SetPathTrigger function block. | Program valid value (parameter Output):
|
445 | INVALID TRIGGER PULSE | An invalid value for the length of the pulse has been programmed in a KRC_SetDistanceTrigger or KRC_SetPathTrigger function block. | Program valid value (parameter Pulse):
|
446 | INVALID CIRC_HP | No auxiliary position was transferred when calling a KRC_MoveCirc function block. | Define at least 1 element of the auxiliary position (parameter CircHP). (>>> E6AXIS) |
447 | INVALID INTERRUPT IO | The number of the digital input to which an interrupt is declared is invalid (function block KRC_DeclareInterrupt). | Program valid value (parameter Input):
|
448 | INVALID INTERRUPT NUMBER/ PRIORITY | An invalid number was transferred when calling a KRC_...interrupt function block. | Program valid value (parameter Interrupt):
|
449 | INTERRUPT NOT DECLARED | Interrupt was not declared. | Declare interrupt. (>>> Declare interrupt) |
450 | INVALID INTERRUPT ACTION | The reaction to the interrupt, which was programmed when an interrupt was declared, is invalid. | Program valid reaction (parameter Reaction) (>>> Declare interrupt) |
451 | INVALID IO NUMBER | The number of the digital input to which an interrupt is declared is invalid (function block KRC_DeclareInterrupt). | Program valid value (parameter Input):
|
452 | INVALID PULSE DURATION | An invalid value for the length of the pulse has been programmed in the KRC_ WriteDigitalOutput function block. | Program valid value (parameter Pulse):
(>>> Write digital output) |
453 | INVALID BUFFER_MODE | An invalid BufferMode has been programmed in a function block. The DIRECT mode is not available for some function blocks, for example. | Program valid BufferMode. (>>> BufferMode) |
454 | INVALID TOOL NUMBER FOR LOAD_DATA | An invalid number has been programmed in the function block KRC_ReadLoadData or KRC_WriteLoadData for reading or writing the load data or the additional load data. | Program valid value (parameter Tool). (>>> Read load data) (>>> Write load data) |
455 | INVALID ANALOG IO NUMBER | An invalid number has been programmed in a function block for the analog input or output. | Program valid number (parameter Number):
|
456 | INVALID IPO_MODE | An invalid value for the interpolation mode has been programmed in a function block, e.g. in a KRC_Move function block. | Program valid value (parameter CoordinateSystem - COORDSYS.IPO_MODE). (>>> COORDSYS) |
457 | INVALID CIRC_TYPE | In a KRC_MoveCirc function block an invalid value has been programmed for the orientation control during the circular motion. | Program valid value (parameter CircType). (>>> CircType) |
458 | INVALID FRAME DATA | Invalid TOOL or BASE data were programmed in a KRC_WriteToolData or KRC_WriteBaseData function block. | Program valid data (parameter ToolData or BaseData). (>>> Write TOOL data) (>>> Write BASE data) |
459 | INVALID LOAD DATA | Invalid load data were programmed in a KRC_WriteLoadData function block. | Program valid data. (>>> Write load data) |
460 | INVALID SOFT_END (REVERSED) | Error when writing the software limit switches: positive software limit switch < negative software limit switch | Program smaller values for the negative software limit switches than for the positive software limit switches. |
461 | INVALID INTERRUPT STATE | Internal exception error | Contact service. |
462 | INVALID SYS VAR INDEX | In a KRC_ReadSysVar or KRC_WriteSysVar function block an index was transferred for which no system variable is stored. | Program valid value (parameter Index). (>>> Read system variables) (>>> Write system variables) |
463 | INVALID SYS VAR VALUE | An invalid value for the system variable has been programmed in a KRC_WriteSysVar function block. | Program valid value (parameter Value1 ... Value10). (>>> Write system variables) |
464 | SYS VAR NOT WRITEABLE | An error occurred while writing a system variable. The specified system variable does not exist or may not be written to in the current operating state. | |
465 | INVALID REAL VALUE | The programmed real value is invalid. | Program valid value:
|
466 | ERROR SETTING OUTPUT | Error while writing an output. It is possible that the output is already occupied by the system. | Use another digital output (parameter Number):
|
467 | ERROR SETTING SOFTEND | An error occurred while writing a software limit switch. A possible error is, for example, that a rotatory axis is written with a value outside +/-360°. | Program valid values for the software limit switches (see machine data). |
468 | INVALID TECH FUNCTION INDEX | In a KRC_TechFunction function block a TechFunctionID was transferred for which no technology function is stored. | Contact service. |
469 | INVALID TECH FUNCTION PARAMETER | An invalid value has been programmed for a parameter in a KRC_TechFunction function block. | Contact service. |
470 | INVALID PARAMETER VALUE | An invalid value has been programmed for one or more parameters in the called function block. | Program valid values for the parameters. |
471 | PDAT NOT INITIALIZED | No PDAT data was transferred when calling a KRC_ForwardAdvanced or KRC_InverseAdvanced function block. | Define at least 1 element of the PDAT_ACT. |
472 | FDAT NOT INITIALIZED | No FDAT data was transferred when calling a KRC_ForwardAdvanced or KRC_InverseAdvanced function block. | Define at least 1 element of the FDAT_ACT. |
473 | LDAT NOT INITIALIZED | No LDAT data was transferred when calling a KRC_ForwardAdvanced or KRC_InverseAdvanced function block. | Define at least 1 element of the LDAT_ACT. |
474 | INVALID TOOL OR BASE NUMBER | An invalid number for the TOOL coordinate system or for the BASE coordinate system has been programmed in the KRC_ForwardAdvanced or KRC_InverseAdvanced function block. | Specify the number of the TOOL coordinate system currently used in the robot controller (parameter Tool).
Specify the number of the BASE coordinate system currently used in the robot controller (parameter Base).
|