ID-range 1001000-1001249
1001082 - 1001084 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
1001085 | Drive reports an error. | |||
| Description | The SERCOS drive reports an error. Consult the documentation of the drive manufacturer for a further error diagnosis. | ||
Reaction | Class | 3 |
| |
Solution | Class | 6 |
| |
Error type | - | |||
| ||||
1001086 - 1001089 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
1001090 | Logical axis number not permitted. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001095 | Unknown ID in List 16 or 24. | |||
| Description |
| ||
Reaction | Class | - |
| |
Solution | Class | - |
| |
Error type | - | |||
| ||||
1001099 / 1001100 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
1001102 | Block-interface for manual-mode not available. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 7 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | - | ||||
| |||||
1001103 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
1001105 | The fiber-optic transmission rate is wrong. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001106 | The number of SERCOS rings is wrong. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
%3: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001107 | The option does not exist. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001108 | The time value is out of range. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
%3: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001109 | The optional AT- time value calculation not exist. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001110 | The optional digital drive driver is not available. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Corrected value [-] | |||
| |||||
Error type | - | ||||
| |||||
1001111 | Choose interrupt number is over limit. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001112 | Set of interrupt number impossible. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | - | ||||
| |||||
1001113 | Illegal computer address. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001114 | The computer address cannot be set. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
Error type | - | ||||
| |||||
1001115 | Error by interpretation of CTM-DDL. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 7 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001116 | CTM index out of range. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | - | ||||
| |||||
1001117 | List contains unknown elements. | |||
| Description | The startup list includes an unknown list element, which cannot calculated. | ||
Reaction | Class | 1 | Unknown list element will be ignored. | |
Solution | Class | 1 | Remove the unknown list element or correct the wrong entry. | |
Error type | - | |||
| ||||
1001118 | List contains unknown elements. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
1001119 | List contains unknown elements. | |||
| Description | The axis parameter list includes an unknown list element, which cannot calculated. | ||
Reaction | Class | 1 | Unknown list element will be ignored. | |
Solution | Class | 1 | Remove the unknown list element or correct the wrong entry. | |
Error type | - | |||
| ||||
1001120 | List contains unknown elements. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
1001121 | The same log. axis number is used several times. | ||||
| Description | Multiple configured axes are including the same logical axis number. The logical axis number must be explicit in the control system. | |||
Reaction | Class | 3 | Axis cannot be configured. | ||
Solution | Class | 6 | Stop of the control startup. | ||
Parameter | %1: | Logical axis number [-] | |||
Multiple used logical axis number. | |||||
%2: | Actual value [-] | ||||
Axis with this index include the same logical axis number. | |||||
%3: | Actual value [-] | ||||
Axis with this index include the same logical axis number. | |||||
Error type | - | ||||
| |||||
1001122 | Axis for duplication is internally unknown. | ||||
| Description | The given logical axis number is unknown (parameter clone_of). No duplication can be done. | |||
Reaction | Class | 3 | No transfer of the axis parameter possible. | ||
Solution | Class | 7 | Set the correct logical axis number. | ||
Parameter | %1: | Logical axis number [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
Unknown logical axis number. | |||||
Error type | 6, Error message by data transfer into control device. | ||||
| |||||
1001125 | Number of channels does not match to configuration. | ||||
| Description | For several configurations (P-STUP-00007) a set of number of channels is possible. In this case the configured number of channels does not match with the actual configuration. | |||
Reaction | Class | 1 | Correction of the entry number of channels. | ||
Solution | Class | 1 | Correction of the startup list. | ||
Parameter | %1: | Expected value [-] | |||
Expected number of channels. | |||||
%3: | Corrected value [-] | ||||
Corrected number of channels. | |||||
Error type | 6, Error message by data transfer into control device. | ||||
| |||||
1001129 | Maximum number of axes exceeded; no license available. | |||
| Description | No license available for configured number of axes. Please contact control vendor. | ||
Reaction | Class | 3 | No startup of control possible. | |
Solution | Class | 7 | Bring in missing license key or reduce number of axes. | |
Error type | - | |||
| ||||
1001130 | Maximum number of channels exceeded; no license available. | |||
| Description | No license available for configured number of channels. Please contact control vendor. | ||
Reaction | Class | 3 | No startup of control possible. | |
Solution | Class | 7 | Bring in missing license key or reduce number of channels. | |
Error type | - | |||
| ||||
1001131 | File name invalid. No external HMI object list can be used. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001132 | Invalid mode. No external HMI object list can be used. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001133 | File name invalid. No external BF-Channel object list can be used. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001134 | Mode invalid. No external BF-Channel object list can be used. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Corrected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
1001135 | List contains unknown elements. | |||
| Description | During interpretation of an IO devices list an unknown list element is detected. | ||
Reaction | Class | 1 |
| |
Solution | Class | 1 | Remove or modify the unknown list element in the corresponding list. | |
Error type | - | |||
| ||||
1001136 | No valid license for CNC export version. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 7 |
| |
Error type | - | |||
| ||||
1001137 | Valid license only for CNC export version. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 7 |
| |
Error type | - | |||
| ||||
1001138 | Invalid number format in list or permissible range of value exceeded. | |||
| Description | During interpretation of an axis parameter an invalid number format is detected or the interpreted parameter value is outside valid range. | ||
Reaction | Class | 1 | Interpretation of list is continued. The parameter value is limited to the maximum or minimum permissible value or set to zero, if the number format is invalid. | |
Solution | Class | 1 | Correct the number format in the corresponding parameter list. | |
Error type | - | |||
| ||||
1001200 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |