FB_SoEAX5000FirmwareUpdate_ByDriveRef

FB_SoEAX5000FirmwareUpdate_ByDriveRef 1:

With the FB_SoEAX5000FirmwareUpdate_ByDriveRef function block the Firmware of the AX5000 can be checked and automatically changed to a given version (Revision and Build) or to the current Build of the configured revision.

For the update:

A successful update ends with eFwUpdateState = eFwU_FwUpdateDone.

If the update is not required, this is signaled via eFwUpdateState = eFwU_NoFwUpdateRequired.

The firmware is updated via the specified channel (A = 0 or B = 1) from stDriveRef. In the case of two-channel devices only one of the two channels can be used. The other channel signals eFwUpdateState = eFwU_UpdateViaOtherChannelActive or eFwUpdateState = eFwU_UpdateViaOtherChannel.

During the firmware update (eFwUpdateState = eFwU_FwUpdateInProgress), iLoadProgress signals the progress in percent.

Notice

Faulty update due to interruptions

Interruptions during the update may result in it not being executed or executed incorrectly. Afterwards, the drive amplifier may no longer be usable without the appropriate firmware.

The rules during the update are:

  • The PLC and TwinCAT must not be stopped.
  • The EtherCAT connection must not be interrupted.
  • The AX5000 must not be switched off.

FB_SoEAX5000FirmwareUpdate_ByDriveRef 2: Inputs

VAR_INPUT
   stDriveRef       : ST_DriveRef; 
   bExecute         : BOOL;    
   tTimeout         : TIME := DEFAULT_ADS_TIMEOUT;
   sFirmwareVersion : STRING(20);  (* version string vx_yy_bnnnn, e.g. "v1.05_b0009" for v1.05 Build 0009*)
   sFirmwarePath    : T_MaxString; (* drive:\path, e.g. "C:\TwinCAT\Io\TcDriveManager\FirmwarePool" *)
   sNetIdIPC        : T_AmsNetId;
   iReqEcState      : UINT := EC_DEVICE_STATE_OP;
END_VAR

Name

Type

Description

stDriveRef

ST_DriveRef

Reference to the drive. The reference to the drive can be linked directly to the PLC in the System Manager. To do this, an instance of the structure ST_PlcDriveRef must be allocated and the NetID must be converted from the byte array into a string (Type: ST_DriveRef).

bExecute

BOOL

The function block is activated by a positive edge at this input.

tTimeout

TIME

Maximum time allowed for the execution of the function block.

sFirmwareVersion

STRING(20)

Specifies the desired firmware version in the form of vx.yy_bnnnn, e.g. "v1.05_b0009" for Version v1.05 Build 0009.

Release-Builds:

  • "v1.05_b0009" for a specific build, e.g. v1.05 Build 0009
  • "v1.05_b00??" latest build of a specified version, e.g. v1.05
  • "v1.??_b00??" latest build of a specified main version, e.g. v1
  • " " latest build of the latest version

Customer-specific Firmware-Builds:

  • "v1.05_b1009" for a specific build, e.g. v1.05 Build 0009
  • "v1.05_b10??" latest build of a specified version, e.g. v1.05
  • "v1.??_b10??" latest build of a specified main version, e.g. v1
  • "v?.??_b10??" latest build of the latest version
  • "v1.05_b8909" for a specific build, e.g. v1.05 Build 8909
  • "v1.05_b89??" latest build of a specified version, e.g. v1.05
  • "v1.??_b89??" latest build of a specified main version, e.g. v1
  • "v?.??_b89??" latest build of the latest version

Debug-Builds:

  • "v1.05_b9009" for a specific build, e.g. v1.05 Build 9009
  • "v1.05_b90??" latest build of a specified version, e.g. v1.05
  • "v1.??_b90??" latest build of a specified main version, e.g. v1
  • "v?.??_b90??" latest build of the latest version

sFirmwarePath

T_MaxString

Specifies the path for the firmware pool in which the firmware files are located, e.g. C:\TwinCAT\Io\TcDriveManager\FirmwarePool.

sNetIdIPC

T_AmsNetId

AMS-NetID of the controller (IPC)

iReqEcState

UINT

Desired EtherCAT state after the update, only if an update is actually being executed. The states are defined in PLC Lib Tc2_EtherCAT as global constants.

FB_SoEAX5000FirmwareUpdate_ByDriveRef 3: Outputs

VAR_OUTPUT
   bBusy                 : BOOL;
   bError                : BOOL;
   iAdsErrId             : UINT;
   iSercosErrId          : UINT;
   iDiagNumber           : UDINT;
   eFwUpdateState        : E_FwUpdateState;
   iLoadProgress         : INT;
   sSelectedFirmwareFile : STRING(MAX_STRING_LENGTH); (* found firmware file, e.g. "AX5yxx_xxxx_0010_v1_05_b0009.efw" *)
END_VAR

Name

Type

Description

bBusy

BOOL

This output is set when the function block is activated, and remains set until feedback is received.

bError

BOOL

This output is set after the bBusy output has been reset when an error occurs in the transmission of the command.

iAdsErrId

UINT

Returns the ADS error code of the last executed command when the bError output is set.

iSercosErrId

UINT

Returns the Sercos error of the last executed command in the event of a set bError output.

iDiagNumber

UDINT

Returns the drive amplifier error of the last firmware update if the bError output is set.

eFwUpdateState

E_FwUpdateState

Returns the status of the firmware update (see E_FwUpdateState).

iLoadProgress

INT

Returns the progress of the actual firmware update as a percentage.

sSelectedFirmwareFile

STRING(MAX_STRING_LENGTH)

Displays the name of the firmware file being searched for.

Sample

VAR CONSTANT
    iNumOfDrives : INT := 2;
END_VAR

VAR
    bInit : ARRAY [1..iNumOfDrives] OF BOOL := 2(TRUE);
    fbFirmwareUpdate : ARRAY[1..iNumOfDrives] OF FB_SoEAX5000FirmwareUpdate_ByDriveRef;
    stPlcDriveRef AT %I* : ARRAY[1..iNumOfDrives]OF ST_PlcDriveRef;
    stDriveRef : ARRAY [1..iNumOfDrives] OF ST_DriveRef;
    sFirmwareVersion : ARRAY[1..iNumOfDrives] OF STRING(20) := 2('v1.05_b0009');
    eFwUpdateState : ARRAY[1..iNumOfDrives] OF E_FwUpdateState;
    sSelectedFirmwareFile: ARRAY [1..iNumOfDrives] OF STRING(MAX_STRING_LENGTH);
    iUpdateState : INT;
    bExecute : BOOL;
    sNetIdIPC : T_AmsNetId := '';
    sFirmwarePath  : T_MaxString := 'C:\TwinCAT\Io\TcDriveManager\FirmwarePool';
    I : INT;
    bAnyInit : BOOL;
    bAnyBusy : BOOL;
    bAnyError : BOOL;
END_VAR
CASE iUpdateState OF
0:
  bAnyInit := FALSE;
  FOR I := 1 TO iNumOfDrives DO
    IF bInit[I] THEN
       bAnyInit := TRUE;
       stDriveRef[I].sNetId := F_CreateAmsNetId(stPlcDriveRef[I].aNetId);
       stDriveRef[I].nSlaveAddr := stPlcDriveRef[I].nSlaveAddr;
       stDriveRef[I].nDriveNo   := stPlcDriveRef[I].nDriveNo;
       stDriveRef[I].nDriveType := stPlcDriveRef[I].nDriveType;
       IF (stDriveRef[I].sNetId <> '') AND (stDriveRef[I].nSlaveAddr <> 0)
           THEN bInit[I] := FALSE;
       END_IF
    END_IF
  END_FOR
  IF NOT bAnyInit AND bExecute THEN
    iUpdateState := 1;
  END_IF   
1:
    FOR I := 1 TO iNumOfDrives DO
      fbFirmwareUpdate[I](
        stDriveRef := stDriveRef[I],
        bExecute := TRUE,
        tTimeout := T#15s,
        sFirmwareVersion := sFirmwareVersion[I],
        sFirmwarePath := sFirmwarePath,
        sNetIdIPC := sNetIdIPC,
        iReqEcState := EC_DEVICE_STATE_OP,
        eFwUpdateState => eFwUpdateState[I]
      );
    END_FOR
    iUpdateState := 2;
2:
    bAnyBusy := FALSE;
    bAnyError:= FALSE;
    FOR I := 1 TO iNumOfDrives DO
        fbFirmwareUpdate[I](
          eFwUpdateState => eFwUpdateState[I],
          sSelectedFirmwareFile => sSelectedFirmwareFile[I]
        );
      IF NOT fbFirmwareUpdate[I].bBusy THEN
        fbFirmwareUpdate[I](bExecute := FALSE);
        IF fbFirmwareUpdate[I].bError THEN
          bAnyError := TRUE;
        END_IF
      ELSE
        bAnyBusy := TRUE;
      END_IF
    END_FOR
    IF NOT bAnyBusy THEN
      bExecute := FALSE;
      IF NOT bAnyError THEN
        iUpdateState := 0; (* OK *)
      ELSE
      iUpdateState := 0; (* Error *)
      END_IF
    END_IF
END_CASE