EIB_READ_SEND
Application
This function block sends a Read_Group_Req to the set group address. For receiving a Read_Group_Res the group address filter of the KL6301 must be parameterized accordingly.
VAR_INPUT
Group_Address : EIB_GROUP_ADDR;
bRead : BOOL;
str_Rec : EIB_REC;Group_Address: Group address to which the data are sent (see EIB_GROUP_ADDR).
bRead: Rising edge starts the block and sends a Read_Group_Req to the EIB device.
For receiving a response the group address must be entered in the filter!
str_Rec: The data structure with which the KL6301() function block must be linked (see EIB_REC).
VAR_OUTPUT
bError : BOOL;
iErrorID : EIB_ERROR_CODE;
bBusy : BOOL;bError: The bError output becomes TRUE as soon as an error occurs. The error is described via the variable iErrorID.
iErrorID: The output issues an error code when an error occurs (see EIB_ERROR_CODE). Simultaneously bError is TRUE.
bBusy: The block is active. For new functions wait until bBusy is set back to FALSE.