ID-range 292000-292249

292000

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

292001

Kinematic transformation: Division by 0.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has led to calculation error.

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check axis positions, axis configuration and parameters of kinematic transformation.

Error type

-

 

292002

Kinematic transformation: Negative root.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has lead to calculation error.

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check axis positions, correction of axis configuration and parameters of kinematic transformation.

Error type

-

 

292003

Kinematic transformation: Illegal argument for asin.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has lead to calculation error.

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA]

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check axis positions, correction of axis configuration and parameters of kinematic transformation.

Error type

-

 

292004

Kinematic transformation: Illegal argument for acos.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has led to calculation error.

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check axis positions, correction of axis configuration and parameters of kinematic transformation.

Error type

-

 

292005

Kinematic transformation: Illegal kinematic ID.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with invalid kinematic identifier.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Use valid kinematic identifier in CNC command [#KIN ID] or if selection is done by tool selection in machine parameters of tool.

Error type

-

 

292006

Kinematic transformation: Transformation not available.

 

Description

With this kinematic.type and active kinematic transformation (#RTCP ON, #TRAFO ON) a utility functionality is not supported.

Example: Use of #TOOL ORI CS command with tripod kinematic.

wrong:

%trafo
N10 KIN ID[12]
N20 #TRAFO ON
N20 #TOOL ORI CS
N30 G01 G90 X0 Y0 Z100 F2000
N40 M30

correct:

%trafo
N10 KIN ID[1]
N20 #TRAFO ON
N20 #TOOL ORI CS
N30 G01 G90 X0 Y0 Z100 F2000
N40 M30

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Do not use the utility functionality with this kinematic type.

Error type

-

 

292007

Kinematic transformation: Illegal vector.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has led to calculation error.

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check axis positions, correction of axis configuration and parameters of kinematic transformation.

Error type

-

 

292008

Kinematic transformation: Illegal angle phi.

 

Description

Moving to invalid axis positions with active kinematic transformation (#RTCP ON, #TRAFO ON).

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Move in valid axis position range.

Error type

-

 

292009

Kinematic transformation: Inadmissible number of transformation axes.

 

Description

The used CNC version does not support the selected kinematic transformation.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Contact CNC manufacturer.

Error type

-

 

292010

Kinematic transformation: Inadmissible kinematic parameter.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has led to calculation error.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check and correct parameters of kinematic transformation.

Error type

-

 

292011

Kinematic transformation: Inadmissible axis position.

 

Description

Selection of kinematic transformation (#RTCP ON, #TRAFO ON) with wrong or incomplete parameters has led to calculation error.

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Check axis positions, correction of axis configuration and parameters of kinematic transformation.

Error type

-

 

292012

Kinematic transformation: Illegal argument for ATAN.

 

Description

 

Reaction

Class

-

 

Solution

Class

-

 

Error type

-

 

292013

Kinematic transformation: Illegal argument for TAN.

 

Description

Moving to invalid axis positions with active kinematic transformation (#RTCP ON, #TRAFO ON).

If machine is not referenced this error also can occur because of wrong or invalid axis positions.

Further information to kinematic transformation see [PROG], [KITRA].

Reaction

Class

-

Depending on module where error occurs

  • Program execution stops
  • Movement stop of axis

Solution

Class

-

Move in valid axis position range.

Error type

-

 

292014

Kinematic transformation: Invalid WCS orientation.

 

Description

 

Reaction

Class

-

 

Solution

Class

-

 

Error type

-