TP

Pulse generator. This function block can be used to generate pulses with a defined pulse duration.
VAR_INPUT
VAR_INPUT
IN : BOOL; (* Trigger for Start of the Signal *)
PT : TIME; (* The length of the High-Signal in ms *)
END_VAR
VAR_OUTPUT
VAR_OUTPUT
Q : BOOL; (* The pulse *)
ET : TIME; (* The current phase of the High-Signal *)
END_VAR
If IN is FALSE, the outputs are FALSE or 0. As soon as IN becomes TRUE, Q also becomes TRUE and remains TRUE for the pulse duration PT. As long as Q is TRUE, the time is incremented in milliseconds in ET, until the value reaches PT. The value then remains constant. The output Q remains TRUE until the pulse duration has elapsed, irrespective of the state of the input IN. Q therefore supplies a signal over the interval specified in PT.
Graphic display of TP behavior over time:
The TP function requires 14 bytes of data.
Requirements
Development environment |
Target system type |
PLC libraries to be linked |
---|---|---|
TwinCAT v3.0.0 |
PC or CX (x86) |
Tc2_Standard |