Configuration with KS2000

Commissioning procedure

  1. Install the configuration software KS2000, version 4.3.0.39 or higher.
  2. Plug the KL6401 into your bus coupler, and terminate the K-bus with a KL9010.
  3. Log on. Should the dialog box "Create new XML Device Files" be open, cancel at this point.

Configuration with KS2000 1:

The terminal can now be configured under "Settings" Configuration with KS2000 2:.

Configuration with KS2000 3:

Enter the SNVTs in the table Configuration with KS2000 4:. Use  Configuration with KS2000 5:  to add a variable and Configuration with KS2000 6: to remove a selected variable.

The column "Id" cannot be edited. It contains the NV index. This index is also required as input variable "wNVIndex" for the PLC function blocks.

In column "Nv Name" any text can be entered. These descriptions are required in the LON configuration tool (not provided by Beckhoff) for identifying the respective variables.

Select the required SNVT in column "SNVT Type".

Column "Dir" (Direction) indicates whether the variable is sent (out) or received (in).

Configuration with KS2000 7:Set any project name (click on "PROJECTNAME").

Then edit the program ID (Prog ID)Configuration with KS2000 8: . Do this by clicking Program ID, and selecting a Program ID. This program ID may only be issued once in your LON project. A maximum of 256 (0-255) program IDs can be used. This means that you can use 256 different configurations in one project.

Configuration with KS2000 9:

LON terminals with the same configuration also have the same program ID.

Use the button Configuration with KS2000 10: to create the Xif file. This file is required in the LON configuration tool (not provided by Beckhoff).

Use the button Configuration with KS2000 11: to save the configuration in a BLC file. This file can be used to load the configuration if a terminal is replaced or to use the same configuration in another terminal.

The data can now be written to the terminal. Use the buttons [>>>] or [<<<] to select the required slot and then the button "WRITE" to write the data to the terminal. The slot may not be activated (green) during this process.

Configuration with KS2000 12:

The terminal is supplied with slot 0 active (factory setting). This slot contains a fixed configuration and cannot be modified. To transfer other values a different slot has to be configured and activated. Only one slot at a time is active.

The project must be activated after the download has successfully been completed. Use the button "SET ACTIVE PROJECT". The KL6401 must now be disconnected from the power supply. After switching on the KL6401 (switching the power supply on again) the desired configuration is active.

Description of the editing functions

Configuration with KS2000 13:

Configuration with KS2000 14: Deletes the table

Configuration with KS2000 15: Opens an existing SNVT configuration file (*.BLC) for the KL6401

Configuration with KS2000 16: Saves the current configuration as a BLC file

Configuration with KS2000 17: Edits an SNVT variable

Configuration with KS2000 18: Inserts an SNVT variable

Configuration with KS2000 19: Deletes an SNVT variable

Configuration with KS2000 20: Creates an XIF file for a LON configuration tool (not provided by Beckhoff)

Configuration with KS2000 21: Opens the Help

Configuration with KS2000 22: Information