ADS Return Codes

Grouping of error codes: 0x000..., 0x500..., 0x700..., 0x1000...

Global error codes

Hex

Dec

HRESULT

Name

Description

0x0

0

0x9811 0000

ERR_NOERROR

No error.

0x1

1

0x9811 0001

ERR_INTERNAL

Internal error.

0x2

2

0x9811 0002

ERR_NORTIME

No real-time.

0x3

3

0x9811 0003

ERR_ALLOCLOCKEDMEM

Allocation locked – memory error.

0x4

4

0x9811 0004

ERR_INSERTMAILBOX

Mailbox full – the ADS message could not be sent. Reducing the number of ADS messages per cycle will help.

0x5

5

0x9811 0005

ERR_WRONGRECEIVEHMSG

Wrong HMSG.

0x6

6

0x9811 0006

ERR_TARGETPORTNOTFOUND

Target port not found – ADS server is not started or is not reachable.

0x7

7

0x9811 0007

ERR_TARGETMACHINENOTFOUND

Target computer not found – AMS route was not found.

0x8

8

0x9811 0008

ERR_UNKNOWNCMDID

Unknown command ID.

0x9

9

0x9811 0009

ERR_BADTASKID

Invalid task ID.

0xA

10

0x9811 000A

ERR_NOIO

No IO.

0xB

11

0x9811 000B

ERR_UNKNOWNAMSCMD

Unknown AMS command.

0xC

12

0x9811 000C

ERR_WIN32ERROR

Win32 error.

0xD

13

0x9811 000D

ERR_PORTNOTCONNECTED

Port not connected.

0xE

14

0x9811 000E

ERR_INVALIDAMSLENGTH

Invalid AMS length.

0xF

15

0x9811 000F

ERR_INVALIDAMSNETID

Invalid AMS Net ID.

0x10

16

0x9811 0010

ERR_LOWINSTLEVEL

Installation level is too low –TwinCAT 2 license error.

0x11

17

0x9811 0011

ERR_NODEBUGINTAVAILABLE

No debugging available.

0x12

18

0x9811 0012

ERR_PORTDISABLED

Port disabled – TwinCAT system service not started.

0x13

19

0x9811 0013

ERR_PORTALREADYCONNECTED

Port already connected.

0x14

20

0x9811 0014

ERR_AMSSYNC_W32ERROR

AMS Sync Win32 error.

0x15

21

0x9811 0015

ERR_AMSSYNC_TIMEOUT

AMS Sync Timeout.

0x16

22

0x9811 0016

ERR_AMSSYNC_AMSERROR

AMS Sync error.

0x17

23

0x9811 0017

ERR_AMSSYNC_NOINDEXINMAP

No index map for AMS Sync available.

0x18

24

0x9811 0018

ERR_INVALIDAMSPORT

Invalid AMS port.

0x19

25

0x9811 0019

ERR_NOMEMORY

No memory.

0x1A

26

0x9811 001A

ERR_TCPSEND

TCP send error.

0x1B

27

0x9811 001B

ERR_HOSTUNREACHABLE

Host unreachable.

0x1C

28

0x9811 001C

ERR_INVALIDAMSFRAGMENT

Invalid AMS fragment.

0x1D

29

0x9811 001D

ERR_TLSSEND

TLS send error – secure ADS connection failed.

0x1E

30

0x9811 001E

ERR_ACCESSDENIED

Access denied – secure ADS access denied.

Router error codes

Hex

Dec

HRESULT

Name

Description

0x500

1280

0x9811 0500

 

ROUTERERR_NOLOCKEDMEMORY

Locked memory cannot be allocated.

0x501

1281

0x9811 0501

 

ROUTERERR_RESIZEMEMORY

The router memory size could not be changed.

0x502

1282

0x9811 0502

 

ROUTERERR_MAILBOXFULL

The mailbox has reached the maximum number of possible messages.

0x503

1283

0x9811 0503

 

ROUTERERR_DEBUGBOXFULL

The Debug mailbox has reached the maximum number of possible messages.

0x504

1284

0x9811 0504

ROUTERERR_UNKNOWNPORTTYPE

The port type is unknown.

0x505

1285

0x9811 0505

ROUTERERR_NOTINITIALIZED

The router is not initialized.

0x506

1286

0x9811 0506

ROUTERERR_PORTALREADYINUSE

The port number is already assigned.

0x507

1287

0x9811 0507

ROUTERERR_NOTREGISTERED

The port is not registered.

0x508

1288

0x9811 0508

ROUTERERR_NOMOREQUEUES

The maximum number of ports has been reached.

0x509

1289

0x9811 0509

ROUTERERR_INVALIDPORT

The port is invalid.

0x50A

1290

0x9811 050A

ROUTERERR_NOTACTIVATED

The router is not active.

0x50B

1291

0x9811 050B

ROUTERERR_FRAGMENTBOXFULL

The mailbox has reached the maximum number for fragmented messages.

0x50C

1292

0x9811 050C

ROUTERERR_FRAGMENTTIMEOUT

A fragment timeout has occurred.

0x50D

1293

0x9811 050D

ROUTERERR_TOBEREMOVED

The port is removed.

General ADS error codes

Hex

Dec

HRESULT

Name

Description

0x700

1792

0x9811 0700

ADSERR_DEVICE_ERROR

General device error.

0x701

1793

0x9811 0701

ADSERR_DEVICE_SRVNOTSUPP

Service is not supported by the server.

0x702

1794

0x9811 0702

ADSERR_DEVICE_INVALIDGRP

Invalid index group.

0x703

1795

0x9811 0703

ADSERR_DEVICE_INVALIDOFFSET

Invalid index offset.

0x704

1796

0x9811 0704

ADSERR_DEVICE_INVALIDACCESS

Reading or writing not permitted.

0x705

1797

0x9811 0705

ADSERR_DEVICE_INVALIDSIZE

Parameter size not correct.

0x706

1798

0x9811 0706

ADSERR_DEVICE_INVALIDDATA

Invalid data values.

0x707

1799

0x9811 0707

ADSERR_DEVICE_NOTREADY

Device is not ready to operate.

0x708

1800

0x9811 0708

ADSERR_DEVICE_BUSY

Device is busy.

0x709

1801

0x9811 0709

ADSERR_DEVICE_INVALIDCONTEXT

Invalid operating system context. This can result from use of ADS function blocks in different tasks. It may be possible to resolve this through Multi-task data access synchronization in the PLC.

0x70A

1802

0x9811 070A

ADSERR_DEVICE_NOMEMORY

Insufficient memory.

0x70B

1803

0x9811 070B

ADSERR_DEVICE_INVALIDPARM

Invalid parameter values.

0x70C

1804

0x9811 070C

ADSERR_DEVICE_NOTFOUND

Not found (files, ...).

0x70D

1805

0x9811 070D

ADSERR_DEVICE_SYNTAX

Syntax error in file or command.

0x70E

1806

0x9811 070E

ADSERR_DEVICE_INCOMPATIBLE

Objects do not match.

0x70F

1807

0x9811 070F

ADSERR_DEVICE_EXISTS

Object already exists.

0x710

1808

0x9811 0710

ADSERR_DEVICE_SYMBOLNOTFOUND

Symbol not found.

0x711

1809

0x9811 0711

ADSERR_DEVICE_SYMBOLVERSIONINVALID

Invalid symbol version. This can occur due to an online change. Create a new handle.

0x712

1810

0x9811 0712

ADSERR_DEVICE_INVALIDSTATE

Device (server) is in invalid state.

0x713

1811

0x9811 0713

ADSERR_DEVICE_TRANSMODENOTSUPP

AdsTransMode not supported.

0x714

1812

0x9811 0714

ADSERR_DEVICE_NOTIFYHNDINVALID

Notification handle is invalid.

0x715

1813

0x9811 0715

ADSERR_DEVICE_CLIENTUNKNOWN

Notification client not registered.

0x716

1814

0x9811 0716

ADSERR_DEVICE_NOMOREHDLS

No further handle available.

0x717

1815

0x9811 0717

ADSERR_DEVICE_INVALIDWATCHSIZE

Notification size too large.

0x718

1816

0x9811 0718

ADSERR_DEVICE_NOTINIT

Device not initialized.

0x719

1817

0x9811 0719

ADSERR_DEVICE_TIMEOUT

Device has a timeout.

0x71A

1818

0x9811 071A

ADSERR_DEVICE_NOINTERFACE

Interface query failed.

0x71B

1819

0x9811 071B

ADSERR_DEVICE_INVALIDINTERFACE

Wrong interface requested.

0x71C

1820

0x9811 071C

ADSERR_DEVICE_INVALIDCLSID

Class ID is invalid.

0x71D

1821

0x9811 071D

ADSERR_DEVICE_INVALIDOBJID

Object ID is invalid.

0x71E

1822

0x9811 071E

ADSERR_DEVICE_PENDING

Request pending.

0x71F

1823

0x9811 071F

ADSERR_DEVICE_ABORTED

Request is aborted.

0x720

1824

0x9811 0720

ADSERR_DEVICE_WARNING

Signal warning.

0x721

1825

0x9811 0721

ADSERR_DEVICE_INVALIDARRAYIDX

Invalid array index.

0x722

1826

0x9811 0722

ADSERR_DEVICE_SYMBOLNOTACTIVE

Symbol not active.

0x723

1827

0x9811 0723

ADSERR_DEVICE_ACCESSDENIED

Access denied.

0x724

1828

0x9811 0724

ADSERR_DEVICE_LICENSENOTFOUND

Missing license.

0x725

1829

0x9811 0725

ADSERR_DEVICE_LICENSEEXPIRED

License expired.

0x726

1830

0x9811 0726

ADSERR_DEVICE_LICENSEEXCEEDED

License exceeded.

0x727

1831

0x9811 0727

ADSERR_DEVICE_LICENSEINVALID

Invalid license.

0x728

1832

0x9811 0728

ADSERR_DEVICE_LICENSESYSTEMID

License problem: System ID is invalid.

0x729

1833

0x9811 0729

ADSERR_DEVICE_LICENSENOTIMELIMIT

License not limited in time.

0x72A

1834

0x9811 072A

ADSERR_DEVICE_LICENSEFUTUREISSUE

License problem: Time in the future.

0x72B

1835

0x9811 072B

ADSERR_DEVICE_LICENSETIMETOLONG

License period too long.

0x72C

1836

0x9811 072C

ADSERR_DEVICE_EXCEPTION

Exception at system startup.

0x72D

1837

0x9811 072D

ADSERR_DEVICE_LICENSEDUPLICATED

License file read twice.

0x72E

1838

0x9811 072E

ADSERR_DEVICE_SIGNATUREINVALID

Invalid signature.

0x72F

1839

0x9811 072F

ADSERR_DEVICE_CERTIFICATEINVALID

Invalid certificate.

0x730

1840

0x9811 0730

ADSERR_DEVICE_LICENSEOEMNOTFOUND

Public key not known from OEM.

0x731

1841

0x9811 0731

ADSERR_DEVICE_LICENSERESTRICTED

License not valid for this system ID.

0x732

1842

0x9811 0732

ADSERR_DEVICE_LICENSEDEMODENIED

Demo license prohibited.

0x733

1843

0x9811 0733

ADSERR_DEVICE_INVALIDFNCID

Invalid function ID.

0x734

1844

0x9811 0734

ADSERR_DEVICE_OUTOFRANGE

Outside the valid range.

0x735

1845

0x9811 0735

ADSERR_DEVICE_INVALIDALIGNMENT

Invalid alignment.

0x736

1846

0x9811 0736

ADSERR_DEVICE_LICENSEPLATFORM

Invalid platform level.

0x737

1847

0x9811 0737

ADSERR_DEVICE_FORWARD_PL

Context – forward to passive level.

0x738

1848

0x9811 0738

ADSERR_DEVICE_FORWARD_DL

Context – forward to dispatch level.

0x739

1849

0x9811 0739

ADSERR_DEVICE_FORWARD_RT

Context – forward to real-time.

0x740

1856

0x9811 0740

ADSERR_CLIENT_ERROR

Client error.

0x741

1857

0x9811 0741

ADSERR_CLIENT_INVALIDPARM

Service contains an invalid parameter.

0x742

1858

0x9811 0742

ADSERR_CLIENT_LISTEMPTY

Polling list is empty.

0x743

1859

0x9811 0743

ADSERR_CLIENT_VARUSED

Var connection already in use.

0x744

1860

0x9811 0744

ADSERR_CLIENT_DUPLINVOKEID

The called ID is already in use.

0x745

1861

0x9811 0745

ADSERR_CLIENT_SYNCTIMEOUT

Timeout has occurred – the remote terminal is not responding in the specified ADS timeout. The route setting of the remote terminal may be configured incorrectly.

0x746

1862

0x9811 0746

ADSERR_CLIENT_W32ERROR

Error in Win32 subsystem.

0x747

1863

0x9811 0747

ADSERR_CLIENT_TIMEOUTINVALID

Invalid client timeout value.

0x748

1864

0x9811 0748

ADSERR_CLIENT_PORTNOTOPEN

Port not open.

0x749

1865

0x9811 0749

ADSERR_CLIENT_NOAMSADDR

No AMS address.

0x750

1872

0x9811 0750

ADSERR_CLIENT_SYNCINTERNAL

Internal error in Ads sync.

0x751

1873

0x9811 0751

ADSERR_CLIENT_ADDHASH

Hash table overflow.

0x752

1874

0x9811 0752

ADSERR_CLIENT_REMOVEHASH

Key not found in the table.

0x753

1875

0x9811 0753

ADSERR_CLIENT_NOMORESYM

No symbols in the cache.

0x754

1876

0x9811 0754

ADSERR_CLIENT_SYNCRESINVALID

Invalid response received.

0x755

1877

0x9811 0755

ADSERR_CLIENT_SYNCPORTLOCKED

Sync Port is locked.

RTime error codes

Hex

Dec

HRESULT

Name

Description

0x1000

4096

0x9811 1000

RTERR_INTERNAL

Internal error in the real-time system.

0x1001

4097

0x9811 1001

RTERR_BADTIMERPERIODS

Timer value is not valid.

0x1002

4098

0x9811 1002

RTERR_INVALIDTASKPTR

Task pointer has the invalid value 0 (zero).

0x1003

4099

0x9811 1003

RTERR_INVALIDSTACKPTR

Stack pointer has the invalid value 0 (zero).

0x1004

4100

0x9811 1004

RTERR_PRIOEXISTS

The request task priority is already assigned.

0x1005

4101

0x9811 1005

RTERR_NOMORETCB

No free TCB (Task Control Block) available. The maximum number of TCBs is 64.

0x1006

4102

0x9811 1006

RTERR_NOMORESEMAS

No free semaphores available. The maximum number of semaphores is 64.

0x1007

 

4103

 

0x9811 1007

 

RTERR_NOMOREQUEUES

 

No free space available in the queue. The maximum number of positions in the queue is 64.

0x100D

4109

0x9811 100D

RTERR_EXTIRQALREADYDEF

An external synchronization interrupt is already applied.

0x100E

4110

0x9811 100E

RTERR_EXTIRQNOTDEF

No external sync interrupt applied.

0x100F

4111

0x9811 100F

RTERR_EXTIRQINSTALLFAILED

Application of the external synchronization interrupt has failed.

0x1010

4112

0x9811 1010

RTERR_IRQLNOTLESSOREQUAL

Call of a service function in the wrong context

0x1017

4119

0x9811 1017

RTERR_VMXNOTSUPPORTED

Intel VT-x extension is not supported.

0x1018

4120

0x9811 1018

RTERR_VMXDISABLED

Intel VT-x extension is not enabled in the BIOS.

0x1019

4121

0x9811 1019

RTERR_VMXCONTROLSMISSING

Missing function in Intel VT-x extension.

0x101A

4122

0x9811 101A

RTERR_VMXENABLEFAILS

Activation of Intel VT-x fails.

TCP Winsock error codes

 

Hex

Dec

Name

Description

0x274C

10060

WSAETIMEDOUT

A connection timeout has occurred - error while establishing the connection, because the remote terminal did not respond properly after a certain period of time, or the established connection could not be maintained because the connected host did not respond.

0x274D

10061

WSAECONNREFUSED

Connection refused - no connection could be established because the target computer has explicitly rejected it. This error usually results from an attempt to connect to a service that is inactive on the external host, that is, a service for which no server application is running.

0x2751

10065

WSAEHOSTUNREACH

No route to host - a socket operation referred to an unavailable host.

More Winsock error codes: Win32 error codes