Error codes
| Value (hex) | Value (dec) | Value (enum) | Description | 
|---|---|---|---|
| 0x0000 | 0 | NO_MP_ERROR | No error. | 
| 0x0001 | 1 | WRONG_TERMINAL | Incorrect terminal connected. | 
| 0x0002 | 2 | NO_ANSWER_FROM_KL6771 | No answer from the KL6771 MP-Bus master terminal. This message usually means that there is no connection to the terminal. Terminal linked to the variables in the System Manager? Terminal plugged in incorrectly? Clean all, rebuild all and read again in the System Manager? | 
| 0x0003 | 3 | NO_LINK_TO_STRUCTURE_strDataKL6771 | Check the link to the structure DataKL6771. | 
| 0x000A | 10 | WRONG_MP_ADDRESS_IS_0 | MP-Bus address is 0. Only addresses between 1 and 8 are allowed. | 
| 0x000B | 11 | WRONG_MP_ADDRESS | MP-Bus address is >8. Only addresses between 1 and 8 are allowed. | 
| 0x0015 | 21 | WRONG_SET_POINT | Incorrect set point. | 
| 0x0019 | 25 | MP_BUS_TIMEOUT_NO_ANSWER_FROM_SLAVE | MP-Bus timeout, no answer from slave. | 
| 0x0020 | 26 | MP_BUS_SETPOINT_DIFF_TOO_HIGH | Difference from setpoint too high. | 
| 0x001F | 31 | KL6771_TIME_OUT | KL6771 timeout. | 
| 0x0020 | 32 | MP_ADDRESS_IS_IN_USE | MP-Bus address is in use. | 
| 0x0021 | 33 | MP_DISABLED | MP-Bus disabled. | 
| 0x0057 | 87 | MP_BUS_ERROR | MP-Bus error. | 
| 0x0058 | 88 | MP_NO_ANSWER_ON_EVENT | MP-Bus no answer to an event. | 
| 0x0059 | 89 | MP_NO_ANSWER | MP-Bus no answer. | 
| 0x005A | 90 | MP_COM_BREAK | MP-Bus abort communication. | 
| 0x0062 | 98 | MP_LENGTH_PARITY_ERROR | MP-Bus length parity error. | 
| 0x0063 | 99 | MP_CROSS_PARITY_ERROR | MP-Bus cross parity error. | 
| 0x0065 | 101 | MP_MASTER_CONFLICT_ERROR | MP-Bus MASTER_CONFLICT_ERROR. | 
| 0x0066 | 102 | MP_GAP_TIMEOUT_ERROR | MP-Bus GAP Timeout. | 
| 0x0067 | 103 | MP_NO_ANSWER_SLAVE | MP-Bus no answer from slave. | 
| 0x006E | 110 | MP_ANSWER_ERROR_FLAG | MP-Bus error bit in answer telegram is set. | 
| 0x006F | 111 | MP_ANSWER_WRONG_LEN | MP-Bus wrong telegram length. | 
| 0x0070 | 112 | MP_ANSWER_WRONG_TELEG | MP-Bus wrong telegram received. | 
| 0x0073 | 115 | MP_ANSWER_WITH_ERROR | Answer contains an error. | 
| 0x00C8 | 200 | MP_ERROR_WrongDeviceFamily | Wrong device family. | 
| 0x012C | 300 | MP_CONF_ERROR_CO2LimitGood | Configuration error for CO2 limitation "Good". | 
| 0x012D | 301 | MP_CONF_ERROR_CO2LimitModerate | Configuration error for CO2 limitation "Moderate". | 
| 0x012E | 302 | MP_CONF_ERROR_CO2Limit | Configuration error for CO2 limitation. | 
| 0x012F | 303 | MP_CONF_ERROR_WRONG_TEMP_OFFSET | Configuration error for temperature offset. | 
| 0x0130 | 304 | MP_CONF_ERROR_WRONG_HUMIDITY_OFFSET | Configuration error for humidity offset. | 
| 0x0131 | 305 | MP_CONF_ERROR_WRONG_CO2_OFFSET | Configuration error for CO2 offset. | 
| 0x0132 | 306 | MP_CONF_ERROR_WRONG_TempSetpoint | Configuration error for temperature setpoint. | 
| 0x0133 | 307 | MP_CONF_ERROR_WRONG_RelativeTempSetpoint | Configuration error for relative temperature setpoint. | 
| 0x0134 | 308 | MP_CONF_ERROR_WRONG_DefaultTempSetpoint | Configuration error for preset temperature setpoint. | 
| 0x0135 | 309 | MP_CONF_ERROR_WRONG_TempSetpointRange | Configuration error for temperature setpoint range. | 
| 0x800A | 32778 | MP_ANSWER_Reserve | Reserve. | 
| 0x800B | 32779 | MP_ANSWER_UnknowCommand | Unknown command. | 
| 0x800C | 32780 | MP_ANSWER_WrongOrNoPassword | Wrong or no password. | 
| 0x800D | 32781 | MP_ANSWER_CommandExecution | Command execution. | 
| 0x800E | 32782 | MP_ANSWER_ParameterError | Parameter error. | 
| 0x800F | 32783 | MP_ANSWER_UnknowId | Unknown ID. | 
| 0x8010 | 32784 | MP_ANSWER_SizeMismatch | Wrong size. | 
| 0x8011 | 32785 | MP_ANSWER_IllegalBlockNr | Invalid block number. | 
| 0x8012 | 32786 | MP_ANSWER_InternalBusBusy | Internal bus is busy. | 
| 0x80FF | 33023 | MP_ANSWER_ReservedForFuture | Reserve. |