Process Data

If the scanner is not yet in its RUN state when process data is accessed (CCO Directory, offset 0x14), error code 0x0708 (Device not ready) is returned.

I/O Connection

An I/O connection is established to ControlNet adapters (e.g. BK7000, AB-Flex-I/O).

Receive Data (ADS Read Response)

Offset 

Attributes

0x00

General status (0: ok, 1: error (Status of the connection)

0x01

reserved

0x02

Extended Status (0: ok, > 0: error (Status of the connection)

0x04

Update counter (is incremented by the sender whenever new data is transmitted)

0x06

Adapter status (is transmitted)

0x0A

Input data (see device description)

Send Data (ADS Write Request)

Offset 

Attributes

0x00

Scanner status (is transmitted)

0x04

Output data (see device description)

Receive Connection

A receive connection is established to other ControlNet scanners (e.g. ControlLogix, PLC5).

Receive Data (ADS Read Response)

Offset 

Attributes

0x00

General status (0: ok, 1: error (Status of the connection)

0x01

reserved

0x02

Extended Status (0: ok, > 0: error (Status of the connection)

0x04

Update counter (is incremented by the sender whenever new data is transmitted)

0x06

Input data (see device description)

Send Connection

A send connection is established to other ControlNet scanners (e.g. ControlLogix, PLC5).

Send Data (ADS Write Request)

Offset 

Attributes

0x00

Output data

Receive Data (ADS Read Response)

Offset 

Attributes

0x00

General status (0: ok, 1: error (Status of the connection)

0x01

reserved

0x02

Extended Status (0: ok, > 0: error (Status of the connection)