ST_TcMcAutoIdent (from V3.0.4)
In this structure the parameters for an MC_AxUtiAutoIdent_BkPlcMc function block are stored. It contains further information about the purpose of the individual elements.
Syntax
TYPE ST_TcMcAutoIdent :
(* last modification: 08.11.2019 *)
STRUCT
EndOfTravel_Negativ: LREAL:=0.0;
EndOfTravel_Positiv: LREAL:=0.0;
EndOfTravel_NegativLimit: LREAL:=0.0;
EndOfTravel_PositivLimit: LREAL:=0.0;
DecelerationFactor: LREAL:=1.0;
EndOfVelocity_NegativLimit: LREAL:=0.0;
EndOfVelocity_PositivLimit: LREAL:=0.0;
EndOfTravel_LastIdent_P: LREAL:=0.0;
EndOfTravel_LastIdent_M: LREAL:=0.0;
ValveCharacteristicLowEnd: LREAL:=0.0;
ValveCharacteristicHighEnd: LREAL:=0.0;
ValveCharacteristicRamp: LREAL:=0.0;
ValveCharacteristicSettling:LREAL:=0.0; (* starting with V3.0.32 *)
ValveCharacteristicRecovery:LREAL:=0.0;
ValveCharacteristicMinCycle:LREAL:=0.0;
Valve_LinLimitP: LREAL:=0.0; (* starting with V3.0.46 *)
Valve_LinLimitM: LREAL:=0.0;
ValveCharacteristicTable: ARRAY[1..100,1..2] OF LREAL;
EndOfIncrements_Negativ: DINT:=0;
EndOfIncrements_Positiv: DINT:=0;
ValveCharacteristicType: INT:=0; (* starting with V3.0.33 *)
ValveCharacteristicTblCount:INT:=0;
EnableEndOfTravel: BOOL:=FALSE;
EnableOverlap: BOOL:=FALSE;
EnableZeroAdjust: BOOL:=FALSE;
EnableArreaRatio: BOOL:=FALSE;
EndOfTravel_PositivDone: BOOL:=FALSE;
EndOfTravel_NegativDone: BOOL:=FALSE;
EnableValveCharacteristic: BOOL:=FALSE;
EnableNoUturn: BOOL:=FALSE;
END_STRUCT
END_TYPE
Parameter
Name | Type | Description |
|---|---|---|
EndOfTravel_Negativ | LREAL |
|
EndOfTravel_Positiv | LREAL |
|
EndOfTravel_NegativLimit | LREAL |
|
EndOfTravel_PositivLimit | LREAL |
|
DecelerationFactor | LREAL |
|
EndOfVelocity_NegativLimit | LREAL |
|
EndOfVelocity_PositivLimit | LREAL |
|
EndOfTravel_LastIdent_P | LREAL |
|
EndOfTravel_LastIdent_M | LREAL |
|
ValveCharacteristicLowEnd | LREAL |
|
ValveCharacteristicHighEnd | LREAL |
|
ValveCharacteristicRamp | LREAL |
|
ValveCharacteristicSettling | LREAL |
|
ValveCharacteristicRecovery | LREAL |
|
ValveCharacteristicMinCycle | LREAL |
|
Valve_LinLimitP | LREAL |
|
Valve_LinLimitM | LREAL |
|
ValveCharacteristicTable | ARRAY |
|
EndOfIncrements_Negativ | DINT |
|
EndOfIncrements_Positiv | DINT |
|
ValveCharacteristicType | INT |
|
ValveCharacteristicTblCount | INT |
|
EnableEndOfTravel | BOOL |
|
EnableOverlap | BOOL |
|
EnableZeroAdjust | BOOL |
|
EnableArreaRatio | BOOL |
|
EndOfTravel_PositivDone | BOOL |
|
EndOfTravel_NegativDone | BOOL |
|
EnableValveCharacteristic | BOOL |
|
EnableNoUturn | BOOL |
|