ID-range 260000-260249
260001 | AT-telegram was missing two times. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Logical axis number [-] | ||||
| |||||
%3: | Actual value [-] | ||||
| |||||
%4: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260002 | MST telegram was missing two times, signal MSTMISS, MSTEARLY, MSTLATE. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Ring number [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260003 | Physical transmission is disturbed. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Ring number [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260004 | Programming error or transmission error. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Actual value [-] | ||||
| |||||
%5: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260005 | HS time-out error occurred. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Logical axis number [-] | ||||
| |||||
%3: | Status [-] | ||||
| |||||
Error type | - | ||||
| |||||
260007 | General time-out occurred. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
%3: | Logical axis number [-] | ||||
| |||||
%4: | Limit value [-] | ||||
| |||||
%5: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260008 | Selected phase is wrong, phase 1 after 0 not possible. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260009 | Selected phase is wrong, phase 2 after 1 not possible. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260010 | Selected phase is wrong, phase 3 after 2 not possible. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260011 | Selected phase is wrong, phase 4 after 3 not possible. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260012 | Selected phase does not exist. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260013 | Phase switch exceeds time-out. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
%3: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260016 | Checked address could not be found. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260017 | Phase switch to CP1 not possible (HS-TIMEOUT). Check drive addresses. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260018 | Received telegram wrong in CP1. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Logical axis number [-] | ||||
| |||||
Error type | - | ||||
| |||||
260019 | Switch back from phase 1 to phase 0 not possible. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260020 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 1 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
260021 | Received phase is wrong <value 1..3> equal to err / back / phase. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Expected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260022 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 1 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
260023 | Time slot parameter error <value 1..3> equal to ident / axis / ring. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Logical axis number [-] | ||||
| |||||
%3: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260025 | Calculation of T1.m not possible (TATAT time slot missing). | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
%3: | Logical axis number [-] | ||||
| |||||
Error type | - | ||||
| |||||
260026 | MDT cannot be sent in permitted time (T2 too big). | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
%3: | Limit value [-] | ||||
| |||||
%4: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260027 - 260030 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 1 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
260031 | Identification 0002 in SERCON 410B not found. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Expected value [-] | ||||
| |||||
%3: | Expected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260032 | Sercon 410B cannot be reset. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Expected value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260033 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 1 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
260034 | Read data are longer than commanded data length. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Expected value [-] | ||||
| |||||
%4: | Incorrect value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260035 | Received HS-bit is wrong. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260036 | In this moment the service channel are not open. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | [-] | |||
| |||||
%2: | Ident number [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Status [-] | ||||
| |||||
Error type | - | ||||
| |||||
260037 | Wrong access of element 0. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260038 | IDENT number not exist. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260039 | Wrong access of element 1. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260040 | Element of the name from IDENT does not exist. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260041 | The transfer of the name is too short. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260042 | The transfer of the name is too long. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260043 | The name cannot be changed. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260044 | In this time the name is write protect. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260045 | The transfer of the attribute is too short. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260046 | The transfer of the attribute is too long. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260047 | It is impossible to change the attribute. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260048 | In this time the attribute is write protect. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260049 | The unit element of IDENT not exist. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260050 | The transfer of the unit is too short. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260051 | The transfer of the unit is too long. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260052 | It is impossible to change the unit. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260053 | In this time the unit is write protect. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260054 | Minimum value element from IDENT does not exist. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260055 | The transfer of the minimum value is too short. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260056 | The transfer of the minimum value is too long. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260057 | It is impossible to change the minimum value. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260058 | In this time the minimum value is write protect. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260059 | Maximum value element from IDENT does not exist. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260060 | The transfer of the maximum value is too short. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260062 | It is impossible to change the maximum value. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260063 | In this time the maximum value is write protect. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260064 | The transfer of the date is too short. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260065 | It is impossible to change the date. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260066 | It is impossible to change the date. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260067 | In this time the date is write protect. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260068 | The date is under the minimum value. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260069 | The date is greater than the max. value. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260070 | Incorrect data value. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260071 | The error in service data is not code. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260074 | Bad reception by transfer of date-data, signal RDIST. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Ring number [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260075 | Transfer of MST comes be early back, signal MSTEARLY. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Ring number [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260076 | Transfer of MST comes be late back, signal MSTLATE. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Ring number [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Incorrect value [-] | ||||
| |||||
%4: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260077 | Requested address too big. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260078 | A - parameter too big. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260079 | Y - Parameter too big. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260080 | Index from a searching IDENT too big. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260081 | ||||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 1 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
260082 | Wrong element instructed. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | State [-] | ||||
| |||||
%3: | Ring number [-] | ||||
| |||||
Error type | - | ||||
| |||||
260083 | Impossible to initialize SERCOS-master. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260084 | Order from service channel by SERCOS CP under 2. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Incorrect value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Limit value [-] | ||||
| |||||
Error type | - | ||||
| |||||
260085 | Time slot parameter information. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [1 µsec] | |||
| |||||
Error type | - | ||||
| |||||
260086 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 1 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
260089 | MDT-Configuration of SERCOS telegram 7 wrong. | ||||
| Description | At least one element of the configured master data telegram (MDT) for SERCOS is not known. All configured telegram entries must be known by the CNC to be linked to the corresponding CNC element. If you want to configure elements in the drive telegram, which are not commanded by the CNC, just add this additional elements after linkage of CNC axis to physical axis. Example:
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 6 |
| ||
Parameter | %1: | Actual value [-] | |||
s. P-AXIS-00016 | |||||
Error type | - | ||||
| |||||
260090 | AT-Configuration of SERCOS telegram 7 wrong. | ||||
| Description | At least one element of the configured drive telegram (AT) for SERCOS is not known. All configured telegram entries must be known by the CNC to be linked to the corresponding CNC element. If you want to configure elements in the drive telegram, which are not linked to the CNC, just add this additional elements after linkage of CNC axis to physical axis. Example:
| |||
Reaction | Class | 3 |
| ||
Solution | Class | 7 |
| ||
Parameter | %1: | Logical axis number [-] | |||
s. P-AXIS-00016 | |||||
%2: | Actual value [-] | ||||
s. P-AXIS-00131 | |||||
Error type | - | ||||
| |||||
260091 | SERCOS, calculation of total MDT-length failed. | |||
| Description |
| ||
Reaction | Class | 3 |
| |
Solution | Class | 7 |
| |
Error type | - | |||
| ||||
260092 | Operation data write protected by a password | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260093 | Operation data is write protected, it is configured cyclically. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260094 | Invalid indirect addressing: (e.g., data container, list handling) | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260095 | Operation data is write protected, due to other settings. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260096 | Procedure command is already active. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260097 | Procedure command not interruptible. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260098 | Procedure command in current state not executable. | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260099 | Procedure command not executable (invalid / false parameters). | |||
| Description |
| ||
Reaction | Class | 1 |
| |
Solution | Class | 1 |
| |
Error type | - | |||
| ||||
260100 | Invalid slave arrangement. | ||||
| Description |
| |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Actual value [-] | ||||
| |||||
%3: | Logical axis number [-] | ||||
| |||||
Error type | - | ||||
| |||||