ID-range 270000-270249
270000 / 270001 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270018 | Object does not exist. | |||
| Description | A communication object needed for startup is missing in the parameter lists for HMI-Objects or BF Channel. This error only occurs, if the startup list is changed. The new parameter lists for HMI-objects or BF Channel are not complete. | ||
Reaction | Class | 3 |
| |
Solution | Class | 7 | Setting parameter P-STUP-00024 up to P-STUP-00027 to the default values, described in [STUP]. | |
Error type | - | |||
| ||||
270021 | Transition for this mode in actual state not allowed. | |||
| Description | The selected transition is not possible in the actual operation mode. In the documentation [HLI] (operation mode) is described, which transitions are allowed. State diagram for all operation modes An easier way using the operation modes is to use an additional interface implemented called mode-state unit. The selected switch into the new mode and state will be done. All necessary transitions between the states (and the mode) is done by the control itself. | ||
Reaction | Class | 1 |
| |
Solution | Class | 1 | Correct selection of the transition, which is possible in the actual state. Change of the order in the PLC or HMI. | |
Error type | - | |||
| ||||
270022 | Unknown state or mode. | |||
| Description | The selected state in the order for switching the state or the operation mode is not known. The possible states are described in [HLI] (operation modes). | ||
Reaction | Class | 1 | The order is rejected | |
Solution | Class | 1 | Change order by HMI or PLC | |
Error type | - | |||
| ||||
270023 | Choosen mode is invalid. | |||
| Description | The chosen operation mode is not known. The operation modes are described in [HLI] (operation modes). | ||
Reaction | Class | 1 | The request is ignored | |
Solution | Class | 1 | Change of the order and new request by HMI or PLC. | |
Error type | - | |||
| ||||
270024 | Object cannot be written. | |||
| Description | The Request cannot be executed. The necessary communication object was not writeable. One cause of the error message is a multiple request, which cannot be calculated in the actual cycle. | ||
Reaction | Class | 3 | The request is ignored | |
Solution | Class | 1 | Send new request by HMI or PLC | |
Error type | - | |||
| ||||
270029 / 270030 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270031 | BF-Pin cannot connect with HLD from an axis. | |||
| Description | A BF could not be connected to the High Level Driver of the PLC interface. | ||
Reaction | Class | 3 | Command is aborted. | |
Solution | Class | 7 | Restart system. | |
Error type | - | |||
| ||||
270032 | BF-Pin cannot connect with HLD from CTM-plug. | |||
| Description | A BF could not be connected to the CTM. | ||
Reaction | Class | 3 | Command is aborted. | |
Solution | Class | 7 | Restart system. | |
Error type | - | |||
| ||||
270033 | Check reset of NC-channel without explicit order over MCM. | |||
| Description | The NC-channel was commanded to do a reset, although the MCM did not command any. | ||
Reaction | Class | 1 | Output of a warning. | |
Solution | Class | 1 | Check reset command. | |
Error type | - | |||
| ||||
270034 - 270036 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270037 | PLC-RUN-Mode: PLC must run before CNC startup. | |||
| Description | After startup of the control the cnc tests every cycle, in which control units of the HLI [HLI] enable is set or not. So the internal unit simulation is switched on or off, the HMI requests are send to the PLC or direct to the CNC. With parameter P-STUP-00032it can be selected which units will be serviced by the PLC at startup time. A later registration is not possible. It is necessary, that the PLC is started before startup of the CNC. | ||
Reaction | Class | 3 | Transition in error state, no communication with PLC possible. | |
Solution | Class | 7 | Set parameters P-STUP-00032to 0. | |
Error type | - | |||
| ||||
270039 | Initialization of work data from HLDX (in PLC_RUN_MODE) failed. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 7 |
| |
Error type | - | |||
| ||||
270040 | Initialization of work data from HLDX (in PLC_RUN_MODE) failed. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 7 |
| |
Error type | - | |||
| ||||
270041 | Initialization of work data from HLDX (in PLC_TEST_MODE) failed. | |||
| Description | The initialization of the axis specific working data of the High-Level Driver for the PLC interface failed. | ||
Reaction | Class | 3 | Command is aborted. | |
Solution | Class | 7 | Restart system. | |
Error type | - | |||
| ||||
270042 | Initialization of work data from HLDX (in PLC_TEST_MODE) failed. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 7 |
| |
Error type | - | |||
| ||||
270045 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270046 | Interpreter cannot evaluate the PLC-I/O-mapping list. | |||
| Description | There was an error during interpretation of the PLC-I/O mapping list, e.g. wrong token. | ||
Reaction | Class | 3 | Command is aborted. | |
Solution | Class | 1 | Check PLC-I/O mapping list. | |
Error type | - | |||
| ||||
270047 | Error while checking the new mapping list. | ||||
| Description | An error was detected in the parameter of the new PLC-I/O mapping list. | |||
Reaction | Class | 3 | Command is aborted. | ||
Solution | Class | 1 | Check parameter in the new PLC-I/O mapping list. | ||
Parameter | %1: | Actual value [-] | |||
Current state of the interpreter. | |||||
Error type | - | ||||
| |||||
270048 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270049 | No mapping declaration for SERCOS-Ident (output) found. | ||||
| Description | There is no mapping rule configured in the PLC-I/O mapping list for the cyclic SERCOS output ident. | |||
Reaction | Class | 3 | Command is aborted. | ||
Solution | Class | 1 | Check PLC-I/O mapping list. | ||
Parameter | %1: | Actual value [-] | |||
Incorrect SERCOS ident. | |||||
Error type | - | ||||
| |||||
270050 | No mapping declaration for SERCOS-Ident (input) found. | ||||
| Description | There is no mapping rule configured in the PLC-I/O mapping list for the cyclic SERCOS input ident. | |||
Reaction | Class | 3 | Command is aborted. | ||
Solution | Class | 1 | Check PLC-I/O mapping list. | ||
Parameter | %1: | Actual value [-] | |||
Incorrect SERCOS ident. | |||||
Error type | - | ||||
| |||||
270051 | Global transfer memory does not exist. | ||||
| Description | The number of the I/O-devices could not be read, because there was no access to the global transfer memory. | |||
Reaction | Class | 3 | Command is aborted. | ||
Solution | Class | 7 | Restart the system. | ||
Parameter | %1: | Actual value [-] | |||
Size of PLC-I/O transfer memory. | |||||
Error type | - | ||||
| |||||
270052 | The I/O-interface of the PLC cannot be allocated. | ||||
| Description | The shared memory to transport the cyclic PLC-I/O data between NC and PLC could not be allocated. | |||
Reaction | Class | 3 | Command is aborted. | ||
Solution | Class | 7 | Restart the system. | ||
Parameter | %1: | Actual value [-] | |||
Size of PLC-I/O transfer memory. | |||||
Error type | - | ||||
| |||||
270053 | CNC monitors PLC - No sign of life of PLC. | |||
| Description | The live counter of the PLC was tested cyclic by the CNC. The live counter test has failed, the PLC has exceeded the programmed runtime. The PLC has activated the runtime test and doesn’t acknowledge the execution in the programmed time. The runtime of the PLC has to be tested, the check time has to be adjusted ([HLI]). | ||
Reaction | Class | - |
| |
Solution | Class | - |
| |
Error type | - | |||
| ||||
270054 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270055 | Interpreter cannot evaluate the device list. | |||
| Description | There is an error in the parameter of the device list. | ||
Reaction | Class | 1 | Command is aborted. | |
Solution | Class | 1 | Check the parameter of the device list. | |
Error type | - | |||
| ||||
270056 / 270057 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270059 | The actual operation mode differs from the expected one. | |||
| Description | Requesting the operation mode / state switch, the actual operation mode differs from the expected one. The operation mode switch will not be executed. The values included in the mode-state unit [HLI] must be corrected. Possibilities:
| ||
Reaction | Class | 3 | The transition will not be done | |
Solution | Class | 1 | Correction of …FromMode in ModeState Unit Create new request | |
Error type | - | |||
| ||||
270060 | The actual state differs from the expected one. | |||
| Description | Requesting the operation mode / state switch, the actual state differs from the expected one. The operation mode switch will not be executed. The values included in the mode-state unit [HLI] must be corrected. Possibilities:
| ||
Reaction | Class | 3 | The transition will not be done | |
Solution | Class | 1 | Correction of …FromState in ModeState Unit Create new request | |
Error type | - | |||
| ||||
270061 | Given destination state in transition not allowed. | |||
| Description | The destination state in the transition order is not allowed or unknown. Which states are allowed in which operation mode is described in [HLI] (operation mode). State diagram of one operation mode | ||
Reaction | Class | 3 | The transition will not be executed | |
Solution | Class | 1 | Correct the destination state and start new request | |
Error type | - | |||
| ||||
270062 | Destination state could not be reached in an appropriate time. | |||
| Description | Switching in the destination state could not be done in the appropriate time. The timeout aborts the transition. | ||
Reaction | Class | 1 | The transition is not completely done. | |
Solution | Class | 1 | New request of the transition | |
Error type | - | |||
| ||||
270063 - 270069 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 6 | Command is aborted. | |
Solution | Class | 8 | Restart of NC-control necessary. | |
270070 | An error message could not be written to the HLI (channel interface). | ||||
| Description | The PLC has enabled the error message unit in the HLI (s. [HLI]). But the PLC task is too slow to get all error messages. Therefor some of the error messages get lost. To read all error messages by the PLC, the PLC-task should get higher priority and/or lower cycle time. | |||
Reaction | Class | 3 | Creating a new error message | ||
Solution | Class | 7 | The PLC-task should get higher priority and/or lower cycle time. | ||
Parameter | %1: | Actual value [-] | |||
Error-id of the missing error message | |||||
Error type | - | ||||
| |||||
270071 | An error message could not be written to the HLI (axis interface). | ||||
| Description | The PLC has enabled the error message unit in the HLI (s. [HLI]). But the PLC task is to slow to get all error messages. Therefor some of the error messages get lost. To read all error messages by the PLC, the PLC-task should get higher priority and/or lower cycle time. | |||
Reaction | Class | 3 | Creating a new error message | ||
Solution | Class | 7 | The PLC-task should get higher priority and/or lower cycle time. | ||
Parameter | %1: | Actual value [-] | |||
Error-id of the missing error message | |||||
%2: | Logical axis number [-] | ||||
| |||||
Error type | - | ||||
| |||||
270073 | No PDU-buffer for SERCOS service available. | |||
| Description | There is no PDU-buffer anymore for the PLC High Level Driver. Therefore the SERCOS service channel command cannot be posted. | ||
Reaction | Class | 3 | Command is aborted. | |
Solution | Class | 7 | Do reset. | |
Error type | - | |||
| ||||
270074 | Output of PDU for SERCOS service failed. | ||||
| Description | The PLC High Level Driver could not send the SERCOS service channel command. | |||
Reaction | Class | 3 | Command is aborted. | ||
Solution | Class | 7 | Do reset. | ||
Parameter | %1: | Logical axis number [-] | |||
| |||||
Error type | - | ||||
| |||||
270075 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270076 | CNC-reset triggered by user. | |||
| Description | A CNC-reset was activated by the HMI or PLC. This message will be created, if a transition causes a reset of the control. By analyzing this message, error events can be synchronized. Older error messages are no longer valid. | ||
Reaction | Class | - | - | |
Solution | Class | - | - | |
Error type | - | |||
| ||||
270077 | Activation job for manual mode was not processed by PLC (control unit not empty). | |||
| Description | CNC tries to forward data from another application (e.g. HMI) to the PLC. The order contains data which device (e. g. key, handwheel) commands a specific axis in manual mode. This order to link a device to an axis couldn’t sent via a control unit of the interface to the PLC within a defined number of CNC cycles, because the related control unit is occupied by a former order. The PLC application must be checked, to be sure that
See [HLI], keyword „Activation of operating device“ | ||
Reaction | Class | 3 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
270078 | Continuous jog parameter was not processed by PLC (control unit not empty). | |||
| Description | CNC tries to forward data to parametrize continuous jog to the PLC, which another application (e. g. HMI) sends. This data couldn’t be transmitted to the PLC via the interface within a defined number of CNC cycles, because the related control unit is occupied by former written parametrization data. | ||
Reaction | Class | 3 |
| |
Solution | Class | 1 | The PLC application must be checked, to be sure that
See [HLI], keyword „Programming Jog mode“ | |
Error type | - | |||
| ||||
270079 | Incremental jog parameter was not processed by PLC (control unit not empty). | |||
| Description | CNC tries to forward data to the PLC, which another application (e. g. HMI) sends, to parametrize incremental jog mode. This data couldn’t be transmitted to the PLC via the interface within a defined number of CNC cycles, because the related control unit is occupied by a former order to parametrize incremental jog mode. The PLC application must be checked, to be sure that
See [HLI], keyword „ Programming Inching mode“ | ||
Reaction | Class | 3 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
270080 | Handwheel parameter was not processed by PLC (control unit not empty). | |||
| Description | CNC tries to forward data to the PLC, which another application (e. g. HMI) sends, to parametrize handwheel mode. This data couldn’t be transferred to the PLC via the interface within a defined number of CNC cycles, because the related control unit is occupied by a former order to parametrize handwheel mode. | ||
Reaction | Class | 3 |
| |
Solution | Class | 1 | The PLC application must be checked, to be sure that
See [HLI], keyword „ Programming handwheel mode” | |
Error type | - | |||
| ||||
270081 | Key press was not processed by PLC (control unit not empty). | |||
| Description | CNC tries to forward data, about a pressed key to the PLC. The pressed key was detected within another application (e. g. HMI). The CNC couldn’t write the data within a defined number of CNC cycles into the interface to the PLC, because the related control unit is occupied by former data concerning a pressed key. | ||
Reaction | Class | 3 |
| |
Solution | Class | 1 | The PLC application must be checked, to be sure that
See [HLI], keyword „Ensuring compliance with a keystroke” | |
Error type | - | |||
| ||||
270082 | Rapid mode key press was not processed by PLC (control unit not empty). | |||
| Description | CNC tries to forward data, about a pressed rapid key to the PLC. The pressed rapid key was detected within another application (e. g. HMI). The CNC couldn’t write the data within a defined number of CNC cycles into the interface to the PLC, because the related control unit is occupied by former data transfer concerning a pressed rapid key. | ||
Reaction | Class | 3 |
| |
Solution | Class | 1 | The PLC application must be checked, to be sure that
See [HLI], keyword „Rapid traverse speed during traverse motion” | |
Error type | - | |||
| ||||
270083 / 270085 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 6 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270086 | File name is too long. | |||
| Description |
| ||
Reaction | Class | - |
| |
Solution | Class | - |
| |
Error type | - | |||
| ||||
270091 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
270092 | BF-Pin cannot connect with HLD from I/O-station. | |||
| Description | A BF could not be connected to the High Level Driver of the PLC I/O-interface. | ||
Reaction | Class | 3 | Command is aborted. | |
Solution | Class | 7 | Restart the system. | |
Error type | - | |||
| ||||
270093 | Index of PLC-I/O-station exceeds limits. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Lower limit value [-] | ||||
| |||||
%3: | Upper limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
270094 | Index of PLC-I/O-slots exceeds limits. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Lower limit value [-] | ||||
| |||||
%3: | Upper limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
270095 | Index of PLC-I/O-data exceeds limits. | ||||
| Description |
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Lower limit value [-] | ||||
| |||||
%3: | Upper limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
270096 | Trace of IPO data in zero channel configuration not possible. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
270097 | List contains unknown elements. | |||
| Description | During interpretation of the mapping list of the IO devices an unknown list element is detected. | ||
Reaction | Class | 1 |
| |
Solution | Class | 1 | Remove or modify the unknown list element in the corresponding list. | |
Error type | - | |||
| ||||
270098 - 270102 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |